Plan Review Notes
Plan Review Notes For Permit 08020128
Permit Number 08020128
Review Stop P
Sequence Number 8
Notes
Date Text
2009-04-23 16:18:12REVISIONS DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1 (ADMINISTRATIVE)
  
 1. SHT P141 NO REVISIONS NOTED. PLEASE CLOUD AND NUMBER
 ALL REVISIONS. BP-3.0 SHOWS NO NEW REVISIONS. SECTION
 106.1.3.
  
 2. SHT P302. SOME REVISIONS NOTED WITH NO CLOUDS OR
 REVISION NUMBERS. PLEASE INDICATE ALL REVISIONS WITH
 CLOUD AND A REVISION NUMBER. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  