2008-06-24 15:00:55BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 2NDREVIEW 6-24-08
 ACTION: DENIED
  
 1A)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL, PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL, 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL, FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. PLEASE CORRECT
 SHEET G001 BUILDINGCODE INFORMATION.
 BUILDING ALLOWABLE FLOOR AREA- IS INDICATED AS
 UNLIMITED, NOTE S-2 PORTION OF THE BUILDING DOES HAVE
 AREA LIITATIONS TABLE 503.
  
 PLEASE NOTE THAT IF A PERMIT APPLICATION WILL NEED TO
 BE APPLIED FOR BEFORE DEC. 31, 2008 TO LOCK THIS
 PROJECT IN UNDER THE 2004 FBC. ON JAN.1, 2009 THE 2007
 FBC WILL GO INTO AFFECT.
  
 2) 2ND REQUEST, AT THIS TIME WE HAVE NOT SEEN ANY
 APPLICATION FOR A RESIDENT INSPECTOR. FBC* 109.3.7
 RESIDENT INSPECTOR. SUBMIT INSPECTOR RESUME' AND
 LICENSE DOCUMENTS TO KEN CONRAD , DIRECTOR OF THE
 RESIDENT INSPECTOR PROGRAM. 805-6711 OR 805-3749.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS
 PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING:
 XXX -BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE STRENGTH (F'C)
 IN EXCESS OF 3000 PSI
 - PILE DRIVING
 XXX - BUILDINGS OVER 20,000 SQ FT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 3) FBC* 109.3.7 SINCE A RESIDENT INSPECTOR WILL
 REQUIRED, THREE OF ALL DOCUMENTS (PLANS, REPORTS,
 SUBMITTALS AND PRODUCT APPROVALS) WILL BE REQUIRED FOR
 ISSUANCE OF THE PERMIT.
  
 4) NOTE THERE HAVE BEEN (2) SUBMITIONS OF SOILS REPORTS
 TO THIS OFFICE, MAY 29TH 3 SETS OF COPIED SIGNATURES OF
 THE ENGINNEER WERE SUBMITTED, THE SECOND SET DATED JUNE
 22, 2008 WERE SUBMITTED TO THIS OFFICE AGAIN
 PHOTO-COPIED SIGNATURES WITH A RAISED SEAL WERE
 SUBMITTED TO THIS OFFICE.
 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 SOILS REPORTS PLEASE SUBMIT THREE REPORTS WITH ORIGINAL
 SIGNATURES, NOT COPIES OR STAMPED SIGNATURES.1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6
 .
  
 ALLOF THE SUBMITTED SOILS REPORTS ARE GOING TO BE
 RETAINED FOR POSSIBLE REVIEW BY THE FLORIDA ENGINEERS'
 BOARD.
  
 5)BUILDING PROVISO:109.3.10* IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE APPLICABLE
 PROPERTY OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO
 THE APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE
 FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING
 STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 6) BUILDING PROVISO:109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00.IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8A)SEECOMMENT 1-E .
  
 8B-C) COMPLIED.
  
 9-10) COMPLIED.
  
 11) PLEASE REVIEWSHEET A021 EXIT ANALYSIS, SALES AREA
 PERSQ FT/ OCC. THIS IS THE 2ND FLOOR WHICH IS NOT
 CONSIDERED THE GRADE FLOOR. THE OCCUPANT LOAD FOR THIS
 FLOORS SALES AREA WOULD BE FIGURED AT60 FT / OCCUPANT
 NOT THE 30 AS INDICATED IN THE TABLE SEE TABLE
 1004.1.2.
  
 11A) COMPLIED.
  
 11B) SEMI-COMPLIED.AS DISCUSSED IN OUR MEETING WITH
 THE TARGET DESIGN TEAM WE CONCUR THAT STAIRA IS NOT
 PART OF THE REQUIRED EGRESS STAIRS BUT IF THIS IS TO BE
 THE CASE PLEASE SEE A021 THAT DOES HAVE TRAVEL
 DISTANCES MARKED WITH AN ARROW DIRECTLY DOWN THESE
 STAIRS. 707.2, EXCEPTION 2.
  
 11C-11K) COMPLIED.
  
 12A)PROVISO: PLEASE PROVIDE CUT SHEET OF ASTM E1966
 ASSEMBLY. NUMBER.A021 REFERS TO DETAIL#2 SHEETA331
 THIS SECTION OR DETAIL REFERENCES DETAIL 20 ON SHEET
 A231. IT APPEARS TO BE AN EXPANSION JOINT IN THE FLOOR
 BUT THERE IS NO INFORMATION THAT I CAN FIND ON THE
 FIREPROOFING REQUIREMENTS TABLE 601 FOR FLOOR SYSTEMS
 AND OCCUPANCY TYPE SEPARATION TABLE 302.3.2.PLEASE
 PROVIDE FLOOR CEILING TYPE PENETRATIONS FOR PIPES AND
 CONDUITS AS WELL AS FOR ANY HORIZONTAL PENETRATION OF
 RATED FLOOR/ CEILING ASSEMBLY.
 SEE 711.3.& 712.3.1.
  
 12B)COMPLIED.
  
 13) 2ND REQUEST, THE RESPONSE INDICATES COMPLIANCE ON
 CIVIL PLANS , PLEASE PROVIDE THE PLANS FOR REVIEW.
 SHEETA110 INDICATES THE DISABLED PARKING SPACES AND
 ACCESS AISLES BUT NOT THE ELEVATION CHANGES OF THE
 PARKING LOT VERSES DISABLED SPACES AND ACCESS AISLES.
 THE OTHER ISSUE IS NO INFORMATION FOR DETECTABLE
 WARNING AT HAZARDOUS VEHICULAR AREAS 11-4.29.5.
  
 14) SHEET A110 :
 A-C)COMPLIED.
 D) NEW COMMENT: THIS SHEET INDICATES MULTIPLE AREAS
 WHERE CURB CUTS ARE INDICATED, PLEASE COMPLY WITH
 11-4.7.5 FLARED SIDES.
 E) NEW COMMENT: GRID LINE 8 AT B/C THIS HANDICAPPED
 PARKING SPACE IS MISSING THE ACCESS AISLE11-4.6.3.
  
 15-19) COMPLIED.
  
 20)2ND REQUEST, SHEET A351 & A352 BOTH INDICATE AN
 ELECTRICAL DISTRIBUTION CENTER THAT DOES NOT HAVE A
 CODE COMPLIANT STAIR. THE CODE DOES ALLOW FOR FIXED
 LADDERS AS PART OF A MEANS OF EGRESS IN THE FOLLOWING
 LOCATIONS:FOR BOILERS (1014.3), REFRIGERATION ROOM
 (1014.4), STAGE EXITS 410.5.4, 1014.6.6.1 GALLERY,
 GRIDIRONS AND CATWALKS THAT ARE ASSOCIATED WITH STAGES
 AND HELISTOPS (1018.1.2.). PLEASE PROVIDE A CODE
 COMPLIANT STAIRWAY.THE PLANS WILL MEET THE EXCEPTION
 UNDER 1009.3 INDUSTRIAL EQUIPMENT ACCESS STAIRS. PLEASE
 PROVIDE THE WIDTH OF THE STAIRS, TREAD AND RISERS.
  
 21) 2ND REQUESTPLEASE PROVIDE ADDITIONAL INFORMATION
 ON THE ELECTRICAL DISTRIBUTION CENTER,
 PRE-MANUFACTURED? TYPE OF MATERIAL, FIRE RATINGS ETC?
 NFPA 13.8.14.10. THE STAIR WALL THAT LEADS TO THE EDC
 ARE INDICATED AS 2HR WALLS. THE WALLS DO NOT CONTINUE
 TO ENCLOSE THE STAIR LANDING WHICH WOULD BE WHAT
 SUROUNDS THE EDC. HOW DOES THIS MAKE A STAIRWELL
 ENCLOSURE WITH A 2 HR RATING?
 THE COMMENT# 24 WILL ILLUSTRATE THE 2 HR WALL RATING
 REQUIRED AROUND THE EMERGENCY EQUIREMENT ROOM ONLY.
  
 22-23) COMPLIED.
  
 24) SHEET A351,A361 & ELECTRICAL CUT SHEETS FROM
 MITSUBISHI ELECTRIC, THEMAIN ELECTRIC CENTER ROOM 129
 & 137, PLEASE PROVIDE ADDITIONAL INFORMATION ON THE
 ELECTRICAL DISTRIBUTION CENTER THAT IS INDICATED TO BE
 PRE-MANUFACTURED. TYPE OF MATERIAL, FIRE RATINGS ETC?
 NFPA 13.8.14.10. THE CUT SHEETS DO NOT PROVIDE HOW THE
 HOUR RATING IS ACHIEVED OR WHAT MATERIALS EITHER OF THE
 EDCS ARE
 CONSTRUCTED OF? PLEASE PROVIDE RATING OF THE DOORS FOR
 BOTH 129 AND 137. NOTE IN UNIT 137 THE EMERGENCY
 EQUIPMENT ROOM WILL ALSO REQUIRE A 2HR RATING FROM THE
 REST OF THE ENCLOSURE. THERE CAN BE
 NO REDUCTION FOR FIRE SPRINKLERS, PLEASE SEE NFPA 110
 7.2.1.1, ALSO SEE ELECTRICAL COMMENTS. PLEASE PROVIDE A
 COPY OF THE UL RATING U415 SYSTEM F/ 2006 UL DIRECTORY,
 WE DO NOT HAVE UP TO DATE
 UL LISTING BOOKS TO VERIFY DETAIL 5/ A351.
  
 25-27) COMPLIED.
  
 28) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 3COPIES IF THRESHOLD OR RESIDENT INSPECTOR OF
 PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
  
 28A) WINDOWS: CURTAIN-WALL - COMPLIED.
  
 28B) WINDOWS: STOREFRONT- 2ND REQUEST,
 THISNOA WAS ISSUED AND TESTEDBEFORE THE 2004 FBC
 WENT INTO EFFECT. BEFORE THIS DATE STEEL INCREASES OF 1
 1/3 WERE COMMON PLACE AND TAKEN WITH FASTENERS, AP.E.
 SHOULD REVIEW THE TEST REPORT INFORMATION TO SEE IF THE
 INCREASES WERE TAKEN.THE NEWER MIAMI-DADE NOAS THAT
 WERE RENEWED AFTER THE 2004 FBC WENT INTO EFFECT WILL
 STATE UNDER THE HEADING (3) CALCULATIONS, ANCHOR
 VERIFICATION VERIFIED TO THE 2004 FBC- NO STEEL
 INCREASES TAKEN. NOA 04-0308.02 ANCHOR CALCULATIONS
 THIS REVISION ON 04/13/04 BEFORE THE ISSUANCE OF THE
 2004 FBC.
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
 EXCEPTION: INCREASES IN ALLOWABLE STRESS SHALL BE
 PERMITTED IN ACCORDANCE WITH ACI 530/ASCE 5/TMS 402
 PROVIDED THE LOAD REDUCTION OF SECTION 1605.3.1.1 ITEM
 1 SHALL NOT BE APPLIED.
 3.SIMULTANEOUS USE OF BOTH ONE-THIRD INCREASE IN
 ALLOWABLE STRESS AND THE 25-PERCENT REDUCTION IN
 COMBINED LOADS SHALL NOT BE PERMITTED.
  
 28C1) AUTOMATIC BYPASS DOOR NOA03-0605.03
 THISNOA WAS ISSUED AND TESTEDBEFORE THE 2004 FBC
 WENT INTO EFFECT. BEFORE THIS DATE STEEL INCREASES OF 1
 1/3 WERE COMMON PLACE AND TAKEN WITH FASTENERS, AP.E.
 SHOULD REVIEW THE TEST REPORT INFORMATION TO SEE IF THE
 INCREASES WERE TAKEN.THE NEWER MIAMI-DADE NOAS THAT
 WERE RENEWED AFTER THE 2004 FBC WENT INTO EFFECT WILL
 STATE UNDER THE HEADING (3) CALCULATIONS, ANCHOR
 VERIFICATION VERIFIED TO THE 2004 FBC- NO STEEL
 INCREASES TAKEN. NOA 03-0605.03 ANCHOR CALCULATIONS
 THIS REVISION ON 10/31/03 BEFORE THE ISSUANCE OF THE
 2004 FBC.
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
 EXCEPTION: INCREASES IN ALLOWABLE STRESS SHALL BE
 PERMITTED IN ACCORDANCE WITH ACI 530/ASCE 5/TMS 402
 PROVIDED THE LOAD REDUCTION OF SECTION 1605.3.1.1 ITEM
 1 SHALL NOT BE APPLIED.
 3.SIMULTANEOUS USE OF BOTH ONE-THIRD INCREASE IN
 ALLOWABLE STRESS AND THE 25-PERCENT REDUCTION IN
 COMBINED LOADS SHALL NOT BE PERMITTED.
  
 28C2) AUTOMATIC SLIDING DOORS NOA 04-1026.02
 THISNOA WAS ISSUED AND TESTEDBEFORE THE 2004 FBC
 WENT INTO EFFECT. BEFORE THIS DATE STEEL INCREASES OF 1
 1/3 WERE COMMON PLACE AND TAKEN WITH FASTENERS, AP.E.
 SHOULD REVIEW THE TEST REPORT INFORMATION TO SEE IF THE
 INCREASES WERE TAKEN.THE NEWER MIAMI-DADE NOAS THAT
 WERE RENEWED AFTER THE 2004 FBC WENT INTO EFFECT WILL
 STATE UNDER THE HEADING (3) CALCULATIONS, ANCHOR
 VERIFICATION VERIFIED TO THE 2004 FBC- NO STEEL
 INCREASES TAKEN. NOA 04-1026.02ANCHOR CALCULATIONS
 THIS REVISION ON 10/11/04 BEFORE THE ISSUANCE OF THE
 2004 FBC.
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
 EXCEPTION: INCREASES IN ALLOWABLE STRESS SHALL BE
 PERMITTED IN ACCORDANCE WITH ACI 530/ASCE 5/TMS 402
 PROVIDED THE LOAD REDUCTION OF SECTION 1605.3.1.1 ITEM
 1 SHALL NOT BE APPLIED.
 3.SIMULTANEOUS USE OF BOTH ONE-THIRD INCREASE IN
 ALLOWABLE STRESS AND THE 25-PERCENT REDUCTION IN
 COMBINED LOADS SHALL NOT BE PERMITTED.
  
 28D) EXTERIOR GLAZED SWING DOORS NOA 04-0209.03 THIS
 NOA WAS ISSUED AND TESTEDBEFORE THE 2004 FBC WENT
 INTO EFFECT. BEFORE THIS DATE STEEL INCREASES OF 1 1/3
 WERE COMMON PLACE AND TAKEN WITH FASTENERS, AP.E.
 SHOULD REVIEW THE TEST REPORT INFORMATION TO SEE IF THE
 INCREASES WERE TAKEN.THE NEWER MIAMI-DADE NOAS THAT
 WERE RENEWED AFTER THE 2004 FBC WENT INTO EFFECT WILL
 STATE UNDER THE HEADING (3) CALCULATIONS, ANCHOR
 VERIFICATION VERIFIED TO THE 2004 FBC- NO STEEL
 INCREASES TAKEN. NOA 04-0209.03 ANCHOR CALCULATIONS
 THIS REVISION ON 04/13/04 BEFORE THE ISSUANCE OF THE
 2004 FBC.
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
 EXCEPTION: INCREASES IN ALLOWABLE STRESS SHALL BE
 PERMITTED IN ACCORDANCE WITH ACI 530/ASCE 5/TMS 402
 PROVIDED THE LOAD REDUCTION OF SECTION 1605.3.1.1 ITEM
 1 SHALL NOT BE APPLIED.
 3.SIMULTANEOUS USE OF BOTH ONE-THIRD INCREASE IN
 ALLOWABLE STRESS AND THE 25-PERCENT REDUCTION IN
 COMBINED LOADS SHALL NOT BE PERMITTED.
  
 28E1) EXTERIOR HOLLOW METAL DOORS SINGLE AND PAIRSNOA
 04-0203.03
 THISNOA WAS ISSUED AND TESTEDBEFORE THE 2004 FBC
 WENT INTO EFFECT. BEFORE THIS DATE STEEL INCREASES OF 1
 1/3 WERE COMMON PLACE AND TAKEN WITH FASTENERS, AP.E.
 SHOULD REVIEW THE TEST REPORT INFORMATION TO SEE IF THE
 INCREASES WERE TAKEN.THE NEWER MIAMI-DADE NOAS THAT
 WERE RENEWED AFTER THE 2004 FBC WENT INTO EFFECT WILL
 STATE UNDER THE HEADING (3) CALCULATIONS, ANCHOR
 VERIFICATION VERIFIED TO THE 2004 FBC- NO STEEL
 INCREASES TAKEN. NOA 04-0203.03 ANCHOR CALCULATIONS
 THIS REVISION ON 08/09/04 BEFORE THE ISSUANCE OF THE
 2004 FBC.
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
 EXCEPTION: INCREASES IN ALLOWABLE STRESS SHALL BE
 PERMITTED IN ACCORDANCE WITH ACI 530/ASCE 5/TMS 402
 PROVIDED THE LOAD REDUCTION OF SECTION 1605.3.1.1 ITEM
 1 SHALL NOT BE APPLIED.
 3.SIMULTANEOUS USE OF BOTH ONE-THIRD INCREASE IN
 ALLOWABLE STRESS AND THE 25-PERCENT REDUCTION IN
 COMBINED LOADS SHALL NOT BE PERMITTED.
  
 28E2) EXTERIOR HOLLOW METAL DOORS SINGLE AND PAIRS -
 COMPLIED.SEE CALCULATION STATEMENT # 1, ANCHOR
 VERIFICATION OF THE 2004 FBC
  
 28F)1) EXTERIOR COIL DOORS/ SECTIONAL DOORSCORNELL IRON
 WORKS SUBMITTED FL5416 THE ATTACHED MIAMI-DADE REPORT
 IS NOT THE CORRECT BACK-UP REPORT LISTED WITH THE
 STATE, ES16-23-01 IS THE CORRECT REPORT.
  
 28F)2) EXTERIOR COIL/ ROLL UP DOOR COOKSON COMPANY
 FL2211-R1 THE ATTACHED IS A MIAMI-DADE REPORT IS NOT
 THE CORRECT BACK-UP REPORT LISTED WITH THE STATE,
 WLCD-002-B-2004 IS THE CORRECT REPORT,
  
 28F)3) EXTERIOR SECTIONAL DOOR: CLOPAY MISSING THE
 FLORIDA COVERSHEET AND CORRESPONDING REPORTS THERE ARE
 (3) REPORTS WITH THE DOOR MODEL 3200 OR 3220. NOTE
 PRESSURES ARE LOWER UNDER THESE REPORTS.
  
 28G) FASCIA SYSTEMS
  
 28H) EFIS WALL SYSTEMS- DRYVIT SYSTEMS FL2030-R2
 SUBMITTED 06-0608.05PLEASE SUPPLY CORRESPONDING
 REPORT 06-1004.06DRYVIT OUTSULATION PLUS, PLEASE
 CORRECT.
  
 28I) ROOFING SYSTEMS W/ INSULATION- COMPLIED.
  
 28J) ROOF HATCH- COMPLIED.
  
 28K) LOUVER WALL- RUSKIN FL3283-R1 WAS SUBMITTED WITH
 THE WRONG MIAMI-DADE NOA FOR BACK UP
  
 28L) ALCAN ALUCOBOND COMPOSITE WALL PANEL NOA
 06-1019.02 IS A NON-FIRE RATED COMPOSITE PANEL, WHERE
 WILL THIS PRODUCT BE USED, TYPE I-B NONCOMBUSTIBLES AND
 SECTION 603?
 NOTE # 4 STUDS GRATER THAN 4'-0"IN HEIGHT MUST
 BE DESIGNED BY A FL PE FOR A MAXIMUM OF 90+/-. FLORIDA
 DOES HAVE ALCAN COMPOSITE PANELS LISTED ON WEBSITE.
  
 29)COMPLIED.
  
 30)COMPLIED.
  
 31) BUILDING PROVISO: PLEASE PROVIDE THE MANUFACTURERS
 SPEC FOR FIRE RESISTANT RATING OF STRUCTURAL MEMBERS
 BEFORE FRAMING INSPECTION. THE CODE ANALYSIS INDICATES
 THIS TO BE A TYPE I-B BUILDING REQUIRING FIRE RATINGS
 OF THE STRUCTURAL STEEL AND BAR JOIST, PLEASE PROVIDE
 THE MANUFACTURERS SPEC AND THE THICKNESS REQUIRED TO
 ACHIEVE THE REQUIRED FIRE RATING. TABLE 601 & 721.5.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved