| 2008-02-08 21:01:19 | AUDIT DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL ARCHITECTURAL SHEETS SHALL SHOW THE BUSINESS |
| | LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), IN THE |
| | TITLE BLOCK PER FAC 61G1-16.004 & FS 481.219, 481.2055. |
| | (SEE ATTACHED SHEET FROM FLORIDA DBPR WEBSITE). |
| | |
| | 2. SHTS G0207 & A0201 P. TOILET ROOM 0100. PER SECTION |
| | 11-4.22.2(1) DOORS SHALL NOT SWING INTO THE CLEAR FLOOR |
| | SPACE OF ANY REQUIRED FIXTURE. THE DOOR IS SHOWN |
| | SWINGING INTO THE CLEAR FLOOR SPACE OF THE WATER |
| | CLOSET. |
| | |
| | 3. SUBMIT DETAILS FOR THE TOILET ROOM SHOW COMPLIANCE |
| | WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22 WITH ALL |
| | SUBSECTIONS. SHOW DETAILS ON AN ELEVATION WHICH SHOW |
| | THE WATER CLOSET 18" OFF THE WALL TO THE CENTERLINE OF |
| | THE FIXTURE AS WELL AS THE LAV MIN. 15" OFF THE WALL TO |
| | THE CENTERLINE OF THE FIXTURE. FIGURES 28 & 32. |
| | |
| | 4. SHT A0201 DETAIL 16A STATES "CT2 ALONG WETWALL" - |
| | "ALL OTHER WALLS IN TOILET ROOM TO BE PAINTED". PER |
| | SECTION 1210.2 WALLS WITHIN 2FT OF WATER CLOSETS SHALL |
| | HAVE A SMOOTH, HARD, NONABSORBENT SURFACE TO A HEIGHT |
| | OF 4FT. PAINTED WALLS DO NOT COMPLY FOR THE WALL AT THE |
| | SIDE OF THE WATER CLOSET. PLEASE SHOW COMPLIANCE. |
| | |
| | 5. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED. |
| | PLEASE SHOW THE LOCATION OF THE REQUIRED DRINKING |
| | FOUNTAIN. |
| | |
| | 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING |
| | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS |
| | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| | WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | 7. SHT P201 THE DOMESTIC WATER RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. OFFSETS ARE NOT SHOWN, BACKFLOW |
| | AND WATER LINE FOR THE EMERGENCY BYPASS IS NOT SHOWN. |
| | SUBMIT THE DOMESTIC WATER RISER DIAGRAM IN ISOMETRIC |
| | FORM THAT REFLECTS THE FLOOR PLAN. SECTIONS 106.1.1 AND |
| | 106.3.5.1.3. |
| | |
| | 8. SHT P201 STORM DRAIN MODIFICATION DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLANS. SECTION 106.1.1. PLEASE SUBMIT |
| | A STORM RISER DIAGRAM THAT REFLECTS THE FLOOR PLAN WITH |
| | THE OFFSETS ETC. |
| | |
| | 9. PRIVATE PROVIDER AFFIDAVIT PROJECTS-IN ADDITION |
| | TO THE SIGNED AFFIDAVIT FROM THE PRIVATE PROVIDER, WE |
| | MUST ALSO CHECK TO SEE THAT THE OWNER HAS SIGNED AN |
| | OWNER ACKNOWLEDGEMENT LETTER PER FLORIDA STATUTE, |
| | SECTION 553.791(4)(C).THE LETTER IS THE MEANS BY |
| | WHICH THE OWNER ACKNOWLEDGES THAT THEY ARE AWARE THAT |
| | THEIR PROJECT IS BEING REVIEWED (AND IF RELEVANT, |
| | INSPECTED) UNDER THE PRIVATE PROVIDER PROVISIONS OF |
| | FLORIDA STATUTE. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |