2009-03-05 16:54:59DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 NFPA-58
 FBC-2004 CHAPTER 1
  
 1. SHT P110 THE OFFSET DOWNSTREAM OF THE 10 INCH STORM
 DRAIN BY COL LINE 12 SHALL BE INDICATED AS 12 INCH PIPE
 @ 1/4" PER FT PER TABLE 1106.3. PLEASE INDICATE ON
 PLAN. REVISION BP-3.0 WAS NOT FOUND OR APPROVED. PLEASE
 CLARIFY. SECTION 106.1.3. PLEASE INDICATE WHERE
 REVISION BP-3.0 CAN BE FOUND.
  
 2. SHT P111 THE PROPANE TANK IS REQUIRED TO BE A
 MINIMUM OF 10 FEET FROM THE BUILDING. NFPA-58 SECTION
 6.2.1 & ANNEX I SECTION I.1 AND FIGURE I.1(B). THE
 PROPANE TANK IS INDICATED UNDER THE BUILDING.
  
 3. SHT P111 ALL REVISIONS SHALL BE CLOUDED AND
 INDICATED WITH A REVISION NUMBER THAT IS SHOWN ON THE
 REVISION INDEX. SECTION 106.1.3. THERE ARE REVISIONS
 THAT ARE CLOUDED, BUT SHOW NO REVISION NUMBER. ALSO
 REVISION BP-3.0 WAS NOT FOUND OR APPROVED. PLEASE
 CLARIFY. SECTION 106.1.3. PLEASE INDICATE WHERE
 REVISION BP-3.0 CAN BE FOUND.
  
 4. SHT P141 REVISION INDEX SHOWS REVISION BP-3.0. THIS
 REVISION WAS NOT FOUND OR APPROVED. NO REVISIONS WERE
 FOUND ON THIS SHEET. PLEASE CLARIFY. SECTION 106.1.3.
  
 5. SHT P302 ALL REVISIONS SHALL BE CLOUDED AND
 INDICATED WITH A REVISION NUMBER THAT IS SHOWN ON THE
 REVISION INDEX. SECTION 106.1.3. THERE ARE REVISIONS
 THAT ARE CLOUDED, BUT SHOW NO REVISION NUMBER. (SEE
 BETWEEN COL. LINES 1 & 2). THERE WAS A CHANGE/REVISION
 THAT WAS NOT CLOUDED/NUMBERED TO THE RIGHT OF COL. LINE
 1 JUST ABOVE COL. LINE B. PLEASE CLOUD AND NUMBER ALL
 REVISIONS. ALSO REVISION BP-3.0 WAS NOT FOUND OR
 APPROVED. PLEASE CLARIFY. SECTION 106.1.3. PLEASE
 INDICATE WHERE REVISION BP-3.0 CAN BE FOUND.
  
 6. SHT P351 ALL REVISIONS SHALL BE CLOUDED AND
 INDICATED WITH A REVISION NUMBER THAT IS SHOWN ON THE
 REVISION INDEX. SECTION 106.1.3. THERE ARE REVISIONS
 THAT ARE CLOUDED, BUT SHOW NO REVISION NUMBER. ALSO
 REVISION BP-3.0 WAS NOT FOUND OR APPROVED. PLEASE
 CLARIFY. SECTION 106.1.3. PLEASE INDICATE WHERE
 REVISION BP-3.0 CAN BE FOUND.
  
 7. SHT P501 ALL REVISIONS SHALL BE CLOUDED AND
 INDICATED WITH A REVISION NUMBER THAT IS SHOWN ON THE
 REVISION INDEX. SECTION 106.1.3. THERE ARE REVISIONS
 THAT ARE CLOUDED, BUT SHOW NO REVISION NUMBER. ALSO
 REVISION BP-3.0 WAS NOT FOUND OR APPROVED. PLEASE
 CLARIFY. SECTION 106.1.3. PLEASE INDICATE WHERE
 REVISION BP-3.0 CAN BE FOUND. ALSO MANY REVISION
 TRIANGLES WITH THE NUMBERS 1 & 2 ARE SHOWN ON THE FLOOR
 PLAN BUT NOT IN THE REVISION INDEX. PLEASE CLARIFY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  