| 2008-04-09 19:00:35 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | MUNICIPAL CODE CITY WPB |
| | |
| | PLANS IN FOR PLAN REVIEW ONLY AT THIS TIME: |
| | |
| | 1. SHT G001 PLUMBING FIXTURE COUNT SHOWS SIX LAVS |
| | REQUIRED. PER TABLE 403.1 SEVEN LAVS ARE REQUIRED. |
| | PLEASE CORRECT REQUIRED LAV FIXTURE COUNT. |
| | |
| | 2. SHT G001 FIXTURES PROVIDED SHOWS 3 DRINKING |
| | FOUNTAINS REQUIRED. 5 DRINKING FOUNTAINS ARE REQUIRED. |
| | DRINKING WATER AVAILABLE AT THE FOOD SERVICE ONLY |
| | COUNTS AS ONE FIXTURE EXCEPTION. SHOW 4 DRINKING |
| | FOUNTAINS. TABLE 403.1 & SECTION 410.1. |
| | |
| | 3. SHT G001 SHEET INDEX. 3 SHEETS ON THE INDEX WERE NOT |
| | FOUND & 2 "F" SHEETS & 10 "R" SHEETS SUBMITTED ARE NOT |
| | SHOWN ON THE INDEX. PLEASE CORRELATE. SECTION 106.1.2. |
| | |
| | 4. SHT A121 SHOW COMPLIANCE WITH SECTIONS 1210.1 & |
| | 1210.2 OF THE BUILDING CODE FOR FINISHES. |
| | |
| | 5. SHTS A141 & P111 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106& 1107 WITH |
| | ALL SUBSECTIONS AND TABLES. INDICATE THE TOTAL AREA TO |
| | BE DRAINED FOR EACH ROOF DRAIN. INCLUDE IN THE |
| | CALCULATIONS 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS AND ANY ROOF AREA THAT DRAINS ON TO THE ROOF |
| | AREA FROM ABOVE. SUBMIT THE ELEVATION OF THE ROOF AT |
| | THE HIGH POINTS AND LOW POINTS AS WELL AS THE ELEVATION |
| | OF THE TOP OF ALL PARAPETS TO VERIFY CALCULATIONS. AS |
| | SHOWN ON SHT P111 THE SQUARE FOOTAGE INDICATED IS THE |
| | SAME FOR EACH ROOF DRAIN, BUT THE AREAS ARE DIFFERENT |
| | PER THE SLOPE AND THE CRICKETS. |
| | |
| | 6. SHT A313 DETAIL #1 SHOW THE ACCESSIBLE WATER CLOSETS |
| | IN TOILET ROOMS 108 & 109 TO BE 1'6" OFF THE SIDE WALL |
| | OF THE STALL PER FIGURE 11-30E. |
| | |
| | 7. SHT A313 SHOW THE CLEAR FLOOR SPACE FOR ACCESSIBLE |
| | WATER CLOSETS AND LAVS PER SECTIONS 11-4.16.2 & |
| | 11-4.19.3. |
| | |
| | 8. SHT A313 DETAIL #20ACCESSIBLE WATER CLOSET IS |
| | INDICATED AS 1'5" CLEAR OFF THE WALL TO THE CENTERLINE |
| | OF THE W/C. THE W/C IS REQUIRED TO BE 1'6" OFF THE WALL |
| | TO THE CENTERLINE OF THE FIXTURE PER FIGURE 11-30E. |
| | PLEASE CHANGE DETAIL. |
| | |
| | 9. PLEASE SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING |
| | FOUNTAINS SHOWING COMPLIANCE WITH SECTION 11-4.15 AND |
| | ALL SUBSECTIONS. AT LEAST 50% OF DRINKING FOUNTAINS |
| | PROVIDED SHALL BE ACCESSIBLE PER SECTION |
| | 11-4.1.3(10)(B). |
| | |
| | 10. SHT FD1 EQUIPMENT SCHEDULE ITEMS FS0593 & SB0036 |
| | WATER FILTERS SHALL MEET THE REQUIREMENTS OF NSF-42. |
| | SECTION 611.1. PLEASE SUBMIT MANUF. SPECIFICATION |
| | SHEETS INDICATING COMPLIANCE. |
| | |
| | 11. SHT P100 KEY NOTES #2 & #3 ALL PIPING SHALL BE |
| | SHOWN FOR STORM AND SANITARY WITHIN THE FOOTPRINT OF |
| | THE BUILDING AND TO 5 FEET OUTSIDE THE BUILDING. THIS |
| | PIPING SHALL BE INSTALLED BY THE PLUMBING CONTRACTOR |
| | NOT THE SITE UTILITY CONTRACTOR AS INDICATED PER |
| | FLORIDA STATUTES 489. SHOW ALL PIPE SIZES, CLEANOUTS, |
| | OFFSETS, DFU'S FOR SANT. AND ALL PIPE SIZE, OFFSETS, |
| | C/O'S, SQUARE FOOTAGE ETC. PER TABLES 710.1, 710.2, |
| | 1106.3 AND SECTIONS 708 & 1101.8. |
| | |
| | 12. SHT P300 DETAIL #4/P300 SHOWS THE TOP OF THE HUB TO |
| | BE 1/2" ABOVE FINISHED FLOOR. SECTION 802.3.2 REQUIRES |
| | THE TOP OF THE HUB TO BE 1" ABOVE FINISHED FLOOR. |
| | PLEASE CORRECT DETAIL. |
| | |
| | 13. SHT P300 3" FLOOR DRAIN IN MECHANICAL ROOM 003 |
| | INDICATES DETAIL 4/P601. DETAIL 4/P601 IS A GREASE |
| | INTERCEPTOR DETAIL. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 14. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE |
| | UTILITY DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL |
| | COMPLIANCE. ALSO THEPHOTO PROCESSING MAY BE REQUIRED |
| | TO INSTALL A NEUTRALIZING TANK. PLEASE CONTACT RODNEY |
| | COMPO, ENVIRONMENTAL COMPLIANCE AT (561)644-1821, OR |
| | BY FAX (561) 822-2287, OR E-MAIL [email protected]. A |
| | WRITTEN DETERMINATION FOR BOTH ISSUES SHALL BE |
| | SUBMITTED WITH PLANS INDICATING THE REQUIREMENT |
| | OUTCOME. ARTICLE III SECTION 90-124(7). |
| | |
| | 15. SHT P301 DETAIL #5 THERMAL EXPANSION CONTROL IS |
| | REQUIRED AT THE WATER HEATER PER SECTION 607.3.2. |
| | PLEASE INDICATE METHOD. |
| | |
| | 16. SUBMIT AN ISOMETRIC RISER DIAGRAM FOR THE 10" AREA |
| | DRAINS AT THE TRUCK RAMP/LOADING AREA SHOWN ON SHT |
| | P110. SHOW ALL PIPE SIZES AND SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM. SHOW THE SQUARE FOOTAGE |
| | DRAINED BY EACH DRAIN AND SUBMIT CALCULATIONS SHOWING |
| | THE VERTICAL CONTRIBUTION ADDED TO EACH AREA. SHOW THE |
| | TERMINATION POINT OF PIPING. SECTIONS 106.3.5.1.3, 1106 |
| | & 1107 WITH ALL SUBSECTIONS & TABLES. |
| | |
| | 17. SHT P302 FILTERS FOR FCW-F, (FS-0593), SHALL MEET |
| | THE REQUIREMENTS OF NSF-42. SECTION 611.1. PLEASE |
| | SUBMIT MANUF. SPECIFICATION SHEETS. |
| | |
| | 18. SHT P302 THE RO SYSTEM SHALL MEET THE REQUIREMENTS |
| | OF NSF-58. SECTION 611.2. PLEASE SUBMIT MANUF. |
| | SPECIFICATION SHEETS. |
| | |
| | 19. SHT P311 DETAIL #3 THERMAL EXPANSION CONTROL IS |
| | REQUIRED PER SECTION 607.3.2. PLEASE INDICATE METHOD. |
| | |
| | 20. SHT P351 DETAIL #5 THERMAL EXPANSION CONTROL IS |
| | REQUIRED PER SECTION 607.3.2. PLEASE INDICATE METHOD. |
| | |
| | 21. SHT P501 DETAILS #2 & #5 WATER HAMMER ARRESTORS |
| | SHALL BE LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE |
| | RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. PLEASE |
| | SHOW THE WATER HAMMER ARRESTORS NEAR THE FIXTURES. |
| | |
| | 22. SHT P501 DETAILS #1, #3 & #4 SUBMIT HORIZONTAL |
| | BUILDING STORM & SANITARYDRAIN ISOMETRIC RISER |
| | DIAGRAMS FOR THE UNDERGROUND PIPING TO 5FT OUTSIDE THE |
| | BUILDING. SHOW ALL PIPE SIZE, CLEANOUTS, OFFSETS DFU'S |
| | FOR SANT. AND ALL PIPE SIZE, C/O'S, OFFSETS, SQUARE |
| | FOOTAGE ETC. PER TABLES 710.1, 710.2, 1106.3 AND |
| | SECTIONS 106.3.5.1.3, 708 & 1101.8. |
| | |
| | 23. SUBMIT VACUUM/CONDENSATE ISOMETRIC RISER DIAGRAM |
| | SHOWING ALL PIPE SIZES, OFFSETS, VENTS AS WELL AS THE |
| | TERMINATION POINT FOR THE SYSTEM. SECTION 106.3.5.1.3. |
| | |
| | 24. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING IS |
| | REQUIRED FOR THE GAS PERMIT. |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE.--LENGHTS OF CUT SECTIONS NOT SHOWN. |
| | |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4).--TO BE VERIFIED WHEN |
| | COMMENT 24(A) SUBMITTED. |
| | |
| | D. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | E. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | G. THE LOCATION OF THE GAS METER, THE GENERATOR AND |
| | ASSOCIATED GAS PIPING SHALL BE INDICATED ON THE |
| | PLUMBING SHEETS TO VERIFY THE GAS ISOMETRIC PIPING. |
| | SECTION 106.1.2. |
| | |
| | 25. PLANS ARE NOT 100% COMPLETE AT THIS TIME AND MORE |
| | COMMENTS MAY FOLLOW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |