| 2009-03-10 15:41:56 | ** DENIED REVISIONS ** |
| | |
| | 1) NOTE: NOT ALL CHANGES AND REVISIONS ON SHEETS HAVE |
| | BEEN IDENTIFIED WITH CLOUDS AND TRIANGLES. |
| | FOR EXAMPLE: PLEASE SEE E1110 WHICH CONTAINS A |
| | SUBSTANTIAL AMOUNT OF REVISIONS MOST ARE NOT |
| | IDENTIFIED. |
| | FOR EXAMPLE: PLEASE SEE E001 WHERE CLOUDS ARE SHOWN |
| | HOWEVER NO IDENTIFICATION IS SHOWN. |
| | |
| | ** THESE ARE TWO EXAMPLES ONLY. THERE ARE OTHERS. |
| | PLEASE BE SURE ALL REVISIONS ARE IDENTIFIED ON PLANS. |
| | |
| | FBC 106.5, 106.1.1, 106.1.2 FOR CLARITY, ADDITIONAL |
| | INFORMATION OF RECORD PLANS. |
| | FBC CHAPTER 13, CHAPTER 10, NEC 2005. |
| | |
| | 2) NOTE: PLANS NOW HAVE MOST ALL PREVIOUS BATTERY BACK |
| | UP FIXTURES REMOVED. BASED ON THE REVISED PLANS THIS IS |
| | NOT PERMITTED AS SHOWN. A STRAIGHT NATURAL GAS |
| | GENERATOR IS NOT PERMITTED BY THIS AHJ. |
| | THIS WAS GONE OVER BEFORE PERMIT OF BUILDING WAS ISSUED |
| | YET PLANS ARE NOW ONCE AGAIN BEING REVISED TO GO BACK |
| | TO SOMETHING THAT HAD ALREADY BEEN COMMENTED ON. |
| | PLEASE SEE 700.12.B.3. ONSITE FUEL SHALL BE REQUIRED. |
| | PLEASE SEE NFPA-101 AS THE BACK UP POWER SOURCE FOR |
| | EMERGENCY LIGHTING FIXTURES ARE AT THE DETERMINATION OF |
| | THE AHJ. SECTION 7.8.2.1. |
| | THE CODE IS SPECIFIC TO THE REQUIREMENT OF ON-SITE FUEL |
| | REQUIRED. PLEASE SEE FBC CHAPTER 10, 1006.2.3. |
| | |
| | 3) NOTE: PLEASE PROVIDE COMPLETE STOCK OF MATERIALS AND |
| | RETAIL GOODS IN AREAS IN WHICH DESIRED USED OF *FINE |
| | MERCHANDISE* IS PLACED IN THE INPUT DATA REPORT OF THE |
| | ENERGY CALCULATIONS. |
| | THE AMOUNT OF FINE MERCHANDISE WOULD BE LIMITED TO |
| | SQUARE FEET OF DISPLAY AREA ONLY. NOT AREAS OF GENERAL |
| | LIGHTING. PLEASE ALSO KNOW THAT THIS ALLOWANCE MAY BE |
| | USED FOR ITEMS SUCH AS JEWELRY AS NOTED IN THE CODE |
| | HOWEVER BASED ON THE CALCULATIONS ALL DISPLAY AREAS ARE |
| | NOTED AS FINE MERCHANDISE WHICH DOES NOT POSSIBLE OR |
| | PERMISSIBLE. |
| | FBC 13-415.2, 13-415.2.ABC.1.1, .1.2, 13-415.2.B.2 ETC |
| | |
| | 4) NOTE: ALL EGRESS PATHS SHALL CONTAIN THE BATTERY |
| | BACK UP FIXTURES SUCH AS STAIRS. SOME STAIR AREAS STILL |
| | CONTAIN FIXTURES AS NOTED HOWEVER STAIRS SUCH AS THE |
| | MAIN EGRESS STAIRS AT THE REAR OF THE STORE HAVE NOW |
| | BEEN REVISED TO REMOVE SUCH FIXTURES. |
| | THIS WILL NOT BE PERMITTED. THIS WAS GONE OVER |
| | EXTENSIVELY BEFORE PERMIT ISSUANCE YET THE PLANS HAVE |
| | NOW BEEN REVISED TO GO BACK TO PREVIOUS COMMENTS. |
| | NFPA-101 7.8.1.3, 7.9.2.1, 7.9.2.2, FBC 1006, NEC |
| | 700.12B3 ETC |
| | |
| | 5) NOTE: PLEASE BE SURE ALL ITEMS IN THE INPUT DATA |
| | REPORT COORDINATES WITH *ALL* LIGHTING ON PLANS. ISSUED |
| | PERMIT WAS BASED ON SOME ERRORS HOWEVER BASED ON THE |
| | FBC 13-103.3 STATES WITHOUT GROSS ERRORS. |
| | AS THERE HAS BEEN NUMEROUS FIXTURES ADDED, TYPES OF |
| | FIXTURES REVISED, TYPES OF FIXTURES TO BE REVISED AND |
| | ACTUAL REMOVAL OF SEVERAL OTHER FIXTURES THE PLANS AND |
| | CALCULATIONS NEED TO COORDINATE COMPLETELY. |
| | ** ONE EXAMPLE WOULD BE FIXTURES ON PREVIOUS |
| | CALCULATIONS WHICH WERE 85VA ARE NOW 58 VA WHICH IS OK, |
| | HOWEVER THIS DOES NOT COORDINATE WITH THE FIXTURE |
| | LEGEND. |
| | ** FOR EXAMPLE: FIXTURES IN AREAS AND ROOMS ON PLANS |
| | NEED TO MATCH THE IDR. ONE LOCATION ALONE WOULD BE ROOM |
| | 105. |
| | |
| | 6) NOTE: TO DATE OF THIS REVIEW NO LOW VOLTAGE PERMIT |
| | APPLICATION HAS BEEN SUBMITTED. PLEASE KNOW THAT THE |
| | LOW VOLTAGE SCOPE OF WORK ON PLANS NEEDS TO BE UNDER A |
| | SEPARATE PERMIT AS NOTED ON ORIGINAL REVIEWS. |
| | PERMIT FEE BASED ON THE LOW VOLTAGE VALUATION WOULD BE |
| | REQUIRED AT THE TIME OF PERMIT APPLICATION. |
| | |
| | 7) NOTE: PLEASE SEE PREVIOUS PROVISO ISSUANCE OF |
| | 9/29/08. NO SELECTIVE COORDINATION STUDY, TIME CURVES |
| | ETC HAVE BEEN SUBMITTED TO DATE. PLEASE SEE 700.27, |
| | 701.8, 240.12, NFPA-110 6.5.1 ETC |
| | |
| | 8) NOTE: PLEASE BE SURE ALL PLANS AS NOTED ABOVE HAVE |
| | ALL REVISIONS LABELED WITH CLOUDS AND TRIANGLES. THERE |
| | ARE SEVERAL LOCATIONS WHERE THE PLANS CONTAIN CLOUDS |
| | YET THERE IS NO IDENTIFICATION OF THE REVISIONS TO |
| | COORDINATE WITH THE TITLE BLOCKS. SEE SHEET E341 FOR |
| | EXAMPLE; |
| | FBC 106.1.1,106.1.2, 106.5. |
| | NEC 2005, 240, 310, 220 ETC CHAPTERS GIVEN IN GENERAL |
| | FOR COORDINATION. |
| | |
| | 9) NOTE: RISER DIAGRAM HAS BEEN COMPLETELY REVISED TO |
| | NOW INCLUDE A NEW PANEL HPE-1 400AMP YET NO PANEL |
| | SCHEDULE FOR LOADS ETC WAS SUBMITTED. |
| | PLEASE SEE 700.9 FOR WIRING OF LIFE SAFETY SYSTEMS WITH |
| | OTHER SYSTEMS. WHAT TYPE OF PANEL IS HPE? |
| | WITH THIS REVISION IF YOU LOSE THE 150KW GENERATOR AND |
| | THE NEW 40KW UNIT HANDLES THE LIFE SAFETY LOADS, WHAT |
| | TAKES CARE OF THE LEGALLY REQUIRED ITEMS? (701 LOADS). |
| | THIS COMMENT ALONG WITH SEVERAL OTHERS ABOVE NEED TO BE |
| | GONE OVER AS SOON AS POSSIBLE AS THE DESIGN CHANGES |
| | WILL HAVE A MAJOR IMPACT OF THE BUILDING CONSTRUCTION |
| | TIME FRAME. |
| | |
| | |
| | **** IMPORTANT> ANY SHEETS WHICH DID NOT NEED TO HAVE |
| | CHANGES MADE NEED TO BE PLACED BACK INTO THE SETS WHEN |
| | RESUBMITTING THE REVISIONS. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |