| Plan Review Notes For Permit 08020137 |
| Permit Number |
08020137 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-09-08 10:09:48 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | | | | 1) MECHANICAL PLAN M-1 GENERAL NOTES #1 REFERENCES THE | | | 2006 FLORIDA INTERNATIONAL MECHANICAL CODE, ETC. THE | | | STATE OF FLORIDA AND THE CITY OF W. P. B. IS UNDER THE | | | 2004 FLORIDA BUILDING CODE WITH THE 2007 SUPPLEMENTS. | | | PLEASE CORRECT PLAN TO REFLECT THIS. | | | | | | 2) VENTILATION AIR CALCULATIONS NOTE #3 STATES NET | | | SQUARE FOOTAGE DOES NOT INCLUDE DISPLAY AREA OR BEDS | | | WHICH ARE NOT OCCUPIABLE SPACES. AS THERE IS NO | | | PERMANENT STRUCTURE BETWEEN THE SPACES THEN ALL THE | | | FLOOR SPACE MUST BE INCLUDED IN THE CALCULATIONS. SEE | | | 2004 FBC/M TABLE 403.3 FOOT NOTE 'E'. IF YOU CAN | | | REFERENCE A FLORIDA BUILDING CODE THAT SUPPORTS YOUR | | | CALCULATION PLEASE SUBMIT IT IN DETAIL, BE SPECIFIC | | | | | | 3) SEE BUILDING REVIEW NOTES 3 AD 8, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|