Plan Review Notes
Plan Review Notes For Permit 08020159
Permit Number 08020159
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-05-20 12:44:00*****PROVISO*****
  
  
 5.DOOR(S) LEADING DIRECTLY TO THE MAIN LOBBY CORRIDOR
 SHALL BE AN APPROVED, LISTED, AND LABELED FIRE DOOR &
 ASSEMBLY IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA
 80.ADD COMMENT TO GENERAL NOTES ON SHEET A0201
  
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 ABOVE COMMENT AND THE OTHERS PLAN REVIEWERS COMMENTS
 HAVE BEEN ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722