Plan Review Notes
Plan Review Notes For Permit 08020137
Permit Number 08020137
Review Stop E
Sequence Number 3
Notes
Date Text
2008-10-28 10:06:39 
 ** DENIED 3RD REVIEW**
  
  
 1) NOTE: PLEASE KNOW THE SHELL PERMITTED BUILDING IS
 NOT COMPLETE AS OF THIS REVIEW. UNTIL THE SHELL PERMIT
 HAS BEEN CLOSED OUT THE BASE BUILDING DESIGN TEAM IS
 RESPONSIBLE FOR BUILDING AND SHALL STAMP SAID BUILD OUT
 PLANS AS *SHOP DRAWINGS*.
  
  
 2) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE NOT COMPLIANT AND DO NOT CONFORM TO THE
 REQUIREMENTS OF THE FLORIDA ENERGY CODE FOR METHOD *A*
 *WHOLE* BUILDING.
 THERE ARE SOME ITEMS STILL SHOWN BLANK WITH NO
 INFORMATION ON THE INPUT DATA REPORT. THIS IS NOT
 POSSIBLE FOR THIS BUILDING AND USING A WHOLE BUILDING
 METHOD.
 ONE EXAMPLE IS THE EXTERIOR LIGHTING WHICH IS BLANK.
 ANOTHER WOULD BE THE NO DOORS.
 ANOTHER WOULD BE NO VALUE/KW FOR WATER HEATER.
  
  
 ***ADDRESS ON THE CALCULATIONS STILL SHOW A LOCATION
 WHICH IS NOT WITHIN THIS JURISDICTION.
 PLEASE BE SURE TO COMPLETE THE CALCULATIONS WITH ALL
 COMPONENTS.
 PLEASE SEE 13-415.2.ABC.1.1,.1.2 AND .1.3.
 PLEASE SEE 13-400.3.A, 13-101.1.6, 13-101.1.1 ETC
 FAC 61G1-16.004, 61G15-23.002
 FBC 106.1.1, 106.5
  
 3) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO FAC
 61G15-23.002 WHICH REQUIRES ALL INFORMATION AS LISTED
 ON THE TITLE BLOCKS FOR ENGINEERING FIRMS. THE FLORIDA
 STATUTE WHICH REQUIRES THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR SAID FIRM IS FS 471.023. THE TITLE BLOCKS
 WERE REVISED HOWEVER THEY LIST THE * FLORIDA STATUTE
 NUMBER 471.023 INSTEAD OF THE FIRM LICENSE NUMBER. ????
 PLEASE KNOW IF THIS HAD BEEN THE ONLY COMMENT THE TITLE
 BLOCKS WOULD HAVE BEEN REDLINED WITH THE CORRECT
 LICENSE INFORMATION AS THE MECHANICAL AND PLUMBING
 REVIEWERS HAVE DONE. AS THIS IS NOT THE ONLY COMMENT
 PLEASE REVISE THE PLANS CORRECTLY WITH THE REQUIRED
 NUMBER.
 THE FLORIDA ADMINISTRATIVE CODES GIVEN REQUIRE THE
 PRINTED NAME AND PRINTED LICENSE NUMBER OF ENGINEER AND
 THE PRINTED FIRM LICENSE NUMBER ALONG WITH ADDRESS ETC.
 ** THIS IS REQUIRED FOR ALL TRADES AND ON ALL SHEETS
 WHETHER OR NOT COMMENT HAS BEEN MADE BY THAT TRADE.
 THIS HAS BEEN A REQUIREMENT SINCE 1977.
  
 4) NOTE: PLEASE SEE CIRCUITING WILL BE REQUIRED TO BE
 REVISED TO BE SPECIFIC.
 HOW CAN THE PANEL SCHEDULE LABEL ALL AS EXISTING
 PANELBOARD WHEN THE RISER SAYS NEW?
 408.4
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  