Plan Review Notes
Plan Review Notes For Permit 08020137
Permit Number 08020137
Review Stop M
Sequence Number 1
Notes
Date Text
2008-03-18 17:27:51PLAN DENIED
 1) PLEASE PROVIDE DETALS ON CURB TIEDOWN TO ROOF AND
 AIR CONDITIONING TIEDOWN TO CURB ON THE PLANS.
 2) PLEASE SHOW LOCATION AND TERMINATION OF A/C
 CONDENSATE DRAIN .
 3) PLEASE SUBMIT ENERGY CALCULATIONS WITH THE PLANS.
 4) PLEASE SUBMIT MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE AIR CONDITIONING UNITS WITH THE
 PLANS .