| 2008-08-07 13:46:10 | BUILDING PLAN REVIEW |
| | PERMIT: 08020128 (PLAN REVIEW) |
| | ADD: 1760 PALM BEACH LAKES |
| | CONT: RYAN COMPANIES |
| | TEL: (621)677-7235 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | BUILDING TYPE: I-B/ FULLY SPRINKLERED |
| | 3RD REVIEW 08-07-08 |
| | ACTION: DENIED |
| | |
| | 1-4) COMPLIED. |
| | |
| | 5) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION. |
| | ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL |
| | BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT |
| | THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH |
| | ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT |
| | TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER |
| | TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY |
| | OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL |
| | OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| | THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 6) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW |
| | CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO |
| | REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND |
| | DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION |
| | SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE |
| | DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND |
| | DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH |
| | WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR |
| | SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS |
| | WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED |
| | SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN |
| | ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO |
| | VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE |
| | PURSUANT TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 8-10) COMPLIED. |
| | |
| | 11)INFORMATIONAL ONLY, PLEASE REVIEW SHEET A021 EXIT |
| | ANALYSIS, SALES AREA PER SQ FT/ OCC. THIS IS THE 2ND |
| | FLOOR WHICH IS NOT CONSIDERED THE GRADE FLOOR. THE |
| | OCCUPANT LOAD FOR THIS FLOORS SALES AREA WOULD BE |
| | FIGURED AT 60 FT / OCCUPANT NOT THE 30 AS INDICATED IN |
| | THE TABLE SEE TABLE 1004.1.2.PLAN NOTES HAVE BEEN ADDED |
| | TO THE EXIT STAIRWAY SCHEDULE. |
| | |
| | 11A) COMPLIED. |
| | |
| | 11B) 08-11-08 COMPLIED. |
| | |
| | 11C-11K) COMPLIED. |
| | |
| | 12A)PROVISO: SUBMITTED WERE TWO TYPES OF FLOOR |
| | EXSPANSION JOINT MATERIALS, IN ONE CASE THE SINCE THE |
| | HFXR-1-1 SYSTEM DOES INDICATE THAT THE FIRE BARRIER IS |
| | OPTIONAL, SHOP DRAWINGS ARE TO BE REVIEWED BY THE |
| | DESIGN TEAM BEFORE SUBMITTED TO THE BUILDING |
| | DEPARTMENT, SINCE THE CUT SHEETS PROVIDED DO NOT |
| | INDICATE THE REQUIRED FIRE BARRIER SYSTEM TO TIE WITH |
| | THIS PRODUCT. |
| | THE SECOND PRODUCT SUBMITTED WAS MM PYRO-FLEX/ PF |
| | SERIES AGAIN THERE IS NO INFORMATION AS TO THE REQUIRED |
| | THICKNESS OF THIS PRODUCT OR THE HOURLY RATING OF THE |
| | PRODUCT, THE DESIGN TEAM BEFORE SUBMITTED TO THE |
| | BUILDING DEPARTMENT, SINCE THE CUT SHEETS PROVIDED DO |
| | NOT INDICATE THE REQUIRED FIRE BARRIER SYSTEM TO TIE |
| | WITH THIS PRODUCT. |
| | |
| | 13) 08-11-08 COMPLIED. |
| | 14-19) COMPLIED. |
| | |
| | 20) COMPLIED. |
| | |
| | 21A) 08-11-08 COMPLIED. |
| | |
| | 21B-C) 11-08-08 COMPLIED.T |
| | |
| | 22-30) COMPLIED. |
| | |
| | 31) BUILDING PROVISO: PLEASE PROVIDE THE MANUFACTURERS |
| | SPEC FOR FIRE RESISTANT RATING OF STRUCTURAL MEMBERS |
| | BEFORE FRAMING INSPECTION. THE CODE ANALYSIS INDICATES |
| | THIS TO BE A TYPE I-B BUILDING REQUIRING FIRE RATINGS |
| | OF THE STRUCTURAL STEEL AND BAR JOIST, PLEASE PROVIDE |
| | THE MANUFACTURERS SPEC AND THE THICKNESS REQUIRED TO |
| | ACHIEVE THE REQUIRED FIRE RATING. TABLE 601 & 721.5. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |