| Date |
Text |
| 2008-12-03 12:49:54 | |
| | ** DENIED 4TH REVIEW** |
| | |
| | *THERE ARE STILL COMMENTS FROM PREVIOUS REVIEW WHICH |
| | HAVE NOT BEEN ADDRESSED. |
| | |
| | |
| | |
| | 1) NOTE: THE BASE BUILDING IS NOT COMPLETE AND STILL |
| | DOES NOT HAVE A CERTIFICATE OF COMPLETION. THE BASE |
| | BUILDING AS GIVEN ON THE LAST THREE REVIEWS ARE STILL |
| | IS STILL UNDER THE RESPONSIBILITY OF THE BASE BUILDING |
| | DESIGN TEAM. ALL PLANS FOR ALL TRADES WHETHER OR NOT |
| | COMMENT IS MADE BY ANY OTHER TRADE REVIEW ARE REQUIRED |
| | TO CONTAIN A *SHOP DRAWING REVIEW STAMP* FROM THE BASE |
| | BUILDING DESIGNERS BEFORE PERMIT MAY BE ISSUED. |
| | WHEN WORK ON THE SAME BUILDING AND SAME SPACE IS TO |
| | TAKE PLACE A LETTER OF UNDERSTANDING BETWEEN EACH |
| | LICENSE CONTRACTOR IS REQUIRED. |
| | FS 481, 471, 489 |
| | |
| | 2) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | ARE STILL NOT CODE COMPLIANT. THERE ARE STILL SPECIFIC |
| | ITEMS WHICH WERE GIVEN ON THE PREVIOUS REVIEWS WHICH |
| | ARE STILL THE EXACT SAME. |
| | ONE EXAMPLE IS THE EXTERIOR LIGHTING WHICH IS STILL IN |
| | FACT *BLANK* ON THE INPUT DATA REPORT. THERE IS NO |
| | LIGHTING AT ALL PLACED INTO THE INPUT DATA REPORT. THIS |
| | IS NOT POSSIBLE WHEN THE PLANS DO HAVE EXTERIOR |
| | LIGHTING SHOWN. PLEASE SEE 13-415.2.ABC.1.3. THE |
| | SUBMITTED METHOD OF CALCULATION IS A METHOD FOR *WHOLE |
| | BUILDING*. THIS METHOD CAN NOT BE USED UNLESS ALL |
| | COMPONENTS REQUIRED FOR MINIMUM COMPLIANCE IS |
| | MET.13-400.3.A. |
| | PLEASE SEE ANOTHER EXAMPLE IS *PIPING* ON THE IDR. THIS |
| | IS ALSO BLANK. THIS IS ALSO NOT POSSIBLE WHEN SECTION |
| | 13-411.1.ABC.2 REQUIRES MINIMUM VALUES. |
| | |
| | ** PLEASE BE SURE TO GO OVER CALCULATIONS AND PLANS. |
| | PLEASE BE SURE TO COORDINATE ALL ITEMS AS PREVIOUSLY |
| | REQUESTED.13-400.3.A, 13-101.1.6, 13-101.1, |
| | 13-415.2.ABC.1.1,.1.2. |
| | |
| | 3) NOTE: PANEL BOARD *A* STILL NOTES THE ENTIRE SECTION |
| | ONE AND TWO AS EXISTING WHEN RISER SHOWS SECTION TWO AS |
| | NEW. IN SECTION ONE OF PANEL THIS SHOWS A SEPARATE |
| | 100AMP FEED TO NEW SECTION. |
| | THIS WOULD NOT BE A SECTION TWO PANEL IF IT HAS A |
| | SEPARATE SUB-PANEL BREAKER AND FEEDERS. THIS WOULD BE A |
| | SUB PANEL. |
| | A SECTION TWO FOR ANY PANEL BOARD IS TYPICALLY |
| | EQUIPMENT WITH THE SAME RATING WITH FEED-THRU LUGS. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |