Plan Review Notes
Plan Review Notes For Permit 08020128
Permit Number 08020128
Review Stop B
Sequence Number 3
Notes
Date Text
2008-08-07 13:46:10BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 3RD REVIEW 08-07-08
 ACTION: DENIED
  
 1-4) COMPLIED.
  
 5) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 6) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8-10) COMPLIED.
  
 11)INFORMATIONAL ONLY, PLEASE REVIEW SHEET A021 EXIT
 ANALYSIS, SALES AREA PER SQ FT/ OCC. THIS IS THE 2ND
 FLOOR WHICH IS NOT CONSIDERED THE GRADE FLOOR. THE
 OCCUPANT LOAD FOR THIS FLOORS SALES AREA WOULD BE
 FIGURED AT 60 FT / OCCUPANT NOT THE 30 AS INDICATED IN
 THE TABLE SEE TABLE 1004.1.2.PLAN NOTES HAVE BEEN ADDED
 TO THE EXIT STAIRWAY SCHEDULE.
  
 11A) COMPLIED.
  
 11B) 08-11-08 COMPLIED.
  
 11C-11K) COMPLIED.
  
 12A)PROVISO: SUBMITTED WERE TWO TYPES OF FLOOR
 EXSPANSION JOINT MATERIALS, IN ONE CASE THE SINCE THE
 HFXR-1-1 SYSTEM DOES INDICATE THAT THE FIRE BARRIER IS
 OPTIONAL, SHOP DRAWINGS ARE TO BE REVIEWED BY THE
 DESIGN TEAM BEFORE SUBMITTED TO THE BUILDING
 DEPARTMENT, SINCE THE CUT SHEETS PROVIDED DO NOT
 INDICATE THE REQUIRED FIRE BARRIER SYSTEM TO TIE WITH
 THIS PRODUCT.
 THE SECOND PRODUCT SUBMITTED WAS MM PYRO-FLEX/ PF
 SERIES AGAIN THERE IS NO INFORMATION AS TO THE REQUIRED
 THICKNESS OF THIS PRODUCT OR THE HOURLY RATING OF THE
 PRODUCT, THE DESIGN TEAM BEFORE SUBMITTED TO THE
 BUILDING DEPARTMENT, SINCE THE CUT SHEETS PROVIDED DO
 NOT INDICATE THE REQUIRED FIRE BARRIER SYSTEM TO TIE
 WITH THIS PRODUCT.
  
 13) 08-11-08 COMPLIED.
 14-19) COMPLIED.
  
 20) COMPLIED.
  
 21A) 08-11-08 COMPLIED.
  
 21B-C) 11-08-08 COMPLIED.T
  
 22-30) COMPLIED.
  
 31) BUILDING PROVISO: PLEASE PROVIDE THE MANUFACTURERS
 SPEC FOR FIRE RESISTANT RATING OF STRUCTURAL MEMBERS
 BEFORE FRAMING INSPECTION. THE CODE ANALYSIS INDICATES
 THIS TO BE A TYPE I-B BUILDING REQUIRING FIRE RATINGS
 OF THE STRUCTURAL STEEL AND BAR JOIST, PLEASE PROVIDE
 THE MANUFACTURERS SPEC AND THE THICKNESS REQUIRED TO
 ACHIEVE THE REQUIRED FIRE RATING. TABLE 601 & 721.5.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.