| Date |
Text |
| 2009-03-05 16:54:59 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | NFPA-58 |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P110 THE OFFSET DOWNSTREAM OF THE 10 INCH STORM |
| | DRAIN BY COL LINE 12 SHALL BE INDICATED AS 12 INCH PIPE |
| | @ 1/4" PER FT PER TABLE 1106.3. PLEASE INDICATE ON |
| | PLAN. REVISION BP-3.0 WAS NOT FOUND OR APPROVED. PLEASE |
| | CLARIFY. SECTION 106.1.3. PLEASE INDICATE WHERE |
| | REVISION BP-3.0 CAN BE FOUND. |
| | |
| | 2. SHT P111 THE PROPANE TANK IS REQUIRED TO BE A |
| | MINIMUM OF 10 FEET FROM THE BUILDING. NFPA-58 SECTION |
| | 6.2.1 & ANNEX I SECTION I.1 AND FIGURE I.1(B). THE |
| | PROPANE TANK IS INDICATED UNDER THE BUILDING. |
| | |
| | 3. SHT P111 ALL REVISIONS SHALL BE CLOUDED AND |
| | INDICATED WITH A REVISION NUMBER THAT IS SHOWN ON THE |
| | REVISION INDEX. SECTION 106.1.3. THERE ARE REVISIONS |
| | THAT ARE CLOUDED, BUT SHOW NO REVISION NUMBER. ALSO |
| | REVISION BP-3.0 WAS NOT FOUND OR APPROVED. PLEASE |
| | CLARIFY. SECTION 106.1.3. PLEASE INDICATE WHERE |
| | REVISION BP-3.0 CAN BE FOUND. |
| | |
| | 4. SHT P141 REVISION INDEX SHOWS REVISION BP-3.0. THIS |
| | REVISION WAS NOT FOUND OR APPROVED. NO REVISIONS WERE |
| | FOUND ON THIS SHEET. PLEASE CLARIFY. SECTION 106.1.3. |
| | |
| | 5. SHT P302 ALL REVISIONS SHALL BE CLOUDED AND |
| | INDICATED WITH A REVISION NUMBER THAT IS SHOWN ON THE |
| | REVISION INDEX. SECTION 106.1.3. THERE ARE REVISIONS |
| | THAT ARE CLOUDED, BUT SHOW NO REVISION NUMBER. (SEE |
| | BETWEEN COL. LINES 1 & 2). THERE WAS A CHANGE/REVISION |
| | THAT WAS NOT CLOUDED/NUMBERED TO THE RIGHT OF COL. LINE |
| | 1 JUST ABOVE COL. LINE B. PLEASE CLOUD AND NUMBER ALL |
| | REVISIONS. ALSO REVISION BP-3.0 WAS NOT FOUND OR |
| | APPROVED. PLEASE CLARIFY. SECTION 106.1.3. PLEASE |
| | INDICATE WHERE REVISION BP-3.0 CAN BE FOUND. |
| | |
| | 6. SHT P351 ALL REVISIONS SHALL BE CLOUDED AND |
| | INDICATED WITH A REVISION NUMBER THAT IS SHOWN ON THE |
| | REVISION INDEX. SECTION 106.1.3. THERE ARE REVISIONS |
| | THAT ARE CLOUDED, BUT SHOW NO REVISION NUMBER. ALSO |
| | REVISION BP-3.0 WAS NOT FOUND OR APPROVED. PLEASE |
| | CLARIFY. SECTION 106.1.3. PLEASE INDICATE WHERE |
| | REVISION BP-3.0 CAN BE FOUND. |
| | |
| | 7. SHT P501 ALL REVISIONS SHALL BE CLOUDED AND |
| | INDICATED WITH A REVISION NUMBER THAT IS SHOWN ON THE |
| | REVISION INDEX. SECTION 106.1.3. THERE ARE REVISIONS |
| | THAT ARE CLOUDED, BUT SHOW NO REVISION NUMBER. ALSO |
| | REVISION BP-3.0 WAS NOT FOUND OR APPROVED. PLEASE |
| | CLARIFY. SECTION 106.1.3. PLEASE INDICATE WHERE |
| | REVISION BP-3.0 CAN BE FOUND. ALSO MANY REVISION |
| | TRIANGLES WITH THE NUMBERS 1 & 2 ARE SHOWN ON THE FLOOR |
| | PLAN BUT NOT IN THE REVISION INDEX. PLEASE CLARIFY. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |