2008-09-29 13:35:10ELECTRICAL PLANS STAMPED IN ALL THREE SETS.
 LOW VOLTAGE SYSTEMS WILL BE UNDER SEPARATE PERMIT(S)
 HOWEVER MAY REFERENCE MAIN PERMIT NUMBER FOR TURN
 AROUND PERMIT.
2008-09-29 13:34:17 
 ** PROVISO/REDLINED **
  
 1) NOTE: EMERGENCY SYSTEMS AS SHOWN ON RISER FOR ATS
 NOTED FOR ELEVATOR IS NOT A SYSTEM UNDER NEC 700.
 PLEASE KNOW THIS MAY BE A SYSTEM AS NOTED FOR 701. ALL
 LIFE SAFETY ITEMS ARE UNDER POWER BACK UP OTHER THAN
 THE GENERATOR FOR LIFE SAFETY.
 UPON CONVERSATION WITH THE DESIGNERS OF RECORD THE
 BATTERY BACK UP LIGHTING ADDED IN MANY AREAS WILL NO
 LONGER BE BATTERY BACK UP AND AN ADDITIONAL GENERATOR
 MAY BE ADDED AT LATER DATE FOR OCCUPANCY UNDER
 GENERATOR POWER.
  
 2) NOTE: PLEASE SEE ROOM #168 ON E141 WHICH INDICATES A
 STANDARD SWITCH DEVICE. NEEDS OCCUPANCY SENSOR TYPE
 DEVICE. 13-415.1.ABC.1.2.
  
 3) NOTE: SELECTIVE COORDINATION STUDAY WILL BE REQUIRED
 FOR ALL EMERGENCY/LEGALLY REQUIRED SYSTEMS.
 700.27,701.8, 240.12 AND NFPA-110 SECTION 6.
  
 ** THE ABOVE NOTES ARE BASED ON INFORMATION THE RISER
 AND SYSTEM DESIGNATIONS WILL BE REVISED AND SUBMITTED
 WITHIN 30DAYS OF ISSUANCE OF PERMIT.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE TO
 CONTACT THIS OFFICE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  