| Date |
Text |
| 2008-06-11 08:57:21 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | MUNICIPAL CODE CITY WPB |
| | |
| | ****FROM PREVIOUS PLAN REVIEW: |
| | |
| | PLANS IN FOR PLAN REVIEW ONLY AT THIS TIME: |
| | |
| | 1. OK |
| | 2. OK |
| | |
| | 3. SHT G001 SHEET INDEX. 3 SHEETS ON THE INDEX WERE NOT |
| | FOUND & 2 "F" SHEETS & 10 "R" SHEETS SUBMITTED ARE NOT |
| | SHOWN ON THE INDEX. PLEASE CORRELATE. SECTION 106.1.2. |
| | ****RESPONSE NOTED, BUT THERE ARE SHEETS MISSING FROM |
| | AT LEAST ONE SET OF PLANS. PLEASE CHECK ALL SETS OF |
| | PLANS TO MAKE SURE THE SHEETS SUBMITTED CORRELATE WITH |
| | THE SHEET INDEX ON SHT G001. |
| | |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | |
| | 7. SHT A313 SHOW THE CLEAR FLOOR SPACE FOR ACCESSIBLE |
| | WATER CLOSETS AND LAVS PER SECTIONS 11-4.16.2 & |
| | 11-4.19.3. |
| | ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS |
| | REQUIRED FOR ALL ACCESSIBLE WATER CLOSETS NO MATTER IF |
| | THEY ARE IN STALLS OR TOILET ROOMS. THE REQUIREMENT IS |
| | FOR TRANSFERING FROM THE WHEELCHAIR TO THE W/C. THE |
| | TURNING AREA IS NOT REQUIRED IN THE STALL AND IS A |
| | DIFFERENT REQUIREMENT FROM THE CLEAR FLOOR SPACE. |
| | |
| | 8. OK |
| | 9. OK |
| | 10. OK (WILL PROVISO - REQUIRED AT TIME OF FINAL |
| | PLUMBING INSPECTION) |
| | |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | |
| | 14. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE |
| | UTILITY DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL |
| | COMPLIANCE. ALSO THEPHOTO PROCESSING MAY BE REQUIRED |
| | TO INSTALL A NEUTRALIZING TANK. PLEASE CONTACT RODNEY |
| | COMPO, ENVIRONMENTAL COMPLIANCE AT (561)644-1821, OR |
| | BY FAX (561) 822-2287, OR E-MAIL [email protected]. A |
| | WRITTEN DETERMINATION FOR BOTH ISSUES SHALL BE |
| | SUBMITTED WITH PLANS INDICATING THE REQUIREMENT |
| | OUTCOME. ARTICLE III SECTION 90-124(7). ****RESPONSE |
| | NOTED, WAITING FOR REVISION FROM RODNEY COMPO. |
| | |
| | 15. OK |
| | 16. OK |
| | 17. OK |
| | 18. OK (SEE COMMENT #10). |
| | 19. OK |
| | 20. OK |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | |
| | 24. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING IS |
| | REQUIRED FOR THE GAS PERMIT. |
| | |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. OK |
| | E. OK |
| | F. OK |
| | G. OK |
| | 25. OK |
| | |
| | **********NEW COMMENT*********** |
| | |
| | 1B. SHOW THE SHUT OFF VALVE AND THE SECOND STAGE |
| | REGULATOR ON THE GAS RISER DIAGRAM. THE SHUT OFF VALVE |
| | SHALL BE INSTALLED UPSTREAM OF THE REGULATOR. SECTION |
| | 409.4. |
| | |
| | 2B. SUBMIT THE MANUFACTURE SPECIFICATION SHEETS FOR THE |
| | SECOND STAGE GAS REGULATOR. INDICATE MODEL NUMBER AND |
| | SHOW LISTING FOR REGULATOR ON SHEETS. SECTION 410.2. |
| | |
| | 3B. VENTED REGULATORS SHALL COMPLY WITH SECTION 410.3. |
| | |
| | 4B. SHTS P100, P3OO & P502 THE FLOOR DRAIN SHOWN IN THE |
| | MECHANICAL ROOM SHALL CONNECT TO THE SANITARY SYSTEM, |
| | NOT THE STORM SYSTEM. ARTICLE III SECTION 203(A). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |