Date Text
2008-09-08 10:09:48PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) MECHANICAL PLAN M-1 GENERAL NOTES #1 REFERENCES THE
 2006 FLORIDA INTERNATIONAL MECHANICAL CODE, ETC. THE
 STATE OF FLORIDA AND THE CITY OF W. P. B. IS UNDER THE
 2004 FLORIDA BUILDING CODE WITH THE 2007 SUPPLEMENTS.
 PLEASE CORRECT PLAN TO REFLECT THIS.
  
 2) VENTILATION AIR CALCULATIONS NOTE #3 STATES NET
 SQUARE FOOTAGE DOES NOT INCLUDE DISPLAY AREA OR BEDS
 WHICH ARE NOT OCCUPIABLE SPACES. AS THERE IS NO
 PERMANENT STRUCTURE BETWEEN THE SPACES THEN ALL THE
 FLOOR SPACE MUST BE INCLUDED IN THE CALCULATIONS. SEE
 2004 FBC/M TABLE 403.3 FOOT NOTE 'E'. IF YOU CAN
 REFERENCE A FLORIDA BUILDING CODE THAT SUPPORTS YOUR
 CALCULATION PLEASE SUBMIT IT IN DETAIL, BE SPECIFIC
  
 3) SEE BUILDING REVIEW NOTES 3 AD 8, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;