| 2008-09-10 10:05:12 | BUILDING PLAN REVIEW |
| | PERMIT: 08020128 |
| | ADD: 1760 PALM BEACH LAKES |
| | CONT: RYAN COMPANIES |
| | TEL: (621)677-7235 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | SEPT. 10/08 |
| | BUILDING TYPE: I-B/ FULLY SPRINKLERED |
| | |
| | ACTION: REVIEWED |
| | |
| | 1)PROVISO: SUBMITTED WERE TWO TYPES OF FLOOR EXSPANSION |
| | JOINT MATERIALS, IN ONE CASE THE SINCE THE HFXR-1-1 |
| | SYSTEM DOES INDICATE THAT THE FIRE BARRIER IS OPTIONAL, |
| | SHOP DRAWINGS ARE TO BE REVIEWED BY THE DESIGN TEAM |
| | BEFORE SUBMITTED TO THE BUILDING DEPARTMENT, SINCE THE |
| | CUT SHEETS PROVIDED DO NOT INDICATE THE REQUIRED FIRE |
| | BARRIER SYSTEM TO TIE WITH THIS PRODUCT. |
| | THE SECOND PRODUCT SUBMITTED WAS MM PYRO-FLEX/ PF |
| | SERIES AGAIN THERE IS NO INFORMATION AS TO THE REQUIRED |
| | THICKNESS OF THIS PRODUCT OR THE HOURLY RATING OF THE |
| | PRODUCT, THE DESIGN TEAM BEFORE SUBMITTED TO THE |
| | BUILDING DEPARTMENT, SINCE THE CUT SHEETS PROVIDED DO |
| | NOT INDICATE THE REQUIRED FIRE BARRIER SYSTEM TO TIE |
| | WITH THIS PRODUCT. |
| | |
| | 2) BUILDING PROVISO: PLEASE PROVIDE THE MANUFACTURERS |
| | SPEC FOR FIRE RESISTANT RATING OF STRUCTURAL MEMBERS |
| | BEFORE FRAMING INSPECTION. THE CODE ANALYSIS INDICATES |
| | THIS TO BE A TYPE I-B BUILDING REQUIRING FIRE RATINGS |
| | OF THE STRUCTURAL STEEL AND BAR JOIST, PLEASE PROVIDE |
| | THE MANUFACTURERS SPEC AND THE THICKNESS REQUIRED TO |
| | ACHIEVE THE REQUIRED FIRE RATING. TABLE 601 & 721.5. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |