2008-03-16 12:58:05REVIEW #: 1ST***PLAN CHECK ONLY***
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M321: RTU 5 DUCT SYSTEM ON FLOOR PLAN CALLS FOR A
 TOTAL OF 10,950 CFM OF SUPPLY WHILE THE RTU SCHEDULE ON
 M141 SHOWS RTU 5 PROVIDING 9125 CFM OF SUPPLY. WHICH
 ONE IS CORRECT? AIR DISTRIBUTION SYSTEMS SHALL BE
 DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED
 DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM 603.1.
  
 2. PG M321: AN 8 INCH ROUND, 175 CFM C-TYPE GRILL IS
 SHOWN ON FLOOR PLAN NEAR PHARMACY STORAGE ROOM 132. THE
 FLOOR PLAN DOES NOT INDICATE FROM WHERE THIS GRILL WILL
 BE SUPPLIED. THIS APPEARS TO BE A POSSIBLE DRAFTING
 ERROR. PLEASE CORRECT. FBCM 603.1.
  
 3. PG M141: DETAIL 2, NO INFORMATION COULD BE FOUND ON
 PLANS OR IN STRUCTURAL CALCULATIONS REGARDING
 ANTICIPATED WIND PRESSURES ON OUTDOOR AND ROOFTOP
 EQUIPMENT AND APPLIANCES. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 ON THE EQUIPMENT AND THE SUPPORTS AS DETERMINED IN
 ACCORDANCE WITH THE FBCB PER FBCM 301.13. PROVIDE WIND
 LOAD CALCULATIONS WITH CORRESPONDING ATTACHMENT DETAILS
 FOR BUILDING PLAN REVIEW. IF MANUFACTURER HAS TESTED
 AND DOCUMENTED DETAILS FOR ATTACHMENT, THEY MAY BE USED
 TO DEMONSTRATE COMPLIANCE (PROVIDE DOCUMENTATION).
 ALSO, PLEASE PROVIDE EQUIPMENT AND APPLIANCE
 MANUFACTURER?S DATA SHOWING ALL OUTDOOR EQUIPMENT SUCH
 AS CONDENSING UNITS, ROOFTOP A/C UNITS, EXHAUST FANS
 AND THE ROOFTOP CONDENSER RACK TO BE DESIGNED AND
 CONSTRUCTED TO WITHSTAND ANTICIPATED WIND PRESSURES
 CALCULATED IN ACCORDANCE WITH FBCB SECTION 1609.
  
 4. PG M141 AND R141: ARE CONDENSING UNITS AND THE
 ROOFTOP CONDENSER RACK TO BE INSTALLED ON SOLID CURBS
 OR STANDS? DETAILS ON PLANS ARE UNCLEAR AS TO WHICH
 TYPE OF CURB IS TO BE USED AT WHICH LOCATION. WHERE
 ROOFING MATERIALS EXTEND BENEATH THE UNIT ON RAISED
 EQUIPMENT SUPPORTS, A MINIMUM CLEARANCE HEIGHT IS
 REQUIRED IN ACCORDANCE WITH FBCB TABLE 1509.7.
 NOTE PRE-ENGINEERED A/C STANDS ARE DEFINED BY FAC RULE
 9B-72 AS STRUCTURAL COMPONENTS. IF SUCH STANDS ARE
 USED, A PRODUCT APPROVAL IS REQUIRED AND SHALL BE
 SUBMITTED WITH PERMIT APPLICATION. PRODUCT APPROVALS
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL TO THE AHJ IN
 ACCORDANCE WITH FBCB 106.3.3.
  
 5. PG M301: THERE DOES NOT APPEAR TO BE A FIRE RATED
 SEPARATION BETWEEN THE PARKING GARAGE AREA (S-2
 OCCUPANCY) AND THE 1ST FLOOR LOBBY AREA OF THE STORE (M
 OCCUPANCY). WHILE THERE IS A "CODE ANALYSIS" ON PG G001
 INDICATING THAT A FIRE RATED SEPARATION IS NOT REQUIRED
 IN THIS AREA, THE ANALYSIS DOES NOT APPEAR TO BE
 ACCURATE. THE GOVERNING CODE SECTION REGARDING REQUIRED
 SEPARATION IS FBCB 406.2.7 WHICH STATES: ?PARKING
 GARAGES SHALL BE SEPARATED FROM OTHER OCCUPANCIES IN
 ACCORDANCE WITH SECTION 302.3.2.? FBCB TABLE 302.3.2
 FOR SEPARATED USES REQUIRES A MINIMUM 2-HOUR SEPARATION
 BETWEEN THESE OCCUPANCIES. AS IT IS UNKNOWN WHERE THIS
 OCCUPANCY SEPARATION WILL BE PROVIDED, IT IS NOT
 POSSIBLE TO DO A THOROUGH REVIEW OF THE MECHANICAL
 SYSTEMS SHOWN ON THIS PAGE AT THIS TIME. ENSURE THAT
 OPENING PROTECTIVES ARE SHOWN WHENEVER DUCTS PENETRATE
 RATED ASSEMBLIES IN ACCORDANCE WITH FBCM 607.5.
 COORDINATE WITH ARCHITECTURAL PLANS.
  
 6. PG M301: KEYNOTES 1 AND 2 CALL FOR DUCT AND PIPE
 PENETRATIONS THROUGH A FIRE RATED HORIZONTAL ASSEMBLY
 (SEE COMMENT ABOVE). SHOW HOW THESE OPENINGS ARE TO BE
 PROTECTED IN ACCORDANCE WITH FBCM 607.6 AND FBCB
 712.4.1.2.
  
 7. PG M301 AND M321: FLOOR PLAN AND KEYNOTES CALL FOR
 COMBINATION FIRE/SMOKE DAMPERS. HOW WILL THE SMOKE
 DAMPERS BE ACTUATED? DETAIL #14 ON PG E941 SHOWS A
 SMOKE DETECTOR W/DAMPER INTERFACE BUT IT IS UNCLEAR
 WHERE THESE DETECTORS WILL BE LOCATED AND WHETHER THEY
 ARE TO BE CONNECTED TO THE SMOKE DAMPERS. INDICATE
 CLEARLY ON PLANS HOW THE SMOKE DAMPERS ARE TO BE
 ACTUATED BY ONE OF THE METHODS LISTED IN ACCORDANCE
 WITH FBCM 607.3.2.1.
  
 8. PG M321: THE 16X16 DUCT FOR TF-4 IS SHOWN
 PENETRATING A 2-HOUR RATED WALL ASSEMBLY (TYPE P33X)
 INTO ROOM 155, AS SHOWN ON PG A351. THIS DUCT IS ALSO
 SHOWN RUNNING PARALLEL DIRECTLY ABOVE THE 2-HOUR RATED
 WALL BETWEEN ROOMS 115 AND 161. THESE WALLS APPEAR TO
 BE FROM FLOOR TO UNDERSIDE OF ROOF DECK. THE FIRE/SMOKE
 DAMPERS IN THE DUCTS FEEDING THE UPPER EDC AREA DO NOT
 APPEAR TO BE LOCATED WHERE FIRE-RESISTANCE RATED
 CONSTRUCTION IS BEING PROVIDED. THIS AREA REQUIRES
 ADDITIONAL CLARIFICATION AS TO THE DESIGN INTENT AND
 THE LOCATION OF ALL FIRE-RESISTANCE RATED ASSEMBLIES.
 PLEASE COORDINATE WITH ARCHITECTURAL PLANS, SHOWING
 OPENING PROTECTIVES AT ALL DUCT PENETRATIONS OF RATED
 ASSEMBLIES IN ACCORDANCE WITH FBCM 607.5.
  
 9. ALL MECHANICAL FLOOR PLANS: BY WHAT MEANS ARE THE
 EXHAUST FANS FOR RESTROOM AREAS BEING CONTROLLED? ARE
 THEY TO RUN CONTINUOUS, RUN BY LIGHT SWITCH OR RUN BY
 OCCUPANCY SENSORS? PLEASE INDICATE ON FAN PRV SCHEDULE
 HOW FANS ARE TO BE CONTROLLED. WHERE MECHANICAL EXHAUST
 IS REQUIRED BY FBCM TABLE 403.3, RECIRCULATION OF AIR
 FROM SUCH SPACES SHALL BE PROHIBITED. ALL AIR SUPPLIED
 TO SUCH SPACES SHALL BE EXHAUSTED, INCLUDING ANY AIR IN
 EXCESS OF THAT REQUIRED BY FBCM TABLE 403.3. SHOW PRV
 CONTROLS FOR RESTROOM AREAS TO BE IN COMPLIANCE WITH
 THIS SECTION. ALSO, SEE FBCM 401.3.
  
 10. PG M301 AND M601: AC-2 SHALL BE PROVIDED WITH FAN
 SHUT-DOWN BY SMOKE DETECTOR IN ACCORDANCE WITH FBCM
 606.2 AND 606.4.
  
 11. OUTSIDE AIR CALCULATIONS COULD NOT BE FOUND ON
 PLANS. PLEASE PROVIDE CALCULATINS SHOWING OCCUPANCY
 CLASSIFICATION, OCCUPANT LOAD, AMOUNT OF VENTILATION
 REQUIRED AND AMOUNT OF VENTILATION PROVIDED IN
 ACCORDANCE WITH FBCM TABLE 403.3. ALSO, PROVIDE AN AIR
 BALANCE SHEDULE SHOWING BUILDING SYSTEMS TO BE IN
 BALANCE IN ACCORDANCE WITH FBCM 403.1 AND FBCB
 13-409.1.ABC.2.
  
 12. SYSTEM SIZING CALCULATIONS: SOME ASPECTS OF THE
 COOLING LOAD CALCULATION DATA DO NOT CORRESPOND WITH
 THE INFORMATIN PROVIDED IN THE EQUIPMENT SCHEDULE ON PG
 M141. EXAMPLE: RTU-02 IN THE SCHEDULE SHOWS THE AIRFLOW
 AT 12,380 CFM WHILE THE AIRFLOW IN THE SYSTEM SIZING
 CALCULATION SHOWS 16,483. PLEASE SHOW INFORMATION IN
 CALCULATIONS TO BE ACCURATE WITH RESPECT TO THE
 INFORMATION SHOWN ON PLANS. ALSO, MOST SYSTEMS IN THE
 CALCULATIONS SHOW RETURN AIR FLOW RATES IN EXCESS OF
 THE SUPPLY AIR FLOW RATES. HOW IS THIS POSSIBLE? ARE
 THE RTU'S EXHAUSTING AIR? WILL THIS CONDITION PUT THE
 SPACES IN NEGATIVE PRESSURE? PLEASE CLARIFY. SEE FBC
 13-407.1.ABC.1.1. SEE ALSO COMMENT #11 ABOVE.
  
 13. ENERGY CALCULATIONS: SEVERAL OF THE A/C SYSTEMS
 SHOWN IN THE SYSTEM REPORT COMPLIANCE PORTION OF THE
 ENERGY CALCULATIONS DO NOT CORRESPOND WITH THE
 INFORMATION PROVIDED IN THE EQUIPMENT SCHEDULE ON
 PLANS.
 EXAMPLE 1: RTU-01 IS IDENTIFIED ON PLANS AS A LENNOX
 48,000 BTU/H SYSTEM BUT IN ENERGY CALCULATIONS IT IS
 SHOWN AS AN AAON SYSTEM SIZED BETWEEN 65,000 AND 135,
 000 BTU/H.
 EXAMPLE 2: RTU-02 IS IDENTIFIED ON PLANS AS A LCC360H4B
 339,506 BTU/H SYSTEM WITH AN EER OF 10.1 BUT IN ENERGY
 CALCULATIONS IT IS SHOWN AS A LCC156H2B SIZED BETWEEN
 135,000 AND 240,000 BTU/H WITH AN EER OF 12.2.
 THE VALUES ENTERED ON THE ENERGY CALCULATION MUST
 CORRESPOND WITH THE INFORMATION ON THE PLAN IN ORDER TO
 SHOW COMPLIANCE WITH FBCB CHAPTER 13. THESE ARE ONLY
 TWO EXAMPLES OF MANY DISCREPENCIES BETWEEN THE PLANS
 AND ENERGY CALCULATIONS. PLEASE VERIFY ALL INPUT DATA
 IN THE ENERGY CALCULATIONS WITH THE INFORMATION SHOWN
 ON THE PLANS TO ENSURE THE ACCURACY OF THE
 CALCULATIONS. THE PLANS AND SPECIFICATIONS, INCLUDING
 THE ENERGY CODE CALCULATIONS, SHALL SHOW, IN SUFFICIENT
 DETAIL, ALL PERTINENT DATA AND FEATURES OF THE BUILDING
 AND THE EQUIPMENT AND SYSTEMS AS HEREIN GOVERNED
 INCLUDING, BUT NOT LIMITED TO: DESIGN CRITERIA,
 EXTERIOR ENVELOPE COMPONENT MATERIALS, U-VALUES OF THE
 ENVELOPE SYSTEMS, R-VALUES OF INSULATING MATERIALS,
 SIZE AND TYPE OF APPARATUS AND EQUIPMENT, EQUIPMENT AND
 SYSTEMS CONTROLS AND OTHER PERTINENT DATA TO INDICATE
 CONFORMANCE WITH THE REQUIREMENTS OF THE CODE IN
 ACCORDANCE WITH FBCB 13-103.3. ENERGY CALCULATIONS WILL
 BE REVIEWED IN THEIR ENTIRETY UPON RESUBMITTAL.
  
 NOTE: A SEPARATE PERMIT IS REQUIRED FOR THE
 REFRIGERATION AND WALK-IN COOLER SYSTEMS. THE
 DOCUMENTATION FOR THESE SYSTEMS IS SUFFICIENT WITH THE
 EXCEPTION OF ANY INFORMATION REQUESTED IN ABOVE
 COMMENTS. THE SEPARATE PERMIT MAY BE APPLIED FOR BY
 REFERENCE TO THE MASTER PERMIT NUMBER AND THESE PLANS.
  
  
 NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING, WIH
 INFORMATION ON HOW THE COMMENT IS ADDRESSED AND WHERE
 THE RELEVANT INFORMATION CAN BE LOCATED.
  