Plan Review Notes For Permit 08020128
Permit Number 08020128
Review Stop M
Sequence Number 3
Notes
Date Text
2008-08-05 10:30:33REVIEW IN TEMPORARY FAIL STATUS PENDING RESOLUTION OF
 COMMENT #5 AND REVIEW OF WIND LOAD DATA FOR MECHANICAL
 APPLIANCES (BY STRUCTURAL REVIEWER). COMMENT #5
 REQUIRES A THROUGH-PENETRATION DETAIL FOR 8" ROUND DUCT
 PENETRATING RATED WALL WITHOUT FIRE DAMPER. SPOKE TO
 ERIC FROM NELSON-RUDIE VIA TELEPHONE. THE DESIGN TEAM
 HAS REQUESTED AN OPPORTUNITY TO PROVIDE THE MISSING
 DOCUMENTATION DURING THIS REVIEW CYCLE. THE WIND LOAD
 DATA FOR THE APPLIANCES WAS NOT PROVIDED WITH ORIGINAL
 SEAL/SIGNATURE OF THE STRUCTURAL ENGINEERS RESPONSIBLE
 FOR THE REPORTS. THIS WILL NEED TO BE CORRECTED. IF
 NECESSARY, ONCE ALL OUTSTANDING ISSUES ARE ADDRESSED,
 THIS MAY BE COVERED WITH A PROVISO TO ALLOW THE PROJECT
 TO MOVE FORWARD.
  