Plan Review Notes
Plan Review Notes For Permit 08020128
Permit Number 08020128
Review Stop P
Sequence Number 2
Notes
Date Text
2008-06-11 08:57:21DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 MUNICIPAL CODE CITY WPB
  
 ****FROM PREVIOUS PLAN REVIEW:
  
 PLANS IN FOR PLAN REVIEW ONLY AT THIS TIME:
  
 1. OK
 2. OK
  
 3. SHT G001 SHEET INDEX. 3 SHEETS ON THE INDEX WERE NOT
 FOUND & 2 "F" SHEETS & 10 "R" SHEETS SUBMITTED ARE NOT
 SHOWN ON THE INDEX. PLEASE CORRELATE. SECTION 106.1.2.
 ****RESPONSE NOTED, BUT THERE ARE SHEETS MISSING FROM
 AT LEAST ONE SET OF PLANS. PLEASE CHECK ALL SETS OF
 PLANS TO MAKE SURE THE SHEETS SUBMITTED CORRELATE WITH
 THE SHEET INDEX ON SHT G001.
  
 4. OK
 5. OK
 6. OK
  
 7. SHT A313 SHOW THE CLEAR FLOOR SPACE FOR ACCESSIBLE
 WATER CLOSETS AND LAVS PER SECTIONS 11-4.16.2 &
 11-4.19.3.
 ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS
 REQUIRED FOR ALL ACCESSIBLE WATER CLOSETS NO MATTER IF
 THEY ARE IN STALLS OR TOILET ROOMS. THE REQUIREMENT IS
 FOR TRANSFERING FROM THE WHEELCHAIR TO THE W/C. THE
 TURNING AREA IS NOT REQUIRED IN THE STALL AND IS A
 DIFFERENT REQUIREMENT FROM THE CLEAR FLOOR SPACE.
  
 8. OK
 9. OK
 10. OK (WILL PROVISO - REQUIRED AT TIME OF FINAL
 PLUMBING INSPECTION)
  
 11. OK
 12. OK
 13. OK
  
 14. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 UTILITY DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE. ALSO THEPHOTO PROCESSING MAY BE REQUIRED
 TO INSTALL A NEUTRALIZING TANK. PLEASE CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE AT (561)644-1821, OR
 BY FAX (561) 822-2287, OR E-MAIL [email protected]. A
 WRITTEN DETERMINATION FOR BOTH ISSUES SHALL BE
 SUBMITTED WITH PLANS INDICATING THE REQUIREMENT
 OUTCOME. ARTICLE III SECTION 90-124(7). ****RESPONSE
 NOTED, WAITING FOR REVISION FROM RODNEY COMPO.
  
 15. OK
 16. OK
 17. OK
 18. OK (SEE COMMENT #10).
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
  
 24. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING IS
 REQUIRED FOR THE GAS PERMIT.
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 G. OK
 25. OK
  
 **********NEW COMMENT***********
  
 1B. SHOW THE SHUT OFF VALVE AND THE SECOND STAGE
 REGULATOR ON THE GAS RISER DIAGRAM. THE SHUT OFF VALVE
 SHALL BE INSTALLED UPSTREAM OF THE REGULATOR. SECTION
 409.4.
  
 2B. SUBMIT THE MANUFACTURE SPECIFICATION SHEETS FOR THE
 SECOND STAGE GAS REGULATOR. INDICATE MODEL NUMBER AND
 SHOW LISTING FOR REGULATOR ON SHEETS. SECTION 410.2.
  
 3B. VENTED REGULATORS SHALL COMPLY WITH SECTION 410.3.
  
 4B. SHTS P100, P3OO & P502 THE FLOOR DRAIN SHOWN IN THE
 MECHANICAL ROOM SHALL CONNECT TO THE SANITARY SYSTEM,
 NOT THE STORM SYSTEM. ARTICLE III SECTION 203(A).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved