Plan Review Notes
Plan Review Notes For Permit 08020128
Permit Number 08020128
Review Stop E
Sequence Number 3
Notes
Date Text
2008-08-14 17:05:24 
  
  
  
  
 ** DENIED REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING.
  
  
  
  
 1) NOTE: PLANS STILL SUBMITTED ONLY FOR PLAN REVIEW AND
 NOT SUBMITTED UNDER PERMIT APPLICATION AT THIS TIME.
  
 2) NOTE: PLEASE BE SURE TO GO THROUGH THE SUBMITTED
 ENERGY CALCULATIONS AND COORDINATE ALL INFORMATION WITH
 PLANS.
 ON THE PREVIOUS REVIEW ONE OF THE EXAMPLES GIVEN WAS
 THE FACT MANY OF THE EXTERIOR LIGHTS SHOWN ON PLANS WAS
 NOT IN THE INPUT DATA REPORT. THE RESPONSE FORM THE
 DESIGN TEAM IS THAT THE EXTERIOR LIGHTS ARE LOCATED IN
 THE EXTERIOR SECTION OF THE INPUT DATA REPORT. THIS
 OFFICE/REVIEWER IS AWARE OF WHERE THE EXTERIOR LIGHTS
 ARE SHOWN IN AN INPUT DATA REPORT. THE COMMENT WAS IN
 FACT THE LIGHTING SHOWN ON THE PLANS FOR ALL EXTERIOR
 LIGHTS DID NOT MATCH WITH THE LIGHTING SHOWN IN THE
 INPUT DATA REPORT.
 PLEASE SEE THE FIXTURE SCHEDULE AS THERE ARE FIXTURES
 LISTED AND ON PLANS WHICH ARE NOT IN THE INPUT DATA
 REPORT FOR EXTERIOR LIGHTS.
 ONE EXAMPLE IS THE 94 WATT FIXTURE AS NO FIXTURES IN
 THE IDR ARE 94WATTS.
 ANOTHER IS THE COUNT OF THE 50WATT FIXTURES AS THE
 PLANS SHOW MORE THAN THE 6 WHICH IS INDICATED IN THE
 IDR.
 ** THIS IS ONLY A COUPLE AS NOTED FOR DESIGN
 BENEFIT.
  
 13-415.2, 13-415.2.ABC.1.1,.1.2 AND .1.3 13-400.A.3
  
 3) NOTE: PLEASE SEE NFPA-101 7.8.1.3 AS NOTED ON
 PREVIOUS REVIEWS. ALL STAIRS ARE REQUIRED TO CONTAIN AT
 LEAST 10FT CANDLES UNDER NORMAL CONDITIONS AND IS
 PERMITTED TO GO DOWN TO 1FT CANDLE UNDER EMERGENCY
 CONDITIONS. PLEASE SEE SHEET ULEN WHICH IS A NEW SHEET
 PROVIDED. PLEASE SEE THE LEVELS SHOWN UNDER NORMAL
 CONDITIONS ARE IN FACT ABOUT 10 TIMES LESS THAN THE
 MINIMUM REQUIRED BY THE LIFE SAFETY CODE.
 ALL LEVELS MUST MEET MINIMUM.
 PLEASE SEE THE EDC STAIRS. THE PLANS INDICATE SOME SORT
 OF EMERGENCY LEVEL HOWEVER THE SECTION OF THE PLANS FOR
 THE FRONT EDC STAIRS IS NOT READABLE AND ONLY SHOWS
 EMERGENCY LEVELS.
 ** KEEP NOTE** THE LIGHTING LEVELS OF OTHER AREAS SHALL
 NOT BE FIGURED INTO THE EQUATION OF AVERAGE.
  
 ** THE PREVIOUS REVIEW REQUESTED A LETTER FROM TARGET
 CORPORATE OFFICES THAT THE STORE WILL NOT BE OCCUPIED
 UNDER EMERGENCY POWER. THE RESPONSE MENTIONS TO SEE
 LETTER FROM TARGET CORPORATION.
 THE LETTER SUBMITTED IS NOT FROM TARGET CORPORATE
 OFFICER.
 THE LETTER STATES THAT TARGET TEAM SHALL EVACUATE ALL
 OCCUPANTS AND THE BUILDING WILL NOT BE *PUBLICLY
 OCCUPIED*.
  
 ** THE LIFE SAFETY CODE DOES NOT ONLY ADDRESS THE
 PUBLIC IS ALSO ADDRESSES THE SAFETY OF ALL EMPLOYEES.
 THE DOCUMENTS SHALL BE FROM TARGET CORPORATE BEING ONE
 OF THE CORPORATION ATTORNEYS/OFFICERS AND IT SHALL
 STATE ALL OCCUPANTS INCLUDING EMPLOYEES SHALL EVACUATE
 OR PLACE BATTERY BACK UP FIXTURES IN EGRESS AREAS
 MEETING THE MINIMUM LEVELS UNDER EMERGENCY EGRESS.
  
 LS 101 7.8, 7.9
  
 4) NOTE: PLEASE PROVIDE INFORMATION WHERE THE RATING
 BETWEEN THE EPSS EQUIPMENT AND OTHER NORMAL EQUIPMENT
 IS SHOWN. THE RESPONSE MENTIONS THE 1HR SEPARATION IS
 PROVIDED HOWEVER BASED ON PLANS AND COORDINATION OF
 SUPPORTING DOCUMENTS THIS COULD NOT BE LOCATED.
 NFPA-110 7.2
  
 5) NOTE: PLEASE SEE COMMENT #18 FROM PREVIOUS REVIEW.
 THE RESPONSE PACKAGE CONTAINS SPECS/CUT SHEETS FOR TYPE
 OF DEVICE WHICH SNAPS ONTOTHE BREAKER. THE RESPONSE
 MENTIONS DISCONNECTS WERE ADDED. IF DISCONNECTS WILL BE
 USED AND NO PROPOSAL OF SOME SORT OF DEVICE BEING ADDED
 TO BREAKER IS GOING TO BE PROPOSED PLEASE REMOVE FROM
 PACKAGE AND ANY OTHER PLANS/DOCUMENTS.
  
 422.30.31.110.3.90.7. ETC
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]