| 2008-06-23 17:08:31 | ** DENIED2ND PLAN REVIEW** |
| | |
| | ** PLAN REVIEW ONLY. |
| | |
| | ** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING. SOME OF THESE |
| | ARE THE SAME NOTES, COMMENTS AND/OR CODE SECTIONS. |
| | |
| | ** PLEASE SEE THERE ARE SOME NEW COMMENTS DUE TO ITEMS |
| | BEING CHANGED OR PLACED ON THE PLANS FOR THE FIRST |
| | TIME. |
| | |
| | ** PLEASE SEE THERE ARE ALSO NEW COMMENTS. |
| | |
| | ** AS STATED ON PREVIOUS REVIEW THERE WERE SOME ITEMS |
| | NOT YET SUBMITTED IN WHICH A REVIEW OF THOSE ITEMS |
| | COULD NOT BE DONE. |
| | |
| | |
| | |
| | 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR * PLAN |
| | REVIEW ONLY * FOR A SECOND REVIEW AND HAVE NOT BEEN |
| | SUBMITTED UNDER PERMIT APPLICATION. |
| | PLEASE KNOW THAT ONCE ALL ITEMS FOR CODE REVIEWS ARE |
| | DONE PLANS WILL STILL REMAIN IN FAILED STATS UNTIL |
| | PERMIT APPLICATION HAS BEEN MADE. VERIFICATION OF |
| | SEVERAL ITEMS SUCH AS VALID LICENSING ETC IS DONE AT |
| | TIME OF APPLICATION BEFORE ISSUANCE OF PERMIT(S). THIS |
| | COMMENT WILL REPEAT AS PERMIT APPLICATION HAS NOT BEEN |
| | MADE. |
| | IF THERE ARE ANY QUESTIONS ON THIS PLEASE CONTACT THIS |
| | OFFICE/REVIEWER. |
| | |
| | 2) NOTE: PLEASE SEE NOTICE AT THE END OF THIS REVIEW |
| | WHICH IS NOTED AS ** IMPORTANT** ON CORRECT PROCEDURE |
| | ON RE-SUBMITTING PLANS AND THE REMOVING OF OLD/VOIDED |
| | SHEETS. IF THERE QUESTIONS PLEASE CONTACT THIS |
| | REVIEWER. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO EPS |
| | LEVEL-1 EQUIPMENT WHICH IS NOT PERMITTED TO BE LOCATED |
| | IN THE SAME ELECTRICAL ROOM AS THE NORMAL ELECTRICAL |
| | EQUIPMENT. THE RESPONSE MENTIONS TO SEE NEW REVISED |
| | E355 HOWEVER THE PLANS NOW ONLY SHOW SORT OF DOORS AND |
| | DASHED LINES. THIS DOES NOT PROVIDE ANY RATINGS OF |
| | WALLS. THIS DOES NOT PROVIDE ANY LISTED ASSEMBLIES FOR |
| | WALL. THIS DOES NOT PROVIDE ANY INFORMATION ON DOORS TO |
| | BE USED. NO WALLS OR DOORS WERE LOCATED ON OTHER TRADE |
| | PLANS SUCH AS ARCHITECTURAL OR MECHANICAL SHEETS. |
| | PLEASE SEE THE FOLLOWING TEXT REMAINS FROM PREVIOUS |
| | REVIEW WITH RESPECT TO NFPA-110 CHAPTER 7. |
| | PLEASE SEE NFPA-110 7.2, 7.1.3 PLEASE SEE 7.2.2.1 BELOW |
| | ALSO. |
| | 7.2.1THE EPS SHALL BE INSTALLED IN A SEPARATE ROOM FOR |
| | LEVEL 1 INSTALLATIONS. EPSS EQUIPMENT SHALL BE |
| | PERMITTED TO BE INSTALLED IN THIS ROOM. |
| | 7.2.1.1THE ROOM SHALL HAVE A MINIMUM 2-HOUR FIRE RATING |
| | OR BE LOCATED IN AN ADEQUATE ENCLOSURE LOCATED OUTSIDE |
| | THE BUILDING CAPABLE OF RESISTING THE ENTRANCE OF SNOW |
| | OR RAIN AT A MAXIMUM WIND VELOCITY REQUIRED BY LOCAL |
| | BUILDING CODES. |
| | 7.2.1.2NO OTHER EQUIPMENT, INCLUDING ARCHITECTURAL |
| | APPURTENANCES, EXCEPT THOSE THAT SERVE THIS SPACE, |
| | SHALL BE PERMITTED IN THIS ROOM. |
| | 7.2.2EPSS EQUIPMENT SHALL NOT BE INSTALLED IN THE SAME |
| | ROOM WHERE THE NORMAL ELECTRICAL SERVICE EQUIPMENT IS |
| | INSTALLED. |
| | 7.2.2.1TRANSFER SWITCHES SHALL BE PERMITTED TO BE |
| | INSTALLED IN THE NORMAL ELECTRICAL SERVICE ROOM WHERE |
| | TWICE THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF |
| | NFPA 70, NATIONAL ELECTRICAL CODE, EXISTS BETWEEN |
| | EQUIPMENT ENCLOSURES. |
| | |
| | 4) NOTE: PLEASE PROVIDE INFORMATION ON LOAD SHEDDING |
| | FOR OTHER SYSTEMS ON EPS LEVEL-1 GENERATOR PER NFPA-110 |
| | 7.1.5. WHAT PROVIDES SHEDDING OF NON-EMERGENCY OR ANY |
| | LEGALLY REQUIRED LOADS? |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO |
| | FOUR POLE TRANSFER SWITCHES. THESE ARE NOW SHOWN ON |
| | RISER AS FOUR POLE YET WHERE IS THE SEPARATELY DERIVED |
| | GENERATOR GROUNDING PER 250.20, 250.50? |
| | |
| | 6) NOTE: PLEASE SEE THE FOLLOWING COMMENTS WITH RESPECT |
| | TO LIGHTING CONTROLS FOR FLORIDA BUILDING CODE CHAPTER |
| | 13 REQUIREMENTS. |
| | PLEASE SEE THERE ARE SEVERAL LOCATIONS IN WHICH |
| | REQUIRED LIGHTING CONTROLS ARE NOT. |
| | PLEASE SEE 13-415.1.ABC.1, .1.1, .1.2 , .1.3 AND .1.4. |
| | |
| | A) ALL SEPARATE SPACES CONTAINING FLOOR TO CEILING |
| | HEIGHT PARTITIONS ARE REQUIRED TO CONTAIN ONE OR MORE |
| | OF THE FOLLOWING FOR SEPARATE SPACE CONTROL. INDIVIDUAL |
| | OCCUPANCY SENSORS OR AN OVER RIDE DEVICE OF SOME SORT |
| | TO OVER RIDE ANY TIME OF DAY SCHEDULING. |
| | PLEASE SEE ROOMS 121,122. RESPONSE MENTIONS TO SEE |
| | REVISED E-131 HOWEVER IT IS UNCLEAR WHAT WAS REVISED. |
| | PLEASE SEE SPACES 105, 105A, 103A, 103, 104. AS |
| | MENTIONS ON PREVIOUS REVIEW THESE ARE SOME EXAMPLES |
| | ONLY. |
| | |
| | B) PLEASE SEE 13-415.1.ABC.1.3 FOR SEPARATE CONTROLS |
| | REQUIRED FOR DISPLAY/ ACCENT LIGHTING. NO AUTOMATED |
| | CONTROLS COULD BE LOCATED FOR THESE SPECIALTY LIGHTS. |
| | |
| | C) PLEASE SEE 13-415.1.ABC.1.4. WHERE ARE THE LIGHTING |
| | CONTROLS LOCATED FOR ALL OUTSIDE LIGHTS MEETING THIS |
| | SECTION? |
| | PLEASE SEE TWO METHODS AS NOTED PREVIOUSLY. IF A TIME |
| | CLOCK IS CHOSEN. IT MUST BE ASTRONOMICAL AND MUST HAVE |
| | A MINIMUM OF 10HR BATTERY BACK UP FOR PROGRAMMING. |
| | |
| | D) PLEASE SEE SOME OTHER AREAS IN WHICH STANDARD |
| | SWITCHES ARE BEING SHOWN. FOR EXAMPLE: PLEASE SEE |
| | STAIRS TO EDC ROOM #2. PLEASE KNOW ANY AUTOMATED |
| | CONTROLS WHICH ARE REQUIRED AND ARE LOCATED IN EGRESS |
| | PATHS SHALL BE FAIL SAFE *ON*> |
| | PLEASE SEE FBC 1016.1, AND NFPA-101 LIFE SAFETY CODE |
| | 7.8.1.2.2. |
| | |
| | E) PLEASE SEE SYMBOL LEGEND WAS NOT UPDATED FOR DEVICES |
| | ON PLANS. |
| | |
| | F) PLEASE SEE THE LIGHTING CONTROLS IN MANY AREAS WHICH |
| | ARE REQUIRED TO BE AUTOMATED OF SOME KIND ARE SHOWING |
| | UP AS *MANUAL ON/OFF * ON THE INPUT DATA REPORT OF THE |
| | SUBMITTED ENERGY CALCULATIONS. |
| | PLEASE BE SURE TO THE FOLLOWING COMMENTS. |
| | |
| | ** AS NOTED ON PREVIOUS REVIEW SOME OF THE ABOVE |
| | EXAMPLES ARE GIVEN AS A BENEFIT AND MAY NOT BE IN |
| | ANYWAY ALL POSSIBLE LOCATIONS. |
| | |
| | 7) NOTE: PLEASE BE SURE THE SUBMITTED ENERGY |
| | CALCULATIONS COORDINATE WITH THE PLANS. THE INPUT DATA |
| | REPORT WILL BE NOTED AS IDR FOR THE REMAINDER OF THIS |
| | COMMENT. |
| | |
| | FOR EXAMPLE: |
| | PLEASE EXPLAIN HOW THE IDR SHOWS *MANUAL ON/OFF* FOR |
| | LIGHTING WHICH IS REQUIRED TO BE SOME SORT OF AUTOMATED |
| | SYSTEM OR DEVICE. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE SPACE FILLED OUT ON THE CERTIFICATION |
| | SHEET STATES THE PERSON WHO PREPARED THE DOCUMENT AS |
| | THE FIRM. THE SHEET CALLS FOR THE INDIVIDUAL TO CERTIFY |
| | THE SUBMITTED CALCULATIONS HOWEVER THE PRINTED NAME AND |
| | SIGNATURE IS NOT LOCATED ON THE SUBMITTED ENERGY |
| | CALCULATIONS. THESE WERE NOT SIGNED, DATED OR SEALED AS |
| | REQUIRED. |
| | PLEASE SEE FBC 13-103.1 AS THESE SHALL BE DONE BY THE |
| | ENGINEER WHO PREPARED CALCULATIONS. |
| | PLEASE BE SURE TO ALSO SEE FAC 61G15-23.002, FS 471.025 |
| | AS THIS REQUIRES ALL DOCUMENTS PREPARED BY AN ENGINEER |
| | TO BE SIGNED, DATED AND SEALED ACCORDINGLY. |
| | ** THIS IS REQUIRED FOR ALL TRADES WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEW TRADES. |
| | |
| | FOR EXAMPLE: |
| | PLEASE COORDINATE THE NUMBER AND KW RATINGS OF ALL |
| | ELECTRIC WATER HEATERS ON PLANS/PANEL SCHEDULES WITH |
| | THAT OF THE SHOWN ON THE IDR. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THERE ARE SEVERAL ITEMS ON EXTERIOR LIGHTING |
| | WHICH IS SHOWN ON PLANS WHICH DO NOT SHOW UP ON THE IDR |
| | AND OTHER WHERE THE NUMBER AND WATTAGE OF FIXTURES DO |
| | NOT CORRELATE. |
| | PLEASE SEE MISSING FIXTURES X-3, X-5, X-6, H1, H1A |
| | ETC. |
| | PLEASE SEE THERE ARE MANY ITEMS ON ELECTRICAL PLANS |
| | WHICH ARE NOT IN THE IDR. |
| | PLEASE ALSO SEE THE FOLLOWING COMMENT WITH RESPECT TO |
| | THE SITE LIGHTING PLANS AND COORDINATION NEEDED. |
| | |
| | FOR EXAMPLE: |
| | PLEASE GO OVER ALL INTERIOR LIGHTING. MOST ARE IN GOOD |
| | SHAPE HOWEVER AS THE FIXTURE LEGEND IS NOT COMPLETE |
| | WITH SOME LIGHTING FOR SPECIALTY LIGHTS AND FIXTURES |
| | SUCH AS S-1, MANY COULD NOT BE VERIFIED. |
| | |
| | ** THESE ARE A FEW EXAMPLES ONLY AND MAY IN NO WAY BE |
| | AN EXHAUSTED LIST. THESE EXAMPLES WERE GIVEN AS A |
| | BENEFIT TO CLEARLY COORDINATE **ALL ** LIGHTING ON |
| | PLANS WITH THE IDR. |
| | |
| | 8) NOTE: PLEASE BE SURE TO COORDINATE THE ELECTRICAL |
| | SITE LIGHTING PLANS WITH THE SL PLANS WHICH ARE IN THE |
| | CIVIL SETS. AS THE LIGHTING IS A REQUIRED DESIGN |
| | PARAMETER UNDER FLORIDA ADMINISTRATIVE CODE |
| | 61G15-33.004 FOR THE ENGINEER THESE ARE REQUIRED TO BE |
| | COMPLETED AT THIS TIME. |
| | PLEASE SEE THE NUMBER OF FIXTURES AND LOCATIONS COULD |
| | NOT BE CONFIRMED AS THE SITE SHEETS WERE NOT THE SAME. |
| | PLEASE SEE THE SL PLANS AS THESE CONTAIN FIXTURES AND |
| | OTHER LOCATIONS WHICH WERE NOT CLEARLY VISIBLE OR |
| | READABLE. PLEASE SEE THE FOLLOWING COMMENT FOR MINIMUM |
| | SCALE AND DETAILS NEEDED. |
| | PLEASE SEE THE OUTSIDE LIGHTS ON THE ELECTRICAL PLANS |
| | FOR WALL PACKS, POLES ETC NEED TO COORDINATE. PLEASE |
| | SEE COMMENTS WITH RESPECT TO LIGHTING FOR LIFE SAFETY |
| | CODE AS WELL. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 9) NOTE: PLEASE SUBMIT PLANS WITH A MINIMUM OF 1/8 INCH |
| | SCALE. THE 1/16 TH INCH SCALE IS OK AS LONG AS THERE |
| | ARE OTHER SHEETS WHICH PROVIDE THE LARGER DETAIL. THIS |
| | IS CLEARLY AN ISSUE AS THE COMMENT #8 ABOVE FINDS |
| | INCONSISTENCIES IN PLANS WHICH ARE NOT EASILY READ. |
| | PLEASE SEE SHEETS E110 AND E11 AS SOME OF THESE SMALLER |
| | AREAS ARE NOT SHOWN ON ANY OTHER LOCATION ON PLANS. |
| | MOST CAN BE READ ON THESE TWO SHEETS BUT NOT ALL AND |
| | THE MINIMUM IS REQUIRED. FBC 106.1.3 ADMIN SECTION. |
| | |
| | 10) NOTE: THE PLANS AND RESPONSE LETTERS MENTIONS THIS |
| | BUILDING WILL NOT BE OCCUPIED IN EMERGENCY. THIS SHOULD |
| | BE STATED THIS WILL BE UN-OCCUPIED UNDER EMERGENCY |
| | POWER. THIS BUILDING WILL BE REQUIRED TO EVACUATE IN |
| | THE ONE AND HALF HOUR TIME FRAME. PLEASE OBTAIN A |
| | LETTER FROM CORPORATE WHICH STATES AN UNDERSTANDING |
| | THAT THIS STORE SHALL REMAIN CLOSED IN THE EVENT OF A |
| | POWER FAILURE. ( OR WORDS TO THAT AFFECT). |
| | A NOTICE AND HOLD WILL BE PLACED ON LAND FILE AND |
| | LETTER WILL REMAIN PERMANENTLY ON FILE FOR THIS |
| | LOCATION. |
| | |
| | 11) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL |
| | EGRESS PATHS UNDER NORMAL AND EMERGENCY CONDITIONS. |
| | SOME WERE SUBMITTED FOR SOME AREAS HOWEVER THERE ARE |
| | OTHER AREAS SUCH AS THE REAR STAIRS WHICH DO NOT SHOW |
| | *ANY* LIGHTING LEVELS FOR EITHER NORMAL OR EMERGENCY. |
| | PLEASE SEE THE SUBMITTED SHEETS LLE AND ULE CLEARLY |
| | STATE THE SHEETS ARE NOT TO BE USED FOR CONSTRUCTION |
| | AND ARE NOT SIGNED, DATED OR SEALED BY THE RESPONSIBLE |
| | DESIGNER OF RECORD. THESE SHEETS ALSO CONTAIN A NOTE |
| | WHICH MENTIONS THESE LEVELS ARE THE LEVELS UNDER |
| | BATTERY. HOW IS THIS POSSIBLE WHEN DOZENS OF THESE |
| | FIXTURES CONTAIN NO BATTERY BACK UP AT ALL? |
| | PLEASE SEE THE RESPONSE ALSO MENTIONS THE NORMAL LEVELS |
| | OF LIGHTING ARE NOT PROVIDED BECAUSE THE INTERPRETATION |
| | IS THAT THE DESIGN MEETS CODE. THIS IS NOT ACCEPTABLE |
| | IN LIEU OF SUBMITTING, SHOWING AND TAKING |
| | RESPONSIBILITY OF THE *MINIMUM* LIGHTING LEVELS AS |
| | REQUIRED UNDER THE LIFE SAFETY CODE. |
| | IT IS THE RESPONSIBILITY OF THE DESIGN PROFESSIONAL TO |
| | ACHIEVE MINIMUM LEVELS AND SHOW ON PLANS FOR DESIGN. |
| | PLEASE SEE FAC 61G15-33.004. |
| | ** |
| | PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR *ALL* EGRESS |
| | AREAS UNDER BOTH NORMAL AND EMERGENCY CONDITIONS. THE |
| | AREAS SUCH AS STAIRS SHALL SHOW LIGHTING LEVELS OF 10FT |
| | CANDLES AT *ALL * WALKING SURFACES ON STAIRS. |
| | THESE LEVELS ARE PERMITTED DOWN TO 1FT CANDLE UNDER |
| | EMERGENCY. PLEASE SEE PREVIOUS COMMENTS AS ALL STAIRS |
| | ARE REQUIRED TO CONTAIN BATTERY BACK UP FIXTURES FOR |
| | THE MINIMUM OF 1FT CANDLE. |
| | ** THIS IS ALSO TO INCLUDE THE REAR STAIRS WHICH |
| | CURRENTLY DO NOT SHOW ANY LEVELS AND FOR ALL OTHER |
| | STAIRS WHICH ONLY SHOW UNDER EMERGENCY. |
| | WHAT ABOUT STAIRS FROM EDC ROOM? NO LEVELS UNDER EITHER |
| | CONDITION? |
| | PLEASE BE SURE TO INDICATE THE *BATTERY BACK UP* OR |
| | *EMERGENCY BALLAST* ON FIXTURE LEGEND FOR FIXTURES AS |
| | REQUIRED. |
| | NFPA-101 2003 7.8, 7.9. 7.8.1.3, 7.9.2.2. |
| | ** PREVIOUS REVIEW** |
| | |
| | 12) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO |
| | NOTES REQUIRED TO BE ADDED TO PLANS PER |
| | 13-413.A.ABC.2.1 AND .2.2. THE RESPONSE MENTIONS NOTES |
| | ADDED TO E000 WHICH WERE LOCATED ON PLANS HOWEVER THE |
| | WORDING AS SHOWN IN THE FLORIDA BUILDING CODE WAS NOT |
| | ON PLANS. THIS WAS CONFIRMED WITH DCA (DEPARTMENT OF |
| | COMMUNITY AFFAIRS) PREVIOUSLY THAT THE WORDING LOCATED |
| | IN THE CODE IS THE WORDING WHICH IS TO BE LOCATED ON |
| | PLANS. |
| | PLEASE ADJUST. |
| | |
| | 13) NOTE: PLEASE SEE THE SIZE OF THE FEEDERS FROM THE |
| | SERVICE EQUIPMENT MAIN TO THE MAIN DISTRIBUTION |
| | SWITCHBOARD DO NOT MEET THE MINIMUM SIZE PER 310.16, |
| | 240.4B. PLEASE SEE THE CONDUCTOR SHALL BE AT OR ABOVE |
| | THE OVER CURRENT PROTECTION WHICH IS PROTECTING THE |
| | CONDUCTORS. |
| | (MAY NOT USE THE 90 DEGREE COLUMN UNLESS ALL EQUIPMENT, |
| | LUGS ETC MEET 90 DEGREE TEMP RATINGS) |
| | PLEASE SEE 110.14. |
| | NEW COMMENT> |
| | |
| | 14) NOTE: PLEASE SEE 250.24, 250.6 AS THE GROUNDING |
| | ELECTRODE SYSTEM SHALL BE ATTACHED TO THE FIRST MEANS |
| | OF DISCONNECT WHICH IS THE SERVICE EQUIPMENT MAIN |
| | LOCATED OUTSIDE. |
| | PLEASE ADJUST RISER GROUNDING ELECTRODE SYSTEM AND |
| | DETAIL. |
| | PLEASE BE SURE TO SEE NOTE ABOVE WITH RESPECT TO THE |
| | GENERATOR AND SEPARATELY DERIVED SYSTEMS. |
| | NEW COMMENT> |
| | |
| | 15) NOTE: PLEASE SEE 250.24, 250.110, 250.122 ETC AS |
| | THE EQUIPMENT GROUNDING CONDUCTOR IS MISSING ON THE |
| | CONDUIT FROM THE MAIN TO THE MAIN SWITCHBOARD. (MDS). |
| | PLEASE SEE FEEDER SCHEDULE 18A. |
| | NEW COMMENT> |
| | |
| | 16) NOTE: PLEASE SEE THE NEW DISCONNECTS WHICH WERE |
| | ADDED FROM PREVIOUS REVIEW NOTES WITH RESPECT TO THE |
| | DISCONNECTING MEANS REQUIRED PER 225.31-225.39, |
| | 700.12B6, 702.11 ARE NOT RATED FOR THE CIRCUIT IN WHICH |
| | THEY ARE A PART OF. PLEASE SEE THE BREAKER AND OVER |
| | CURRENT PROTECTION ON THE GENERATOR IS HIGHER THAN THE |
| | RATING OF THESE NEW DISCONNECTS.THE RISER SHOWS BOTH |
| | AS 60A RATED WHEN THESE ARE WITHIN 100AMP CIRCUITS TO |
| | EMERGENCY LOADS. |
| | PLEASE SEE THAT ALL EQUIPMENT SHALL BE LISTED AND RATED |
| | FOR THE LOAD SERVED.225.39, 110.3, 90.7. |
| | |
| | 17) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH |
| | RESPECT TO THE ELEVATOR PIT LIGHTING LEVELS TO MEET |
| | 620.23, ASTMA17.1-2004 YET NO LEVELS WERE SHOWN. THE |
| | RESPONSE MENTIONS THE FIXTURE WAS CHANGED ON LEGEND. |
| | HOW DOES THIS ADDRESS THE COMMENT? |
| | WHERE ARE THE LIGHTING LEVELS SHOWN? |
| | |
| | 18) NOTE: PLEASE SEE THE PREVIOUS REVIEW COMMENT WITH |
| | RESPECT TO THE HANDLE PROPOSED *LOCK OFF DEVICE*. THE |
| | SUBMITTED MANUFACTURES SPEC/CUT SHEET IS NOT AN |
| | ACCEPTABLE DEVICE IN LIEUOF THE DISCONNECT REQUIRED |
| | AND DOES NOT MEET THE PERMANENT MEANS. |
| | THIS ARE NOT LISTED FOR PERMANENT INSTALLATIONS!! |
| | 110.3. |
| | ** PLEASE KNOW THE NEW NEC 2008 WILL CLARIFY THE CODE |
| | AND THE INTENT.THIS WILL CLEARLY STATE THAT IT WAS |
| | NEVER THE INTENT TO ALLOW *HANDLE LOCK OFF DEVICES* IN |
| | LIEU OF THE REQUIRED DISCONNECTING MEANS. |
| | IN ANY CASE MOST *LOCK OFF*, *LOCK OUT/TAG OUT* DEVICES |
| | ARE FOR TEMPORARY INSTALLATIONS ONLY. MOST ARE NOT |
| | LISTED FOR PERMANENT MEANS. |
| | ** PLEASE ADJUST PLANS ACCORDINGLY FOR DISCONNECTS |
| | ETC. |
| | 110.3, 90.7 |
| | FBC |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| 2008-06-20 17:09:41 | 1ROLL AND BOOKS IN ELEC FOR REVIEW. |
| | REVIEW TO COMMENCE ON 6/23 |