| 2008-02-15 16:13:11 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. M100: THE FLOOR PLAN SHOWS EXHAUST FAN AND RELATED |
| | DUCT BEING RELOCATED TO A SPACE OUTSIDE THIS TENANT |
| | SPACE. THE NEWLY ROUTED EXHAUST DUCT IS SHOWN |
| | PENETRATING FIRE-RESISTANCE RATED WALLS AT MULTIPLE |
| | LOCATIONS WITH NO OPENING PROTECTIVES SHOWN AT THESE |
| | LOCATIONS. DUCT PENETRATIONS OF FIRE RESISTANCE RATED |
| | ASSEMBLIES SHALL BE PROTECTED WITH OPENING PROTECTIVES |
| | IN ACCORDANCE WITH FBC, M 607.5. |
| | |
| | 2. PROVIDE DETAIL FOR THE THROUGH-PENETRATION FIRESTOP |
| | SYSTEM TO BE USED FOR PIPE PENETRATIONS OF RATED WALLS |
| | IN ACCORDANCE WITH FBC 712.3. THIS WOULD INCLUDE |
| | CHILLED WATER, CONDENSER WATER AND POTENTIALLY |
| | CONDENSATE PIPING. |
| | |
| | 3. MRI MACHINES GENERALLY WILL HAVE AN EMERGENCY VENT |
| | FOR THE LIQUID NITROGEN COOLING SYSTEM. WILL THIS |
| | SYSTEM HAVE AN EMERGENCY VENT AND IF SO, WHERE WILL IT |
| | BE LOCATED? PG P201 SHOWS AN EMERGENCY RELIEF VENT FOR |
| | THE CT SCANNER BUT NOT THE MRI. PROVIDE MANUFACTURER?S |
| | INSTRUCTIONS FOR THE EMERGENCY VENTING REQUIREMENTS FOR |
| | THIS EQUIPMENT. FBC 106.1.1. ALSO, THESE VENTING |
| | SYSTEMS WILL BE REVIEWED AND INSPECTED BY THE |
| | MECHANICAL DISCIPLINE. PLEASE SHOW THESE SYSTEMS IN THE |
| | MECHANICAL SECTION OF THE PLANS. PROVIDE DETAIL AS TO |
| | HOW AND WHERE THESE EMERGENCY VENTS WILL TERMINATE. ARE |
| | THEY NEAR ANY WALKWAYS, PROPERTY LINES OR ADJACENT |
| | BUILDINGS? PROVIDE SUFFICIENT INFORMATION TO |
| | DEMONSTRATE COMPLIANCE WITH FBC, M 401.5.2 AND |
| | MANUFACTURER?S INSTRUCTIONS. |
| | |
| | 4. PRIVATE PROVIDER AFFIDAVIT PROJECTS ? IN ADDITION TO |
| | THE SIGNED AFFIDAVIT FROM THE PRIVATE PROVIDER, WE MUST |
| | ALSO CHECK TO SEE THAT THE OWNER HAS SIGNED AN OWNER |
| | ACKNOWLEDGEMENT LETTER PER FLORIDA STATUTE, SECTION |
| | 553.791(4)(C). THE LETTER IS THE MEANS BY WHICH THE |
| | OWNER ACKNOWLEDGES THAT THEY ARE AWARE THAT THEIR |
| | PROJECT IS BEING REVIEWED (AND IF RELEVANT, INSPECTED) |
| | UNDER THE PRIVATE PROVIDER PROVISIONS OF FLORIDA |
| | STATUTE. |
| | |
| | NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH A |
| | DESCRIPTION OF HOW THE COMMENT HAS BEEN ADDRESSED (OR |
| | WHY IT HAS NOT) AS WELL AS WHERE THE RELEVANT |
| | INFORMATION CAN BE FOUND. ALSO, PLEASE RETURN ONE SET |
| | OF OLD/VOIDED PLANS FOR REFERENCE. THESE STEPS WILL |
| | HELP TO ENSURE A TIMELY REVIEW UPON RESUBMISSION. |
| | |