2008-02-14 12:40:59*****DENIED*****
  
  
 1.THE SUITE NUMBER SHALL BE INCLUDED IN THE ADDRESS
 LOCATED IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.IN ADDITION TO THE 2004 FLORIDA FIRE PREVENTION
 CODE AS LISTED IN THE CODE NOTES ON SHEET G0201, NFPA
 101- LIFE SAFETY CODE - 2003 EDITION SHALL BE
 REFERENCED.
  
 4.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO
 THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SITES ON
 THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 3" IN HEIGHT.
  
 5.DOOR(S) LEADING DIRECTLY TO THE CORRIDOR SHALL BE
 AN APPROVED, LISTED, AND LABELED FIRE DOOR & ASSEMBLY
 IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 80.
  
 6.SPECIFY THE INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.
  
 7.PLEASE CLARIFY OR CORRELATE THE NUMBER OF CORRIDOR
 EMERGENCY LIGHTING FIXTURES.ON SHEET E200 - 3 DEVICES
 SHOWN;ON SHEET E201 - 4 DEVICES SHOWN, BUT 6 DEVICES
 ARE LISTED IN THE DESIGN CRITERIA LUMINAIRES USED
 INFORMATION DATA.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  