| Plan Review Notes For Permit 08020128 |
| Permit Number |
08020128 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-08-05 10:30:33 | REVIEW IN TEMPORARY FAIL STATUS PENDING RESOLUTION OF | | | COMMENT #5 AND REVIEW OF WIND LOAD DATA FOR MECHANICAL | | | APPLIANCES (BY STRUCTURAL REVIEWER). COMMENT #5 | | | REQUIRES A THROUGH-PENETRATION DETAIL FOR 8" ROUND DUCT | | | PENETRATING RATED WALL WITHOUT FIRE DAMPER. SPOKE TO | | | ERIC FROM NELSON-RUDIE VIA TELEPHONE. THE DESIGN TEAM | | | HAS REQUESTED AN OPPORTUNITY TO PROVIDE THE MISSING | | | DOCUMENTATION DURING THIS REVIEW CYCLE. THE WIND LOAD | | | DATA FOR THE APPLIANCES WAS NOT PROVIDED WITH ORIGINAL | | | SEAL/SIGNATURE OF THE STRUCTURAL ENGINEERS RESPONSIBLE | | | FOR THE REPORTS. THIS WILL NEED TO BE CORRECTED. IF | | | NECESSARY, ONCE ALL OUTSTANDING ISSUES ARE ADDRESSED, | | | THIS MAY BE COVERED WITH A PROVISO TO ALLOW THE PROJECT | | | TO MOVE FORWARD. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|