Plan Review Notes
Plan Review Notes For Permit 08020159
Permit Number 08020159
Review Stop P
Sequence Number 5
Notes
Date Text
2008-11-13 14:09:10THE FOLLOWING IS FROM THE PREVIOUS REVISION REVIEW...
  
 REVISION DENIED
 REFERENCE: FBC-2004 CHAPTER 1
  
 1. SHT P001 REVISION HISTORY WHEN PERMIT WAS ISSUED
 SHOWED REVISION 2 DATED 3-11-8, REVISION 3 DATED 4-3-8
 & REVISION 4 DATED 5-23-8. THE REVISION SUBMITTED
 8-25-8 SHOWS REVISION 1 DATED 2-13-8, REVISION 2 DATED
 3-11-8 & REVISION 3 DATED 7-11-8. THE BUILDING OFFICIAL
 MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. SECTION
 106.1.3. ALL REVISIONS SHALL BE CLOUDED AND INDICATED
 WITH A REVISION NUMBER. THE REVISION NUMBERS SHALL BE
 SEQUENTIAL AND THE PREVIOUS REVISION HISTORY SHALL NOT
 BE DELETED, CHANGED, OR ALTERED.
  
 2. SHT P201 REVISION HISTORY WHEN PERMIT WAS ISSUED
 SHOWED REVISION 1 DATED 2-13-8, REVISION 2 DATED 3-11-8
 & REVISION 4 DATED 5-23-8. THE REVISION SUBMITTED
 8-25-8 SHOWS THE SAME REVISION NUMBER & DATE FOR
 REVISIONS 1 & 2, DOES NOT SHOW A REVISION 4 AND NOW
 SHOWS REVISION 3 DATED 7-11-8. THE BUILDING OFFICIAL
 MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. SECTION
 106.1.3. ALL REVISIONS SHALL BE CLOUDED AND INDICATED
 WITH A REVISION NUMBER. THE REVISION NUMBERS SHALL BE
 SEQUENTIAL AND THE PREVIOUS REVISION HISTORY SHALL NOT
 BE DELETED, CHANGED, OR ALTERED.
  
 COMMENTS FOR THIS REVISION:
  
 1A. THE REVISION SUBMITTED 10-24-08 DOES NOT ADDRESS
 THESE ISSUES BROUGHT UP IN COMMENT 1. SECTION 106.1.3.
  
 2A. THE REVISION SUBMITTED 10-24-08 DOES NOT ADDRESS
 THESE ISSUES BROUGHT UP IN COMMENT 2. SECTION 106.1.3.
  
 3. SHT P201 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THE DRINKING FOUNTAIN ON THE FLOOR PLAN IS
 NOT SHOWN ON THE RISER DIAGRAM & THE 3/4" SUPPLY LINE
 TO THE S-1 SINK IN MRI EXAM ROOM 0107 IS INDICATED AS
 1/2" ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTIONS
 106.1.3, 106.3.5.1.3, 601.1 & 701.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved