Plan Review Notes
Plan Review Notes For Permit 08020137
Permit Number 08020137
Review Stop E
Sequence Number 1
Notes
Date Text
2008-02-11 09:04:18** DENIED REVIEW **
  
 1) NOTE: PLEASE KNOW THE BUILDING IN WHICH THE APPLIED
 SCOPE OF WORK IS BEING APPLIED IS NOT PERMITTED AT THIS
 TIME.
 PLEASE ALSO KNOW ONCE THE SHELL BUILDING IS ISSUED AND
 THE BUILD OUT SCOPE OF WORK IS BEING DONE IN THIS SHELL
 WHICH DOES NOT CONTAIN A CERTIFICATE OF OCCUPANCY THE
 BUILD OUT PLANS SHALL CONTAIN A STAMP AND SIGNATURE
 FROM THE BASE BUILDING DESIGNERS OF RECORD FOR EACH
 TRADE SHEET. THIS BUILDING WOULD STILL BE UNDER THE
 RESPONSIBILITY OF THE BASE BUILDING DESIGN TEAM AND ANY
 BUILD OUT WORK WOULD NEED TO BE NOTED. THIS STAMP WOULD
 BE A *SHOP DRAWING * REVIEW STAMPED OR OTHER MEANS
 WHICH MAY BE GONE OVER.
 ** THIS IS REQUIRED FOR ALL TRADES AND ALL REVIEWER(S)
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
 THE BASE BUILDING PERMIT # IS 07100650 WHICH AS OF THIS
 REVIEW ON 2/9/08 HAS COMMENTS TO BE ADDRESSED BEFORE
 ISSUANCE.
  
 2) NOTE: PLEASE CORRELATE ADDRESS OF PROJECT. PLEASE
 SEE THE COVER SHEET OF THE SUBMITTED PLANS CONTAINS
 9847 OKEECHOBEE BLVD, YET THE OTHER TITLE BLOCKS IN
 SETS CONTAIN 4354 OKEECHOBEE BLVD.
 PLEASE COORDINATE.
 FBC 106.1.2, 106.5 ADMIN SECTION AS ADOPTED BY THE CITY
 OF WEST PALM BEACH.
 *FOR COORDINATION AND ADDITIONAL INFORMATION.
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE STATED ON PLANS.
 2004 FBC W/2007 REVISIONS. (PLANS SHOW 2006 REVISIONS)
 2005 NFPA-70
 2003 NFPA-101
  
 ** THIS IS REQUIRED ON ELECTRICAL SHEETS AS WELL AS
 ARCHITECTURAL COVER PAGE.
 FBC 106.5, 106.1.2
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN COMPLIANCE WITH FBC 13-415.2
 PLEASE BE AWARE IF THE INTERIOR SCOPE OF WORK IS
 PERMITTED BEFORE C OF O, THE BASE BUILDING METHOD B
 CALCULATIONS WILL BE REQUIRED TO BE REVISED WITH KNOWN
 AS THIS IS CURRENTLY BASED ON ASSUMPTIONS ON SHELL
 PLANS AND CALCULATIONS.
 PLEASE SEE THE METHOD C* FORM SUBMITTED IS NOT
 COMPLETE. THE LIGHTING DENSITIES ARE NOT FILLED OUT AND
 ALL INFORMATION IS MISSING.
 PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3 FOR INTERIOR
 AND EXTERIOR LIGHTING. NOT ALL EXTERIOR LIGHTS AS SHOWN
 ON PLANS ARE ON THE SHELL BUILDING PLANS. FOR EXAMPLE
 THE OCTAGONAL NOTE #4 DOES NOT APPLY TO BASE PLANS.
 PLEASE SEE THE FORMS SUBMITTED ARE ALSO PHOTO-COPIES,
 NOT SIGNED, DATED OR SEALED WITH ORIGINAL SIGNATURES AS
 REQUIRED PER FBC 13-103.1.1.1
 FAC 61G15-23.002
 FS 481.221/ 471.025
  
 ** AS LIGHTING PERFORMANCE CALCULATIONS ARE NOT
 COMPLETE OR SUBMITTED NO FULL REVIEW FOR CODE
 COMPLIANCE COULD BE DONE AT THIS TIME. THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 COULD NOT BE MADE AT THIS TIME.
  
 5) NOTE: PLEASE SEE MISSING REQUIRED INFORMATION ON
 TITLE BLOCKS FOR ENGINEERING FIRM ETC ON MECHANICAL,
 PLUMBING AND ELECTRICAL SHEETS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND
 FLORIDA STATUTES 471.023.
 PLEASE SEE MISSING PRINTED NAME, MISSING PRINTED
 LICENSE NUMBER AND MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER.
 ** THIS IS REQUIRED ON ALL MEP PLANS WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADE REVIEWS.
  
 6) NOTE: PLEASE KNOW BASED ON NOTE #4 ABOVE. PLEASE
 KNOW THE INTENT OF THE ENERGY CODE IS TO CONSERVE
 ENERGY. PLEASE SEE 13-415.1.ABC.1 WHICH REQUIRES ALL
 LIGHTING TO BE TURNED OFF WHEN NOT IN USE. THIS AHJ
 DOES NOT HAVE AN ISSUE WITH PERMITTING *NIGHT LIGHTS*
 FOR THE REASON OF LIFE SAFETY OR SECURITY HOWEVER THIS
 IS TO BE TO A MINIMUM OF 1FT CANDLE WHICH THE LIFE
 SAFETY CODE REQUIRES FOR EGRESS UNDER NORMAL AND
 EMERGENCY CONDITIONS ON FLAT WALKING SURFACES.
 (NFPA-101 7.8/7.9
 PLEASE PROVIDE PHOTO-METRICS LEVELS FOR EGRESS PATHS
 UNDER THE NORMAL AND EMERGENCY CONDITIONS FOR THE NIGHT
 LIGHT FIXTURES AE. PLEASE KNOW IF THE LIGHTING LEVELS
 ARE OVER, THEN DESIGN WILL BE REQUIRED TO ADJUSTED.
 PLEASE SEE BOTH CHAPTER 10 OF THE FBC AND LIFE SAFETY
 CODE 7.8.1.2.2ALLOWS THE USE OF OCCUPANCY SENSORS ON
 THESE FIXTURES.
 THE OTHER ALLOWANCE WOULD BE FOR EACH FIXTURE WHICH IS
 3 LAMPS TO REMAIN ON WITH 1-LAMP OR TWO TO MEET THE 1FT
 CANDLE MINIMUM. PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND
 .1.3 AS LIGHTING CONTROLS ARE NOT COMPLETE WITH ALL
 LIGHTING ON PLANS.
 FOR EXAMPLE: PLEASE SEE SEPARATE SPACES WHICH REQUIRES
 LIGHTING TO BE ABLE TO OVER RIDE THE LIGHTING CONTROLS,
 AND REQUIRES A MAXIMUM OVER RIDE TIME. PLANS INDICATE A
 MANUAL OVER RIDE HOWEVER DOES NOT INDICATE THE MAXIMUM
 OVER RIDE TIME.
 PLEASE SEE THE SEPARATE SPACES AS BATHROOMS ETC ONLY
 SHOW A STANDARD SWITCH WHICH DOES NOT MEET THESE
 SECTIONS OF THE CODE.
 PLEASE SEE THE REAR OFFICE/WORK ROOM WHICH SHOWS A SR
 YET THE SYMBOL LEGEND DOES NOT CONTAIN THIS DEVICE OR
 INFORMATION ON WHAT TYPE OF DEVICE IT IS?? PLEASE ALSO
 SEE THE OCTAGONAL NOTE #2 WHICH STATES OCCUPANCY SENSOR
 YET COULD NOT LOCATE ANY MAXIMUM TIMES.
 ** PLEASE CALL TO GO OVER IF NEEDED.
  
 7) NOTE: PLEASE SEE 700.12F WHICH REQUIRES EMERGENCY
 AND EXIT LIGHTS TO BE CONNECTED TO THE LOCAL LIGHTING
 BRANCH CIRCUIT. THERE IS EXCEPTIONS FOR MULTIPLE
 CIRCUITS IN UNINTERRUPTED AREAS, HOWEVER PLEASE SEE
 PLANS WHICH SHOW FIXTURES IN OTHER SPACES STILL ON THE
 DEDICATED CIRCUIT WHICH IS NOT PERMITTED.
  
 8) NOTE: PLEASE SEE THAT THE PANEL SCHEDULE CIRCUITS
 SHALL BE SPECIFIC TO CIRCUITS. FOR EXAMPLE: THE SHOW
 WINDOW RECEPTACLES ARE REQUIRED TO BE LABELED AS SUCH.
 MAY NOT LABEL ALL AS *GENERAL LIGHTS* OR GENERAL
 RECEPTACLES*.
 PLEASE SEE 408.4, 210.62.
 FBC 106.3.5.1.2, 106.1.2
  
 9) NOTE: PLEASE SHOW THE LOAD CALCULATIONS BASED ON
 NEC. PLEASE SEE THE SHOW WINDOWS FOR EXAMPLE NEED TO
 SHOW HOW THESE LOADS WERE FIGURED PER 220.43
 PLEASE BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125% PER
 215.3, 230.42 ETC
  
 10) NOTE: PLEASE SEE OCTAGONAL NOTE #4 AS MENTIONED
 ABOVE FOR LIGHTING PERFORMANCE, HOWEVER PLEASE SEE AS
 THESE ARE NOT PART OF BASE SHELL PLEASE COMPLETE WITH
 FIXTURE INFORMATION AND CONTROL.
 PLANS MENTIONS BACK UP FOR EMERGENCY ILLUMINATION
 HOWEVER NOT CLEAR ON THIS.
 FBC 106.1.2, FOR ADDITIONAL INFORMATION AS WELL AS
 CHAPTER 13 FOR EXTERIOR LIGHTING CONTROLS AND LIGHTING
 PERFORMANCE CALCULATIONS.
 13-415.1.ABC.1.4, 13-415.2 (SECTIONS GIVEN ABOVE).
  
 11) NOTE: PLEASE SEE PLANS APPEAR TO SHOW PANELS
 OUTSIDE. ARE THESE INSIDE OR OUTSIDE. PLEASE COORDINATE
 WITH BASE SHELL DESIGNER.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-8056717
 [email protected]