Plan Review Notes
Plan Review Notes For Permit 08020159
Permit Number 08020159
Review Stop P
Sequence Number 1
Notes
Date Text
2008-02-08 21:01:19AUDIT DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS SHALL SHOW THE BUSINESS
 LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), IN THE
 TITLE BLOCK PER FAC 61G1-16.004 & FS 481.219, 481.2055.
 (SEE ATTACHED SHEET FROM FLORIDA DBPR WEBSITE).
  
 2. SHTS G0207 & A0201 P. TOILET ROOM 0100. PER SECTION
 11-4.22.2(1) DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE OF ANY REQUIRED FIXTURE. THE DOOR IS SHOWN
 SWINGING INTO THE CLEAR FLOOR SPACE OF THE WATER
 CLOSET.
  
 3. SUBMIT DETAILS FOR THE TOILET ROOM SHOW COMPLIANCE
 WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22 WITH ALL
 SUBSECTIONS. SHOW DETAILS ON AN ELEVATION WHICH SHOW
 THE WATER CLOSET 18" OFF THE WALL TO THE CENTERLINE OF
 THE FIXTURE AS WELL AS THE LAV MIN. 15" OFF THE WALL TO
 THE CENTERLINE OF THE FIXTURE. FIGURES 28 & 32.
  
 4. SHT A0201 DETAIL 16A STATES "CT2 ALONG WETWALL" -
 "ALL OTHER WALLS IN TOILET ROOM TO BE PAINTED". PER
 SECTION 1210.2 WALLS WITHIN 2FT OF WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE TO A HEIGHT
 OF 4FT. PAINTED WALLS DO NOT COMPLY FOR THE WALL AT THE
 SIDE OF THE WATER CLOSET. PLEASE SHOW COMPLIANCE.
  
 5. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE SHOW THE LOCATION OF THE REQUIRED DRINKING
 FOUNTAIN.
  
 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 7. SHT P201 THE DOMESTIC WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. OFFSETS ARE NOT SHOWN, BACKFLOW
 AND WATER LINE FOR THE EMERGENCY BYPASS IS NOT SHOWN.
 SUBMIT THE DOMESTIC WATER RISER DIAGRAM IN ISOMETRIC
 FORM THAT REFLECTS THE FLOOR PLAN. SECTIONS 106.1.1 AND
 106.3.5.1.3.
  
 8. SHT P201 STORM DRAIN MODIFICATION DIAGRAM DOES NOT
 REFLECT THE FLOOR PLANS. SECTION 106.1.1. PLEASE SUBMIT
 A STORM RISER DIAGRAM THAT REFLECTS THE FLOOR PLAN WITH
 THE OFFSETS ETC.
  
 9. PRIVATE PROVIDER AFFIDAVIT PROJECTS-IN ADDITION
 TO THE SIGNED AFFIDAVIT FROM THE PRIVATE PROVIDER, WE
 MUST ALSO CHECK TO SEE THAT THE OWNER HAS SIGNED AN
 OWNER ACKNOWLEDGEMENT LETTER PER FLORIDA STATUTE,
 SECTION 553.791(4)(C).THE LETTER IS THE MEANS BY
 WHICH THE OWNER ACKNOWLEDGES THAT THEY ARE AWARE THAT
 THEIR PROJECT IS BEING REVIEWED (AND IF RELEVANT,
 INSPECTED) UNDER THE PRIVATE PROVIDER PROVISIONS OF
 FLORIDA STATUTE.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  