| 2008-09-17 15:51:01 | |
| | ** DENIED REVIEW ** |
| | |
| | *** PLANS ARE IN FAILED STATUS** |
| | *** NEW SHEETS WILL BE REQUIRED. AT THIS TIME A FINAL |
| | LIST OF NEW SHEETS CAN NOT BE DETERMINED AT THIS TIME |
| | BASED ON COMMENT NUMBER ONE BELOW. |
| | |
| | 1) NOTE: LIGHTING FOR ALL AREAS OUT AND AWAY FROM THE |
| | BUILDING INCLUDING OUT OF THE GARAGE IS CONSIDERED LIFE |
| | SAFETY REQUIRING EGRESS LIGHTING. IF THE GENERATOR AS |
| | NOTED WILL NO LONGER BE FEEDING LIGHTING FOR EGRESS |
| | BACK UP IN AREAS SUCH AS THE GARAGE EGRESS PATHS WILL |
| | REQUIRE BATTERY BACK UP OF SOME SORT. THE GENERATOR |
| | WOULD NO LONGER BE A *LIFE SAFETY/EMERGENCY* GENERATOR |
| | BY DEFINITION. |
| | PLEASE SEE NFPA-101 7.8, 7.9. |
| | CALLED MR. ERDMAN FROM NELSON-RUDIE AND WENT OVER MANY |
| | SCENARIOS. |
| | THE RISER STILL INDICATES THERE BEING A LIFE SAFETY/ |
| | EMERGENCY ATS AND SYSTEM. HOW CAN THE GENERATOR BE |
| | CONSIDERED A LIFE SAFETY SYSTEM? |
| | PLEASE SEE DEFINITIONS OF NFPA-110, NFPA-70, |
| | 700.1,701.1, AND WIRING OF SYSTEMS IN 700.9, 701.10 |
| | ETC. |
| | NOTES ON PLANS WOULD NEED TO BE CHANGED, RISER, |
| | LIGHTING ETC. A PHONE CONFERENCE AT LENGTH MAY BE |
| | NEEDED ONCE ARCHITECT AND ENGINEER CONTACT EACH OTHER |
| | TO GO OVER ITEMS BROUGHT UP. |
| | *** PLEASE SEE DEFINITIONS OF SYSTEM AS NOTED ABOVE. |
| | |
| | 2) NOTE: NO GROSS ERRORS ON INPUT DATA REPORT AS |
| | SUBMITTED AS NOTED IN 13-103.3 |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |