| 2008-08-18 08:57:41 | THE WIND LOAD CALCULATIONS FOR THE HILL PHOENIX |
| | REFRIGERATION EQUIPMENT ROOM ARE OK. THE WIND LOAD |
| | CALCULATIONS FOR ALL OTHER OUTDOOR APPLIANCES ARE |
| | INSUFFICIENT. THE CALCULATIONS ONLY ACCOUNT FOR THE |
| | SIZE OF THE PANELS AND THE STRENGTH OF THE SCREWS |
| | HOLDING THE PANELS. THEY DO NOT COVER ANY OTHER ASPECTS |
| | OF THE CONSTRUCTION OF THE APPLIANCES. A COMPREHENSIVE |
| | ANALYSIS OF THE OVERALL CONSTRUCTION OF THE APPLIANCES |
| | IS REQUIRED TO DEMONSTRATE COMPLIANCE WITH FBCM 301.13. |
| | PLEASE CORRECT AND RESUBMIT. THIS IS THE ONLY |
| | OUTSTANDING MECHHANICAL REVIEW COMMENT AT THIS TIME. AS |
| | SUCH, IT WILL BE COVERED BY A PROVISO TO FACILITATE THE |
| | PROGRESS OF THE PROJECT WHILE A NEW ANALYSIS OR TESTING |
| | CAN BE DONE. |
| | |
| | REVIEW WILL REMAIN IN FAILED STATUS UNTIL THERE HAS |
| | BEEN AN ACTUAL APPLICATION FOR PERMIT. THESE PLANS ARE |
| | STILL SUBMITTED UNDER PLAN REVIEW ONLY STATUS. THE |
| | FOLLOWING PROVISO WILL BE ISSUED WITH THE PERMIT SET OF |
| | PLANS: |
| | |
| | ***************PROVISO************** |
| | ALL MECHANICAL APPLIANCES EXPOSED TO WIND SHALL |
| | DEMONSTRATE COMPLIANCE WITH FBCM 301.13 BY ANALYSIS OR |
| | TESTING. SUPPORTING DOCUMENTATION SHALL BE PROVIDED TO |
| | THE CODE OFFICIAL IN TIME FOR A PASSED REVIEW PRIOR TO |
| | INSTALLATION OF OUTDOOR APPLIANCES. |
| | |