Plan Review Notes
Plan Review Notes For Permit 08020128
Permit Number 08020128
Review Stop E
Sequence Number 9
Notes
Date Text
2009-07-08 13:47:52 
  
 ** DENIED PLANS **
  
 1) NOTE: AS REQUESTED ON PREVIOUS REVIEW PLEASE SUBMIT
 A COMPLETE SELECTIVE COORDINATION STUDY INCLUDING ALL
 RELEVANT TIME CURVES.
 THE SINGLE SHEET DOCUMENT SUBMITTED IS NOT THE COMPLETE
 INFORMATION NEEDED FOR REVIEW.
 PLEASE SEE NFPA-70 700.27, 701.18, 240.12.
 ** THIS WAS DERIVED BASED ON SEVERAL REVISIONS AGO WHEN
 ALL BATTERY BACK UP LIGHTING REQUIRED FOR EGRESS UNDER
 EMERGENCY CONDITIONS WAS REVISED TO ONLY USE THE NEW
 LIFE SAFETY GENERATOR AS BACK UP FOR EMERGENCY
 LIGHTING.
  
 *** THIS WILL AFFECT ANY APPLICATION FOR TCO OR CO OF
 BUILDING.
  
 ** AT THIS TIME SHEET E-801 SUBMITTED IS STAMPED OK.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  