| 2008-09-15 12:05:57 | |
| | ** DENIED REVIEW OF REVISIONS** |
| | |
| | 1) NOTE: PLANS DO NOT INDICATE ANY REVISIONS. THE PLANS |
| | NEED TO INDICATE CHANGES BY CLOUDS/TRIANGLES. THE TITLE |
| | BLOCKS NEED TO REFLECT THESE SAME NUMERICAL |
| | DESIGNATIONS/CHANGES. THE TITLE BLOCK AT THIS TIME |
| | INDICATES * RE-ISSUED FOR PERMIT** HOWEVER PLANS WERE |
| | ISSUED FOR PERMIT PREVIOUSLY. |
| | 106.5, 106.1.1 ADMINISTRATIVE SECTION AS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH FOR CLARITY OF CONSTRUCTION |
| | DOCUMENTS AND RECORD PLANS COORDINATION. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |