Plan Review Notes
Plan Review Notes For Permit 08020137
Permit Number 08020137
Review Stop E
Sequence Number 2
Notes
Date Text
2008-09-03 15:10:18 
  
  
  
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM THE
 PREVIOUS REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
 THERE ARE ALSO SOME NEW COMMENTS BASED ON NEW
 INFORMATION AND/OR DOCUMENTS AS SUBMITTED.
  
 1) NOTE: PLEASE KNOW A RESPONSE LETTER IS NOT REQUIRED
 HOWEVER IS MOST HELPFUL IN ANY REVIEW PROCESS OF PLANS.
  
 2) NOTE: THE BASE BUILDING HAS NOT OBTAINED ANY
 CERTIFICATE OF COMPLETION AT THIS TIME. PLEASE SEE THIS
 NOTE FROM THE PREVIOUS REVIEW. AS STATED PREVIOUSLY THE
 BASE BUILDING DESIGN TEAM IS RESPONSIBLE FOR THE
 BUILDING UNTIL C OF C.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE KNOW THE BUILDING IN WHICH THE APPLIED SCOPE OF
 WORK IS BEING APPLIED IS NOT PERMITTED AT THIS TIME.
 PLEASE ALSO KNOW ONCE THE SHELL BUILDING IS ISSUED AND
 THE BUILD OUT SCOPE OF WORK IS BEING DONE IN THIS SHELL
 WHICH DOES NOT CONTAIN A CERTIFICATE OF OCCUPANCY THE
 BUILD OUT PLANS SHALL CONTAIN A STAMP AND SIGNATURE
 FROM THE BASE BUILDING DESIGNERS OF RECORD FOR EACH
 TRADE SHEET. THIS BUILDING WOULD STILL BE UNDER THE
 RESPONSIBILITY OF THE BASE BUILDING DESIGN TEAM AND ANY
 BUILD OUT WORK WOULD NEED TO BE NOTED. THIS STAMP WOULD
 BE A *SHOP DRAWING * REVIEW STAMPED OR OTHER MEANS
 WHICH MAY BE GONE OVER.
 ** THIS IS REQUIRED FOR ALL TRADES AND ALL REVIEWER(S)
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
 THE BASE BUILDING PERMIT # IS 07100650 WHICH AS OF THIS
 REVIEW ON 2/9/08 HAS COMMENTS TO BE ADDRESSED BEFORE
 ISSUANCE.
  
 3) NOTE: THIS NOTE ALSO STILL REMAINS FROM PREVIOUS
 REVIEW AS THERE ARE DOCUMENTS STILL SUBMITTED WITH ANY
 ADDRESS OF 4354.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE ADDRESS OF PROJECT. PLEASE SEE THE
 COVER SHEET OF THE SUBMITTED PLANS CONTAINS 9847
 OKEECHOBEE BLVD, YET THE OTHER TITLE BLOCKS IN SETS
 CONTAIN 4354 OKEECHOBEE BLVD.
 PLEASE COORDINATE.
 FBC 106.1.2, 106.5 ADMIN SECTION AS ADOPTED BY THE CITY
 OF WEST PALM BEACH.
 *FOR COORDINATION AND ADDITIONAL INFORMATION.
  
 4) NOTE: THIS NOTE REMAINS FROM PREVIOUS REVIEW. PLANS
 STILL DO NOT INDICATE ALL CODES AS GIVEN ON PREVIOUS
 REVIEW **
  
 **PREVIOUS REVIEW NOTE **
 PLEASE BE SURE THE FOLLOWING RELEVANT CODES ARE STATED
 ON PLANS.
 2004 FBC W/2007 REVISIONS. (PLANS SHOW 2006 REVISIONS)
 2005 NFPA-70
 2003 NFPA-101
  
 ** THIS IS REQUIRED ON ELECTRICAL SHEETS AS WELL AS
 ARCHITECTURAL COVER PAGE.
 FBC 106.5, 106.1.2
  
 5) NOTE: ** THIS NOTE REMAINS FROM PREVIOUS REVIEW.
 PLEASE SEE PLANS IN FACT CONTAIN THE PREVIOUS
 *PHOTO-COPIED* FORM *C* AND NOW NEW METHOD *A*
 CALCULATIONS. PLEASE PROVIDE THE REQUIRED CALCULATIONS.
 PLEASE ONLY SUBMIT THE *ONE* WHICH MEETS CODE. HOW CAN
 METHOD *A* BE SUBMITTED WHEN THERE ARE SEVERAL ITEMS IN
 THE INPUT DATA REPORT WHICH ARE BLANK. THE METHOD *A*
 IS FOR *WHOLE BUILDING* COMPLIANCE. HOW CAN THIS BE
 SUBMITTED WHEN THERE ARE ITEMS ON THE IDR WHICH ARE
 BLANK? JUST ONE EXAMPLE OF THIS IS THE FACT THE
 EXTERIOR LIGHTS ON PLANS ARE LEFT BLANK ON THE IDR.
 THIS IS NOT THE ONLY ITEM. PLEASE ALSO SEE OTHER ITEMS
 FOR OTHER TRADES.
 13-415.2.ABC.1.1, .1.2 AND .1.3
  
 ** PREVIOUS REVIEW NOTE **
  
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS IN
 COMPLIANCE WITH FBC 13-415.2
 PLEASE BE AWARE IF THE INTERIOR SCOPE OF WORK IS
 PERMITTED BEFORE C OF O, THE BASE BUILDING METHOD B
 CALCULATIONS WILL BE REQUIRED TO BE REVISED WITH KNOWN
 AS THIS IS CURRENTLY BASED ON ASSUMPTIONS ON SHELL
 PLANS AND CALCULATIONS.
 PLEASE SEE THE METHOD C* FORM SUBMITTED IS NOT
 COMPLETE. THE LIGHTING DENSITIES ARE NOT FILLED OUT AND
 ALL INFORMATION IS MISSING.
 PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3 FOR INTERIOR
 AND EXTERIOR LIGHTING. NOT ALL EXTERIOR LIGHTS AS SHOWN
 ON PLANS ARE ON THE SHELL BUILDING PLANS. FOR EXAMPLE
 THE OCTAGONAL NOTE #4 DOES NOT APPLY TO BASE PLANS.
 PLEASE SEE THE FORMS SUBMITTED ARE ALSO PHOTO-COPIES,
 NOT SIGNED, DATED OR SEALED WITH ORIGINAL SIGNATURES AS
 REQUIRED PER FBC 13-103.1.1.1
 FAC 61G15-23.002
 FS 481.221/ 471.025
  
 ** AS LIGHTING PERFORMANCE CALCULATIONS ARE NOT
 COMPLETE OR SUBMITTED NO FULL REVIEW FOR CODE
 COMPLIANCE COULD BE DONE AT THIS TIME. THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 COULD NOT BE MADE AT THIS TIME.
  
 6) NOTE: ON THE PREVIOUS REVIEW NOTE #5 AS NOTED THE
 COMMENT WAS THAT THE CERTIFICATE OF AUTHORIZATION
 NUMBER WAS MISSING. THE PLANS NOW CONTAIN THIS NUMBER
 AND IT HAS BEEN REVIEWED WITH THE STATE OF FLORIDA
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION
 SITE. THE ADDRESS ON THE SITE DOES NOT COORDINATE WITH
 THE PLANS. PLEASE BE SURE THE ADDRESS COORDINATES AS
 SHOWN ON THE STATE SITE. IF THERE IS MORE THAN ONE
 LOCATION OF BUSINESS, THEN MORE THAN ONE MAY BE LISTED.
 FAC 61G15-23.002
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED INFORMATION ON TITLE BLOCKS
 FOR ENGINEERING FIRM ETC ON MECHANICAL, PLUMBING AND
 ELECTRICAL SHEETS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND
 FLORIDA STATUTES 471.023.
 PLEASE SEE MISSING PRINTED NAME, MISSING PRINTED
 LICENSE NUMBER AND MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER.
 ** THIS IS REQUIRED ON ALL MEP PLANS WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADE REVIEWS.
  
 7) NOTE: PLEASE SEE COMMENT FROM PREVIOUS REVIEW WITH
 RESPECT TO THE NUMBER OF NIGHT LIGHTS LEFT ON. THE
 AMOUNT OF LIGHTING AS SHOWN DOES NOT MEET THE INTENT OF
 THE FLORIDA ENERGY CODE AND IS NOT PERMITTED BY THIS
 AHJ.
 PLEASE VERIFY THE LIGHTING CONTROLS ON PLANS. PLANS
 STATE OVER RIDES YET OVER RIDES OF ANY SYSTEM WOULD BE
 AUTOMATED NOT A SINGLE POLE SWITCH . EXAMPLE: AN
 OCCUPANT COMES INTO WORK WHEN THE NORMAL TIME OF DAY
 SCHEDULING IS OFF. THAT PERSON WOULD BE ABLE TO OVER
 RIDE THE TIMED SCHEDULING. THE PERSON LEAVES AN HOUR
 LATER. IF THE OVER WAS A STANDARD SINGLE POLE SWITCH
 THE LIGHTS WOULD REMAIN ON. THERE ARE NOTES ON SYMBOL
 LEGEND WHICH SEEMED TO INDICATE THERE ARE TO BE
 OCCUPANCY SENSORS HOWEVER SEPARATE SPACES SUCH AT THE
 BATHROOMS ONLY SHOW STANDARD SINGLE POLE DEVICES.
 ** PLEASE EXPLAIN SYSTEM.
  
 ** SEE COMMENTS FROM PREVIOUS REVIEW NOTE #6.
 PLEASE KNOW BASED ON NOTE #4 ABOVE. PLEASE KNOW THE
 INTENT OF THE ENERGY CODE IS TO CONSERVE ENERGY. PLEASE
 SEE 13-415.1.ABC.1 WHICH REQUIRES ALL LIGHTING TO BE
 TURNED OFF WHEN NOT IN USE. THIS AHJ DOES NOT HAVE AN
 ISSUE WITH PERMITTING *NIGHT LIGHTS* FOR THE REASON OF
 LIFE SAFETY OR SECURITY HOWEVER THIS IS TO BE TO A
 MINIMUM OF 1FT CANDLE WHICH THE LIFE SAFETY CODE
 REQUIRES FOR EGRESS UNDER NORMAL AND EMERGENCY
 CONDITIONS ON FLAT WALKING SURFACES. (NFPA-101 7.8/7.9
 PLEASE PROVIDE PHOTO-METRICS LEVELS FOR EGRESS PATHS
 UNDER THE NORMAL AND EMERGENCY CONDITIONS FOR THE NIGHT
 LIGHT FIXTURES AE. PLEASE KNOW IF THE LIGHTING LEVELS
 ARE OVER, THEN DESIGN WILL BE REQUIRED TO ADJUSTED.
 PLEASE SEE BOTH CHAPTER 10 OF THE FBC AND LIFE SAFETY
 CODE 7.8.1.2.2ALLOWS THE USE OF OCCUPANCY SENSORS ON
 THESE FIXTURES.
 THE OTHER ALLOWANCE WOULD BE FOR EACH FIXTURE WHICH IS
 3 LAMPS TO REMAIN ON WITH 1-LAMP OR TWO TO MEET THE 1FT
 CANDLE MINIMUM. PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND
 .1.3 AS LIGHTING CONTROLS ARE NOT COMPLETE WITH ALL
 LIGHTING ON PLANS.
 FOR EXAMPLE: PLEASE SEE SEPARATE SPACES WHICH REQUIRES
 LIGHTING TO BE ABLE TO OVER RIDE THE LIGHTING CONTROLS,
 AND REQUIRES A MAXIMUM OVER RIDE TIME. PLANS INDICATE A
 MANUAL OVER RIDE HOWEVER DOES NOT INDICATE THE MAXIMUM
 OVER RIDE TIME.
 PLEASE SEE THE SEPARATE SPACES AS BATHROOMS ETC ONLY
 SHOW A STANDARD SWITCH WHICH DOES NOT MEET THESE
 SECTIONS OF THE CODE.
 PLEASE SEE THE REAR OFFICE/WORK ROOM WHICH SHOWS A SR
 YET THE SYMBOL LEGEND DOES NOT CONTAIN THIS DEVICE OR
 INFORMATION ON WHAT TYPE OF DEVICE IT IS?? PLEASE ALSO
 SEE THE OCTAGONAL NOTE #2 WHICH STATES OCCUPANCY SENSOR
 YET COULD NOT LOCATE ANY MAXIMUM TIMES.
 ** PLEASE CALL TO GO OVER IF NEEDED.
  
 8) NOTE: PLEASE SEE NOTE #7 FROM PREVIOUS REVIEW. MAY
 NOT HAVE THE EMERGENCY/EXIT LIGHTS ALL ON ONE CIRCUIT
 UNLESS MEETING THE EXCEPTIONS IN THE CODE. THE LIGHTING
 IS REQUIRED TO BE CIRCUITED TO THE LOCAL BRANCH
 CIRCUIT. THAT IS THE CODE, THE *EXCEPTION* IS IF YOU
 MEET THE ITEMS LISTED UNDER 700.12F. BASED ON THE PLANS
 AND INFORMATION SUBMITTED, THE LIGHTING DOES *NOT* MEET
 THE EXCEPTION AND CIRCUITING NEEDS TO BE REVISED.
  
 ** PREVIOUS REVIEW COMMENT **
 PLEASE SEE 700.12F WHICH REQUIRES EMERGENCY AND EXIT
 LIGHTS TO BE CONNECTED TO THE LOCAL LIGHTING BRANCH
 CIRCUIT. THERE IS EXCEPTIONS FOR MULTIPLE CIRCUITS IN
 UNINTERRUPTED AREAS, HOWEVER PLEASE SEE PLANS WHICH
 SHOW FIXTURES IN OTHER SPACES STILL ON THE DEDICATED
 CIRCUIT WHICH IS NOT PERMITTED.
  
 9) NOTE: SAME COMMENT AS PREVIOUS REVIEW. MAY NOT USE
 *LIGHTING* OR *RECEPTACLES* IN GENERAL. THE PANEL
 SCHEDULE STILL INDICATES THIS.
 THIS WAS REVISED UNDER THE 2005 CODE
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT THE PANEL SCHEDULE CIRCUITS SHALL BE
 SPECIFIC TO CIRCUITS. FOR EXAMPLE: THE SHOW WINDOW
 RECEPTACLES ARE REQUIRED TO BE LABELED AS SUCH. MAY NOT
 LABEL ALL AS *GENERAL LIGHTS* OR GENERAL RECEPTACLES*.
 PLEASE SEE 408.4, 210.62.
 FBC 106.3.5.1.2, 106.1.2
  
 10) NOTE: PLEASE SEE NOTE #9 FROM PREVIOUS REVIEW. THE
 PLANS STILL DOE NOT CONTAIN ANY LOAD CALCULATIONS
 MEETING THE MINIMUM CODE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW THE LOAD CALCULATIONS BASED ON NEC. PLEASE
 SEE THE SHOW WINDOWS FOR EXAMPLE NEED TO SHOW HOW THESE
 LOADS WERE FIGURED PER 220.43
 PLEASE BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125% PER
 215.3, 230.42 ETC
  
 11) NOTE: ALL TITLE BLOCKS ON ALL SHEETS WHICH CONTAIN
 THE TITLE BLOCK FOR THE ARCHITECT SHALL CONTAIN THE
 INFORMATION AS REQUIRED PER FAC 61G1-16.004.
 ** MISSING PRINTED LICENSE NUMBER*
 THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY THOSE OTHER TRADES.
  
 12) NOTE: THIS IS THE SAME NOTE AS PREVIOUSLY NOTED IN
 #11. THE PLANS STILL SHOW EQUIPMENT OUTSIDE YET RISER
 AND PLANS DO NOT INDICATE THIS EQUIPMENT. PLEASE SEE
 POWER PLANS. THERE IS SOMETHING ON PLANS OUTSIDE. WHAT
 IS IT?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS APPEAR TO SHOW PANELS OUTSIDE. ARE
 THESE INSIDE OR OUTSIDE. PLEASE COORDINATE WITH BASE
 SHELL DESIGNER.
  
 13) NOTE: PLEASE SEE PLAN REVIEW NOTES. MOST OF THE
 NOTES ARE THE SAME AS PREVIOUS REVIEW. PLEASE SEE
 FLORIDA STATUTES 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR MINIMUM CODE COMPLIANCE.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717