| Plan Review Notes For Permit 08020137 |
| Permit Number |
08020137 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-03-18 17:27:51 | PLAN DENIED | | | 1) PLEASE PROVIDE DETALS ON CURB TIEDOWN TO ROOF AND | | | AIR CONDITIONING TIEDOWN TO CURB ON THE PLANS. | | | 2) PLEASE SHOW LOCATION AND TERMINATION OF A/C | | | CONDENSATE DRAIN . | | | 3) PLEASE SUBMIT ENERGY CALCULATIONS WITH THE PLANS. | | | 4) PLEASE SUBMIT MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS FOR THE AIR CONDITIONING UNITS WITH THE | | | PLANS . | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|