2008-07-01 09:08:29*****UNSAT*****
  
  
 16.ON SHEET A020 AND A021, THE PATH OF EGRESS IS
 SHOWN TO PASS THROUGH OBSTRUCTIONS.THE PATH OF EGRESS
 (TRAVEL DISTANCE ROUTE) SHALL NOT BE THROUGH AN
 OBSTRUCTION OR POSSIBLE OBSTRUCTION
  
 18.ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTERS' EMERGENCY OPERATIONS OF ASME A17.1;AND
 SHALL BE ABLE TO ACCOMMODATE PARAMEDICAL EQUIPMENT. ADD
 COMMENT TO AN APPROPIATE PLAN SHEET
  
 24.NFPA 13 - 2002 EDITION - SHALL BE REFERENCED FOR
 THE INSTALLATION OF THE BUILDING'S SPRINKLER SYSTEM. IT
 IS INDICATED ON SHEET F300 REFERENCING THE 2004
 EDITION.THERE STILL IS A REFERENCE TO 2004 EDITION IN
 THE 61G15-32.004.(2) UNDER APPLICABLE NFPA STANDARD TO
 BE APPLIED
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  