Plan Review Notes
Plan Review Notes For Permit 08020128
Permit Number 08020128
Review Stop E
Sequence Number 2
Notes
Date Text
2008-06-23 17:08:31** DENIED2ND PLAN REVIEW**
  
 ** PLAN REVIEW ONLY.
  
 ** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING. SOME OF THESE
 ARE THE SAME NOTES, COMMENTS AND/OR CODE SECTIONS.
  
 ** PLEASE SEE THERE ARE SOME NEW COMMENTS DUE TO ITEMS
 BEING CHANGED OR PLACED ON THE PLANS FOR THE FIRST
 TIME.
  
 ** PLEASE SEE THERE ARE ALSO NEW COMMENTS.
  
 ** AS STATED ON PREVIOUS REVIEW THERE WERE SOME ITEMS
 NOT YET SUBMITTED IN WHICH A REVIEW OF THOSE ITEMS
 COULD NOT BE DONE.
  
  
  
 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR * PLAN
 REVIEW ONLY * FOR A SECOND REVIEW AND HAVE NOT BEEN
 SUBMITTED UNDER PERMIT APPLICATION.
 PLEASE KNOW THAT ONCE ALL ITEMS FOR CODE REVIEWS ARE
 DONE PLANS WILL STILL REMAIN IN FAILED STATS UNTIL
 PERMIT APPLICATION HAS BEEN MADE. VERIFICATION OF
 SEVERAL ITEMS SUCH AS VALID LICENSING ETC IS DONE AT
 TIME OF APPLICATION BEFORE ISSUANCE OF PERMIT(S). THIS
 COMMENT WILL REPEAT AS PERMIT APPLICATION HAS NOT BEEN
 MADE.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CONTACT THIS
 OFFICE/REVIEWER.
  
 2) NOTE: PLEASE SEE NOTICE AT THE END OF THIS REVIEW
 WHICH IS NOTED AS ** IMPORTANT** ON CORRECT PROCEDURE
 ON RE-SUBMITTING PLANS AND THE REMOVING OF OLD/VOIDED
 SHEETS. IF THERE QUESTIONS PLEASE CONTACT THIS
 REVIEWER.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO EPS
 LEVEL-1 EQUIPMENT WHICH IS NOT PERMITTED TO BE LOCATED
 IN THE SAME ELECTRICAL ROOM AS THE NORMAL ELECTRICAL
 EQUIPMENT. THE RESPONSE MENTIONS TO SEE NEW REVISED
 E355 HOWEVER THE PLANS NOW ONLY SHOW SORT OF DOORS AND
 DASHED LINES. THIS DOES NOT PROVIDE ANY RATINGS OF
 WALLS. THIS DOES NOT PROVIDE ANY LISTED ASSEMBLIES FOR
 WALL. THIS DOES NOT PROVIDE ANY INFORMATION ON DOORS TO
 BE USED. NO WALLS OR DOORS WERE LOCATED ON OTHER TRADE
 PLANS SUCH AS ARCHITECTURAL OR MECHANICAL SHEETS.
 PLEASE SEE THE FOLLOWING TEXT REMAINS FROM PREVIOUS
 REVIEW WITH RESPECT TO NFPA-110 CHAPTER 7.
 PLEASE SEE NFPA-110 7.2, 7.1.3 PLEASE SEE 7.2.2.1 BELOW
 ALSO.
 7.2.1THE EPS SHALL BE INSTALLED IN A SEPARATE ROOM FOR
 LEVEL 1 INSTALLATIONS. EPSS EQUIPMENT SHALL BE
 PERMITTED TO BE INSTALLED IN THIS ROOM.
 7.2.1.1THE ROOM SHALL HAVE A MINIMUM 2-HOUR FIRE RATING
 OR BE LOCATED IN AN ADEQUATE ENCLOSURE LOCATED OUTSIDE
 THE BUILDING CAPABLE OF RESISTING THE ENTRANCE OF SNOW
 OR RAIN AT A MAXIMUM WIND VELOCITY REQUIRED BY LOCAL
 BUILDING CODES.
 7.2.1.2NO OTHER EQUIPMENT, INCLUDING ARCHITECTURAL
 APPURTENANCES, EXCEPT THOSE THAT SERVE THIS SPACE,
 SHALL BE PERMITTED IN THIS ROOM.
 7.2.2EPSS EQUIPMENT SHALL NOT BE INSTALLED IN THE SAME
 ROOM WHERE THE NORMAL ELECTRICAL SERVICE EQUIPMENT IS
 INSTALLED.
 7.2.2.1TRANSFER SWITCHES SHALL BE PERMITTED TO BE
 INSTALLED IN THE NORMAL ELECTRICAL SERVICE ROOM WHERE
 TWICE THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF
 NFPA 70, NATIONAL ELECTRICAL CODE, EXISTS BETWEEN
 EQUIPMENT ENCLOSURES.
  
 4) NOTE: PLEASE PROVIDE INFORMATION ON LOAD SHEDDING
 FOR OTHER SYSTEMS ON EPS LEVEL-1 GENERATOR PER NFPA-110
 7.1.5. WHAT PROVIDES SHEDDING OF NON-EMERGENCY OR ANY
 LEGALLY REQUIRED LOADS?
  
 5) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO
 FOUR POLE TRANSFER SWITCHES. THESE ARE NOW SHOWN ON
 RISER AS FOUR POLE YET WHERE IS THE SEPARATELY DERIVED
 GENERATOR GROUNDING PER 250.20, 250.50?
  
 6) NOTE: PLEASE SEE THE FOLLOWING COMMENTS WITH RESPECT
 TO LIGHTING CONTROLS FOR FLORIDA BUILDING CODE CHAPTER
 13 REQUIREMENTS.
 PLEASE SEE THERE ARE SEVERAL LOCATIONS IN WHICH
 REQUIRED LIGHTING CONTROLS ARE NOT.
 PLEASE SEE 13-415.1.ABC.1, .1.1, .1.2 , .1.3 AND .1.4.
  
 A) ALL SEPARATE SPACES CONTAINING FLOOR TO CEILING
 HEIGHT PARTITIONS ARE REQUIRED TO CONTAIN ONE OR MORE
 OF THE FOLLOWING FOR SEPARATE SPACE CONTROL. INDIVIDUAL
 OCCUPANCY SENSORS OR AN OVER RIDE DEVICE OF SOME SORT
 TO OVER RIDE ANY TIME OF DAY SCHEDULING.
 PLEASE SEE ROOMS 121,122. RESPONSE MENTIONS TO SEE
 REVISED E-131 HOWEVER IT IS UNCLEAR WHAT WAS REVISED.
 PLEASE SEE SPACES 105, 105A, 103A, 103, 104. AS
 MENTIONS ON PREVIOUS REVIEW THESE ARE SOME EXAMPLES
 ONLY.
  
 B) PLEASE SEE 13-415.1.ABC.1.3 FOR SEPARATE CONTROLS
 REQUIRED FOR DISPLAY/ ACCENT LIGHTING. NO AUTOMATED
 CONTROLS COULD BE LOCATED FOR THESE SPECIALTY LIGHTS.
  
 C) PLEASE SEE 13-415.1.ABC.1.4. WHERE ARE THE LIGHTING
 CONTROLS LOCATED FOR ALL OUTSIDE LIGHTS MEETING THIS
 SECTION?
 PLEASE SEE TWO METHODS AS NOTED PREVIOUSLY. IF A TIME
 CLOCK IS CHOSEN. IT MUST BE ASTRONOMICAL AND MUST HAVE
 A MINIMUM OF 10HR BATTERY BACK UP FOR PROGRAMMING.
  
 D) PLEASE SEE SOME OTHER AREAS IN WHICH STANDARD
 SWITCHES ARE BEING SHOWN. FOR EXAMPLE: PLEASE SEE
 STAIRS TO EDC ROOM #2. PLEASE KNOW ANY AUTOMATED
 CONTROLS WHICH ARE REQUIRED AND ARE LOCATED IN EGRESS
 PATHS SHALL BE FAIL SAFE *ON*>
 PLEASE SEE FBC 1016.1, AND NFPA-101 LIFE SAFETY CODE
 7.8.1.2.2.
  
 E) PLEASE SEE SYMBOL LEGEND WAS NOT UPDATED FOR DEVICES
 ON PLANS.
  
 F) PLEASE SEE THE LIGHTING CONTROLS IN MANY AREAS WHICH
 ARE REQUIRED TO BE AUTOMATED OF SOME KIND ARE SHOWING
 UP AS *MANUAL ON/OFF * ON THE INPUT DATA REPORT OF THE
 SUBMITTED ENERGY CALCULATIONS.
 PLEASE BE SURE TO THE FOLLOWING COMMENTS.
  
 ** AS NOTED ON PREVIOUS REVIEW SOME OF THE ABOVE
 EXAMPLES ARE GIVEN AS A BENEFIT AND MAY NOT BE IN
 ANYWAY ALL POSSIBLE LOCATIONS.
  
 7) NOTE: PLEASE BE SURE THE SUBMITTED ENERGY
 CALCULATIONS COORDINATE WITH THE PLANS. THE INPUT DATA
 REPORT WILL BE NOTED AS IDR FOR THE REMAINDER OF THIS
 COMMENT.
  
 FOR EXAMPLE:
 PLEASE EXPLAIN HOW THE IDR SHOWS *MANUAL ON/OFF* FOR
 LIGHTING WHICH IS REQUIRED TO BE SOME SORT OF AUTOMATED
 SYSTEM OR DEVICE.
  
 FOR EXAMPLE:
 PLEASE SEE THE SPACE FILLED OUT ON THE CERTIFICATION
 SHEET STATES THE PERSON WHO PREPARED THE DOCUMENT AS
 THE FIRM. THE SHEET CALLS FOR THE INDIVIDUAL TO CERTIFY
 THE SUBMITTED CALCULATIONS HOWEVER THE PRINTED NAME AND
 SIGNATURE IS NOT LOCATED ON THE SUBMITTED ENERGY
 CALCULATIONS. THESE WERE NOT SIGNED, DATED OR SEALED AS
 REQUIRED.
 PLEASE SEE FBC 13-103.1 AS THESE SHALL BE DONE BY THE
 ENGINEER WHO PREPARED CALCULATIONS.
 PLEASE BE SURE TO ALSO SEE FAC 61G15-23.002, FS 471.025
 AS THIS REQUIRES ALL DOCUMENTS PREPARED BY AN ENGINEER
 TO BE SIGNED, DATED AND SEALED ACCORDINGLY.
 ** THIS IS REQUIRED FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEW TRADES.
  
 FOR EXAMPLE:
 PLEASE COORDINATE THE NUMBER AND KW RATINGS OF ALL
 ELECTRIC WATER HEATERS ON PLANS/PANEL SCHEDULES WITH
 THAT OF THE SHOWN ON THE IDR.
  
 FOR EXAMPLE:
 PLEASE SEE THERE ARE SEVERAL ITEMS ON EXTERIOR LIGHTING
 WHICH IS SHOWN ON PLANS WHICH DO NOT SHOW UP ON THE IDR
 AND OTHER WHERE THE NUMBER AND WATTAGE OF FIXTURES DO
 NOT CORRELATE.
 PLEASE SEE MISSING FIXTURES X-3, X-5, X-6, H1, H1A
 ETC.
 PLEASE SEE THERE ARE MANY ITEMS ON ELECTRICAL PLANS
 WHICH ARE NOT IN THE IDR.
 PLEASE ALSO SEE THE FOLLOWING COMMENT WITH RESPECT TO
 THE SITE LIGHTING PLANS AND COORDINATION NEEDED.
  
 FOR EXAMPLE:
 PLEASE GO OVER ALL INTERIOR LIGHTING. MOST ARE IN GOOD
 SHAPE HOWEVER AS THE FIXTURE LEGEND IS NOT COMPLETE
 WITH SOME LIGHTING FOR SPECIALTY LIGHTS AND FIXTURES
 SUCH AS S-1, MANY COULD NOT BE VERIFIED.
  
 ** THESE ARE A FEW EXAMPLES ONLY AND MAY IN NO WAY BE
 AN EXHAUSTED LIST. THESE EXAMPLES WERE GIVEN AS A
 BENEFIT TO CLEARLY COORDINATE **ALL ** LIGHTING ON
 PLANS WITH THE IDR.
  
 8) NOTE: PLEASE BE SURE TO COORDINATE THE ELECTRICAL
 SITE LIGHTING PLANS WITH THE SL PLANS WHICH ARE IN THE
 CIVIL SETS. AS THE LIGHTING IS A REQUIRED DESIGN
 PARAMETER UNDER FLORIDA ADMINISTRATIVE CODE
 61G15-33.004 FOR THE ENGINEER THESE ARE REQUIRED TO BE
 COMPLETED AT THIS TIME.
 PLEASE SEE THE NUMBER OF FIXTURES AND LOCATIONS COULD
 NOT BE CONFIRMED AS THE SITE SHEETS WERE NOT THE SAME.
 PLEASE SEE THE SL PLANS AS THESE CONTAIN FIXTURES AND
 OTHER LOCATIONS WHICH WERE NOT CLEARLY VISIBLE OR
 READABLE. PLEASE SEE THE FOLLOWING COMMENT FOR MINIMUM
 SCALE AND DETAILS NEEDED.
 PLEASE SEE THE OUTSIDE LIGHTS ON THE ELECTRICAL PLANS
 FOR WALL PACKS, POLES ETC NEED TO COORDINATE. PLEASE
 SEE COMMENTS WITH RESPECT TO LIGHTING FOR LIFE SAFETY
 CODE AS WELL.
 FBC 106.1.2 FOR COORDINATION.
  
 9) NOTE: PLEASE SUBMIT PLANS WITH A MINIMUM OF 1/8 INCH
 SCALE. THE 1/16 TH INCH SCALE IS OK AS LONG AS THERE
 ARE OTHER SHEETS WHICH PROVIDE THE LARGER DETAIL. THIS
 IS CLEARLY AN ISSUE AS THE COMMENT #8 ABOVE FINDS
 INCONSISTENCIES IN PLANS WHICH ARE NOT EASILY READ.
 PLEASE SEE SHEETS E110 AND E11 AS SOME OF THESE SMALLER
 AREAS ARE NOT SHOWN ON ANY OTHER LOCATION ON PLANS.
 MOST CAN BE READ ON THESE TWO SHEETS BUT NOT ALL AND
 THE MINIMUM IS REQUIRED. FBC 106.1.3 ADMIN SECTION.
  
 10) NOTE: THE PLANS AND RESPONSE LETTERS MENTIONS THIS
 BUILDING WILL NOT BE OCCUPIED IN EMERGENCY. THIS SHOULD
 BE STATED THIS WILL BE UN-OCCUPIED UNDER EMERGENCY
 POWER. THIS BUILDING WILL BE REQUIRED TO EVACUATE IN
 THE ONE AND HALF HOUR TIME FRAME. PLEASE OBTAIN A
 LETTER FROM CORPORATE WHICH STATES AN UNDERSTANDING
 THAT THIS STORE SHALL REMAIN CLOSED IN THE EVENT OF A
 POWER FAILURE. ( OR WORDS TO THAT AFFECT).
 A NOTICE AND HOLD WILL BE PLACED ON LAND FILE AND
 LETTER WILL REMAIN PERMANENTLY ON FILE FOR THIS
 LOCATION.
  
 11) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 EGRESS PATHS UNDER NORMAL AND EMERGENCY CONDITIONS.
 SOME WERE SUBMITTED FOR SOME AREAS HOWEVER THERE ARE
 OTHER AREAS SUCH AS THE REAR STAIRS WHICH DO NOT SHOW
 *ANY* LIGHTING LEVELS FOR EITHER NORMAL OR EMERGENCY.
 PLEASE SEE THE SUBMITTED SHEETS LLE AND ULE CLEARLY
 STATE THE SHEETS ARE NOT TO BE USED FOR CONSTRUCTION
 AND ARE NOT SIGNED, DATED OR SEALED BY THE RESPONSIBLE
 DESIGNER OF RECORD. THESE SHEETS ALSO CONTAIN A NOTE
 WHICH MENTIONS THESE LEVELS ARE THE LEVELS UNDER
 BATTERY. HOW IS THIS POSSIBLE WHEN DOZENS OF THESE
 FIXTURES CONTAIN NO BATTERY BACK UP AT ALL?
 PLEASE SEE THE RESPONSE ALSO MENTIONS THE NORMAL LEVELS
 OF LIGHTING ARE NOT PROVIDED BECAUSE THE INTERPRETATION
 IS THAT THE DESIGN MEETS CODE. THIS IS NOT ACCEPTABLE
 IN LIEU OF SUBMITTING, SHOWING AND TAKING
 RESPONSIBILITY OF THE *MINIMUM* LIGHTING LEVELS AS
 REQUIRED UNDER THE LIFE SAFETY CODE.
 IT IS THE RESPONSIBILITY OF THE DESIGN PROFESSIONAL TO
 ACHIEVE MINIMUM LEVELS AND SHOW ON PLANS FOR DESIGN.
 PLEASE SEE FAC 61G15-33.004.
 **
 PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR *ALL* EGRESS
 AREAS UNDER BOTH NORMAL AND EMERGENCY CONDITIONS. THE
 AREAS SUCH AS STAIRS SHALL SHOW LIGHTING LEVELS OF 10FT
 CANDLES AT *ALL * WALKING SURFACES ON STAIRS.
 THESE LEVELS ARE PERMITTED DOWN TO 1FT CANDLE UNDER
 EMERGENCY. PLEASE SEE PREVIOUS COMMENTS AS ALL STAIRS
 ARE REQUIRED TO CONTAIN BATTERY BACK UP FIXTURES FOR
 THE MINIMUM OF 1FT CANDLE.
 ** THIS IS ALSO TO INCLUDE THE REAR STAIRS WHICH
 CURRENTLY DO NOT SHOW ANY LEVELS AND FOR ALL OTHER
 STAIRS WHICH ONLY SHOW UNDER EMERGENCY.
 WHAT ABOUT STAIRS FROM EDC ROOM? NO LEVELS UNDER EITHER
 CONDITION?
 PLEASE BE SURE TO INDICATE THE *BATTERY BACK UP* OR
 *EMERGENCY BALLAST* ON FIXTURE LEGEND FOR FIXTURES AS
 REQUIRED.
 NFPA-101 2003 7.8, 7.9. 7.8.1.3, 7.9.2.2.
 ** PREVIOUS REVIEW**
  
 12) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO
 NOTES REQUIRED TO BE ADDED TO PLANS PER
 13-413.A.ABC.2.1 AND .2.2. THE RESPONSE MENTIONS NOTES
 ADDED TO E000 WHICH WERE LOCATED ON PLANS HOWEVER THE
 WORDING AS SHOWN IN THE FLORIDA BUILDING CODE WAS NOT
 ON PLANS. THIS WAS CONFIRMED WITH DCA (DEPARTMENT OF
 COMMUNITY AFFAIRS) PREVIOUSLY THAT THE WORDING LOCATED
 IN THE CODE IS THE WORDING WHICH IS TO BE LOCATED ON
 PLANS.
 PLEASE ADJUST.
  
 13) NOTE: PLEASE SEE THE SIZE OF THE FEEDERS FROM THE
 SERVICE EQUIPMENT MAIN TO THE MAIN DISTRIBUTION
 SWITCHBOARD DO NOT MEET THE MINIMUM SIZE PER 310.16,
 240.4B. PLEASE SEE THE CONDUCTOR SHALL BE AT OR ABOVE
 THE OVER CURRENT PROTECTION WHICH IS PROTECTING THE
 CONDUCTORS.
 (MAY NOT USE THE 90 DEGREE COLUMN UNLESS ALL EQUIPMENT,
 LUGS ETC MEET 90 DEGREE TEMP RATINGS)
 PLEASE SEE 110.14.
 NEW COMMENT>
  
 14) NOTE: PLEASE SEE 250.24, 250.6 AS THE GROUNDING
 ELECTRODE SYSTEM SHALL BE ATTACHED TO THE FIRST MEANS
 OF DISCONNECT WHICH IS THE SERVICE EQUIPMENT MAIN
 LOCATED OUTSIDE.
 PLEASE ADJUST RISER GROUNDING ELECTRODE SYSTEM AND
 DETAIL.
 PLEASE BE SURE TO SEE NOTE ABOVE WITH RESPECT TO THE
 GENERATOR AND SEPARATELY DERIVED SYSTEMS.
 NEW COMMENT>
  
 15) NOTE: PLEASE SEE 250.24, 250.110, 250.122 ETC AS
 THE EQUIPMENT GROUNDING CONDUCTOR IS MISSING ON THE
 CONDUIT FROM THE MAIN TO THE MAIN SWITCHBOARD. (MDS).
 PLEASE SEE FEEDER SCHEDULE 18A.
 NEW COMMENT>
  
 16) NOTE: PLEASE SEE THE NEW DISCONNECTS WHICH WERE
 ADDED FROM PREVIOUS REVIEW NOTES WITH RESPECT TO THE
 DISCONNECTING MEANS REQUIRED PER 225.31-225.39,
 700.12B6, 702.11 ARE NOT RATED FOR THE CIRCUIT IN WHICH
 THEY ARE A PART OF. PLEASE SEE THE BREAKER AND OVER
 CURRENT PROTECTION ON THE GENERATOR IS HIGHER THAN THE
 RATING OF THESE NEW DISCONNECTS.THE RISER SHOWS BOTH
 AS 60A RATED WHEN THESE ARE WITHIN 100AMP CIRCUITS TO
 EMERGENCY LOADS.
 PLEASE SEE THAT ALL EQUIPMENT SHALL BE LISTED AND RATED
 FOR THE LOAD SERVED.225.39, 110.3, 90.7.
  
 17) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH
 RESPECT TO THE ELEVATOR PIT LIGHTING LEVELS TO MEET
 620.23, ASTMA17.1-2004 YET NO LEVELS WERE SHOWN. THE
 RESPONSE MENTIONS THE FIXTURE WAS CHANGED ON LEGEND.
 HOW DOES THIS ADDRESS THE COMMENT?
 WHERE ARE THE LIGHTING LEVELS SHOWN?
  
 18) NOTE: PLEASE SEE THE PREVIOUS REVIEW COMMENT WITH
 RESPECT TO THE HANDLE PROPOSED *LOCK OFF DEVICE*. THE
 SUBMITTED MANUFACTURES SPEC/CUT SHEET IS NOT AN
 ACCEPTABLE DEVICE IN LIEUOF THE DISCONNECT REQUIRED
 AND DOES NOT MEET THE PERMANENT MEANS.
 THIS ARE NOT LISTED FOR PERMANENT INSTALLATIONS!!
 110.3.
 ** PLEASE KNOW THE NEW NEC 2008 WILL CLARIFY THE CODE
 AND THE INTENT.THIS WILL CLEARLY STATE THAT IT WAS
 NEVER THE INTENT TO ALLOW *HANDLE LOCK OFF DEVICES* IN
 LIEU OF THE REQUIRED DISCONNECTING MEANS.
 IN ANY CASE MOST *LOCK OFF*, *LOCK OUT/TAG OUT* DEVICES
 ARE FOR TEMPORARY INSTALLATIONS ONLY. MOST ARE NOT
 LISTED FOR PERMANENT MEANS.
 ** PLEASE ADJUST PLANS ACCORDINGLY FOR DISCONNECTS
 ETC.
 110.3, 90.7
 FBC
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2008-06-20 17:09:411ROLL AND BOOKS IN ELEC FOR REVIEW.
 REVIEW TO COMMENCE ON 6/23