| 2008-02-12 16:55:11 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. NOTE: PLEASE CORRELATE THE CORRECT ADDRESS ON |
| | RESUBMITTED PLANS. THE COVER SHEET IS INDICATING 9847 |
| | OKEECHOBEE BLVD, HOWEVER SHEETS A-0.1 THRU P-1 ARE |
| | INDICATING THE ADDRESS AT 4354 OKEECHOBEE BLVD. PER |
| | CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.2 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. SHEET P-1 IS MISSING REQUIRED INFORMATION ON TITLE |
| | BLOCK FOR ENGINEERING FIRM. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 |
| | AND FLORIDA STATUTES 471.023. |
| | NOTE: TITLE BLOCK IS MISSING THE FOLLOWING: PRINTED |
| | NAME AND PRINTED LICENSE NUMBER OF THE PERSON SIGNING |
| | AND SEALING SHEET. ALSO THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER IS MISSING FROM JORDAN & SKALA |
| | ENGINEERS, INC.. |
| | **THIS IS REQUIRED ON ALL MEP PLAN SHEETS WHETHER OR |
| | NOT COMMENT IS MADE BY OTHER TRADE REVIEWS. |
| | |
| | 3. THE WATER HEATER SHALL BE COMPLIANT WITH CHAPTER 13 |
| | ENERGY EFFICIENCY SECTION TABLE 13-612.1.ABC.3.2 |
| | MINIMUM PERFORMANCE STANDARDS WATER HEATING EQUIPMENT |
| | AND THE HOT WATER PIPE SHALL BE COMPLIANT WITH TABLE |
| | 611.1.ABC.1 MINIMUM PIPE INSULATION. |
| | |
| | 4. SHEET P-1, WATER RISER DIAGRAM: THE COLD WATER TO |
| | THE DRINKING FOUNTAIN IS MISSING. PLEASE ADD THIS ON |
| | THE RESUBMITTAL. PER FBC PLUMBING, SECTION *601.1 SCOPE |
| | AND CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION |
| | 106.3.5.1.3 PLUMBING. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |