| Date |
Text |
| 2008-02-11 10:38:25 | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE THE REQUIRED AFFIDAVIT AS REQUIRED |
| | PER FS 553.791(4)(C) WAS NOT SUBMITTED. |
| | |
| | 2) NOTE: REMOVED NOTED |
| | |
| | 3) NOTE: PLEASE SEE THE PLANS NEED TO CONTAIN THE |
| | FOLLOWING RELEVANT CODES STATED FOR DESIGN. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ** SOME MAY ALREADY BE SHOWN HOWEVER NOT ALL. PLEASE BE |
| | AWARE OF ANY CODES REQUIRED BY OTHER TRADE REVIEWERS. |
| | PLEASE ALSO SEE THE CODES ARE NEEDED ON ELECTRICAL AS |
| | WELL. |
| | FBC 106.5, 106.1.2, FS 553.73 |
| | |
| | 4) NOTE: PLEASE SEE THAT THE SUITE/UNIT NUMBER IS |
| | REFLECTED ON TITLE BLOCKS. PLEASE KNOW IF ANY |
| | PARTICULAR SHEET DOES NOT NEED TO BE REVISED FOR CODE |
| | COMPLIANCE, THEN THIS MAY BE HAND PRINTED ON SHEETS. |
| | FBC 106.1.2, 106.5 |
| | FAC 61G1-16.004, FAC 61G15-23.002 |
| | |
| | 5) NOTE: PLEASE SEE MISSING LICENSE INFORMATION ON |
| | TITLE BLOCKS FOR URS CORPORATION. PLEASE SEE MISSING |
| | CERTIFICATE OF AUTHORIZATION NUMBER FOR ARCHITECTURAL |
| | FIRM WHICH IS REQUIRED PER FS 481.219 AND TO BE ON |
| | PLANS PER FAC 61G1-16.004 |
| | PLEASE ALSO SEE FS 471.023 AND FAC 61G15-23.002 WHICH |
| | REQUIRES CERTIFICATE OF AUTHORIZATION NUMBER FOR |
| | ENGINEERING BUSINESS AS WELL. |
| | |
| | 6) NOTE: PLEASE PLACE NOTES ON PLANS FOR REQUIRED |
| | GROUNDING AND INSTALLATION OF SYSTEMS PER NEC 517. |
| | PLEASE SEE 517.1 COMMENTARIES WHICH ARE QUOTED BELOW: |
| | |
| | *THE REQUIREMENTS OF ARTICLE 517 ARE INTENDED TO APPLY |
| | TO ALL TYPES OF HEALTH CARE FACILITIES. THE |
| | REQUIREMENTS FOR EACH TYPE OF HEALTH CARE FACILITY ARE |
| | NEVERTHELESS INTENDED TO BE APPLIED IN A VERY SPECIFIC |
| | MANNER. FOR EXAMPLE, IN A SUITE OF DOCTORS' OFFICES |
| | WITHIN AN OFFICE BUILDING, A DOCTOR'S BUSINESS OFFICE |
| | WOULD BE TREATED AS AN ORDINARY OCCUPANCY AND WOULD BE |
| | REQUIRED TO MEET ONLY THE APPLICABLE PORTIONS OF OTHER |
| | PARTS OF THIS CODE. HOWEVER, THE EXAMINING ROOMS |
| | ATTACHED TO THE DOCTOR'S BUSINESS OFFICE WOULD BE |
| | REQUIRED TO MEET THE PROVISIONS OF PART II AND 517.45 |
| | IN ARTICLE 517.* |
| | PLEASE ALSO BE AWARE ANY UNDER GROUND SLAB AREAS TO |
| | EQUIPMENT SHALL BE RMC, IMC OR OTHER APPROVED CONDUIT |
| | SYSTEM. 517.13, 250, AND SEE USES PERMITTED IN CHAPTER |
| | 13 FOR CONDUITS. |
| | |
| | 7) NOTE: PLEASE SEE ELECTRICAL CLOSET APPEARS DOOR WILL |
| | NOT MEET 110.26 FOR MINIMUM CLEARANCES. |
| | PLEASE ADJUST PANEL LOCATION. |
| | PLEASE ALSO KNOW THIS SHALL BE A DEDICATE ELECTRICAL |
| | SPACE WITH NOT STORAGE. 110.26, 240.24, 408.17 |
| | |
| | 8) NOTE: PLEASE CLARIFY MINIMUM LEVELS FOR SOUNDING |
| | DEVICES FOR ADA COMPLIANCE ARE LOCATED PER FBC |
| | 11-4.28.1, .2 AND .3. PLEASE BE SURE TO LIST THE |
| | DEVICES AND ALL MINIMUM LEVELS FOR ADA COMPLIANCE. THE |
| | MINIMUM LEVELS AND LOCATIONS ON F SHEETS APPEAR TO BE |
| | OK, HOWEVER ONLY NEED TO VERIFY SOUNDING. |
| | PLEASE BE AWARE OF ANY REVIEW COMMENTS FROM FIRE |
| | MARSHAL WHICH MAY AFFECT SAME SHEETS. |
| | |
| | 9) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE INDICATE ALL MAXIMUM TIMES ON DEVICES. |
| | PLEASE SEE MISSING LIGHTING CONTROLS REQUIRED IN ALL |
| | SPACES THAT DO NOT MEET EXCEPTIONS AS STATED IN THE |
| | CODE. |
| | FAC 61G15-33.004 |
| | |
| | 10) NOTE: PLEASE SEE 13-415.2 FOR MISSING LIGHTING |
| | PERFORMANCE CALCULATIONS. |
| | PLEASE ALSO SEE 13-415.2.ABC.1.1, .1.2. |
| | FAC 61G15-33.004 |
| | |
| | 11) NOTE: PLEASE SUBMIT UPDATE LOADS ON MSB FOR NEW |
| | PANEL LOAD ALONG WITH EXISTING. |
| | 220.87, 220. |
| | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 12) NOTE: PLEASE PROVIDE MORE INFORMATION PER |
| | 517.71-517.78. |
| | SOME ITEMS ARE SHOWN HOWEVER NOT ALL. |
| | |
| | 13) NOTE: PLEASE KNOW THESE PLANS MAY BE REFERENCED FOR |
| | LOW VOLTAGE SCOPE OF WORK HOWEVER THE LV WILL BE |
| | REQUIRED TO BE UNDER SEPARATE PERMIT. THIS IS NOTED FOR |
| | INFORMATION ONLY AT THIS TIME. |
| | |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION, F THERE ARE ANY |
| | QUESTIONS; PLEASE DO NOT HESITATE IN CONTACTING THIS |
| | OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |