Plan Review Notes
Plan Review Notes For Permit 08020159
Permit Number 08020159
Review Stop E
Sequence Number 2
Notes
Date Text
2008-05-19 15:18:57** DENIED2ND AUDIT**
  
 ** PLEASE SEE SOME ITEMS STILL REMAIN FROM PREVIOUS
 AUDIT.
  
 1) NOTE: PLEASE SEE AFFIDAVITS ARE NOW ONLY BEING
 SUBMITTED. PLEASE SEE THESE ARE BEING MADE OUT TO
 BALFOUR CONCORD. THE CONTRACTOR ON THIS PROJECT IS
 BALFOUR/BEATTY.
 PLEASE COORDINATE.
 PLEASE ALSO SEE NOTICE TO BUILDING OFFICIAL SUBMITTED
 WHICH IS IN FACT PHOTO-COPIES AND ARE NOT ORIGINAL.
 THESE CONTAIN STAMPS *REVIEWED FOR COMPLIANCE8 FROM THE
 PRIVATE PROVIDER.
 PLEASE ONLY INCLUDE ORIGINAL DOCUMENTS AND PLEASE BE
 SURE TO FILL OUT WITH THE CORRECT CONTRACTOR.
  
 2) NOTE: PLEASE SEE MISSING MAXIMUM TIMES ON OVER RIDES
 AND OCCUPANCY SENSOR DEVICES. THE RESPONSE MENTIONS TO
 SEE E-100 AND E200 HOWEVER THE REVISED DEVICES, OVER
 RIDES AND OCCUPANCY SENSOR SWITCHES DO NOT INDICATE ANY
 TIMES.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AS REQUESTED ON PREVIOUS AUDIT. PLEASE SEE THE
 *LIGHTING CALCULATIONS* SUBMITTED ON 81/2 BY 11 SHEETS
 ARE LIGHTING LEVELS BASED ON PHOTO-METRICS. THIS IS NOT
 LIGHTING PERFORMANCE CALCULATIONS. PLEASES KNOW THESE
 ARE THE SAME SHEETS WHICH WERE GONE OVER IN A MEETING
 HELD PREVIOUS TO PLANS BEING RESUBMITTED.PLEASE SEE
 THE LIGHTING LEVELS SHOWN ON E200 ARE NOT COMPLETE. NO
 FIXTURE LEGEND ETC. SOME OF THE LEVELS AS NOTED EXCEED
 MAXIMUM LEVELS PERMITTED IN THE FLORIDA BUILDING CODE.
 PLEASE SEE 13-415.2.ABC.1.1, .1.2.
 ** THE OTHER SUBMIT DOCUMENTS DO NOT CONTAIN ANY DESIGN
 PROFESSIONAL, TITLE BLOCKS, SIGNED, DATED, SEALED,
 ADDRESS ETC ETC.
 PLEASE SUBMIT COMPLETED DOCUMENTS SIGNED, DATED AND
 SEALED BY THE DESIGN PROFESSIONAL OF RECORD.
  
 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS ONLY A NOTICE
 GIVEN AT THIS TIME.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER