| Date |
Text |
| 2008-04-24 12:16:35 | *****DENIED***** |
| | |
| | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 02.WHEN THE OLD BUILDING IS TO BE DEMOLISHED, THE |
| | SPRINKLER SYSTEM SHALL NOT BE RENDERED INOPERABLE |
| | WITHOUT THE APPROVAL OF WEST PALM BEACH FIRE |
| | PREVENTION. |
| | |
| | 03.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER |
| | EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR THE |
| | VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE |
| | LANES) . |
| | |
| | 04.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS |
| | PALM BEACH LAKES BOULEVARD, DISPLAY/SHOW THE ACTUAL |
| | ADDRESS NUMBERS ON THE STRUCTURE OF THE BUILDING.AS |
| | PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE A |
| | MINIMUM OF 6" IN HEIGHT AND 1" IN WIDTH/STROKE.IN THE |
| | EVENT THAT THE ADDRESS IS NOT READILY VISIBLE DUE TO |
| | THE BUILDING'S SETBACK FROM THE STREET, A MONUMENT |
| | SIGN/MARKEE WILL BE REQUIRED DEPICTING THE ADDRESS IN |
| | ADDITION TO THOSE ON THE STRUCTURE OF THE BUILDING. |
| | |
| | 05.ILLUSTRATE ANY EXISTING OR NEW FIRE HYDRANTS. |
| | |
| | 06.KNOX-BOX FOR THE BUILDING SHALL BE REQUIRED.SHOW |
| | WHERE THIS DEVICE WILL BE INSTALLED IN AN ACCESSIBLE |
| | LOCATION SO THAT FIRE RESCUE MAY GAIN EMERGENCY ACCESS |
| | TO THE STRUCTURE. |
| | |
| | 07.ONLY ONE FIRE DEPARTMENT CONNECTION (FDC) IS |
| | SHOWN.CONSIDERING THE SIZE OF THIS CLASS A ( MORE |
| | THAN 30,000 SQUARE FEET) MERCANTILE OCCUPANCY WITHOUT |
| | THE MENTION OF A FIRE PUMP, WILL THE ONE FDC BE |
| | ADEQUATE? |
| | |
| | 08.KNOX LOCKING CAPS SHALL BE REQUIRED ON THE FIRE |
| | DEPARTMENT CONNECTION(S) .FOR AN APPLICATION, CONTACT |
| | WEST PALM BEACH FIRE PREVENTION AT 561-804-4724. |
| | |
| | 09.THE FIRE BARRIER SEPARATING PARKING STRUCTURES |
| | FROM THE MERCANTILE OCCUPANCY SHALL BE A FIRE BARRIER |
| | HAVING A FIRE RESISTIVE RATING OF NOT LESS THAN 2 |
| | HOURS. |
| | |
| | 10.OUTSIDE STAIRS, RAMPS, AND LANDINGS SHALL BE |
| | DESIGNED TO MINIMIZE WATER ACCUMULATION ON THEIR |
| | SURFACES. |
| | |
| | 11.PRESCRIPTIVE STRENGHT REQUIREMENTS SHALL BE NOTED |
| | FOR ALL HANDRAILS AND GUARDRAILS. |
| | |
| | 12.HANDRAILS/GUARDRAILS SHALL BE REQUIRED ON BOTH |
| | SIDES OF THE STAIRS AND RAMPS. |
| | |
| | 13.FIRE DOORS AND FIRE WINDOWS SHALL COMPLY WITH NFPA |
| | 80. |
| | |
| | 14.BUILDING PLANS SHALL BE DRAWN TO A MINUMUM OF 1/8 |
| | INCH SCALE.SEVERAL SHEETS (SUCH AS A201, E911, FOR |
| | EXAMPLE) ARE SHOWN AT 1/16 INCH SCALE. |
| | |
| | 15.ON SHEET A020 AND A021, IT IS ASSUMED THAT THE |
| | EXIT DIAGRAM IS THE SAME AS THE LIFE SAFETY PLAN. IF |
| | THIS ASSUMPTION IS INCORRECT, PROVIDE A LIFE SAFETY |
| | PLAN DEPICTING TRAVEL DISTANCES TO THE EXITS. |
| | |
| | 16.ON SHEET A020 AND A021, THE PATH OF EGRESS IS |
| | SHOWN TO PASS THROUGH OBSTRUCTIONS.THE PATH OF EGRESS |
| | (TRAVEL DISTANCE ROUTE) SHALL NOT BE THROUGH AN |
| | OBSTRUCTION OR POSSIBLE OBSTRUCTION. |
| | |
| | 17.SPECIFYTHE INTERIOR WALL AND CEILING FINISH |
| | MATERIAL IN TERMS OF CLASS A OR CLASS B.SPECIFY |
| | INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II. |
| | |
| | 18.ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE |
| | FIGHTERS' EMERGENCY OPERATIONS OF ASME A17.1;AND |
| | SHALL BE ABLE TO ACCOMMODATE PARAMEDICAL EQUIPMENT. |
| | |
| | 19.ON SHEET A130, NO EXIT LIGHTS AND EMERGENCY |
| | LIGHTING IS SHOWN. |
| | |
| | 20.ON SHEET A131, NO EMERGENCY LIGHTING IS SHOWN AND |
| | MORE EXIT LIGHTS MAY BE REQUIRED.VERIFY THAT SIGN |
| | PLACEMENT SHALLBE SUCH THAT NO POINT IN AN EXIT |
| | ACCESS CORRIDOR IS IN EXCESS OF 100 FEET FROM THE |
| | NEAREST SIGN. |
| | |
| | 21.THERE IS AN EXIT LIGHT THAT DIRECTS PATRONS TO |
| | AREA/ROOM 174 BUT NO EXIT DOOR IS SHOWN. |
| | |
| | 22. THERE IS NO SHEET A200 IN THE PLAN SET AS INDICATED |
| | IN THE SHEET INDEX (SHEET G001) . |
| | |
| | 23. IN ADDITION TO THE ELECTRONIC SWITCHES, CHAIN AND |
| | LOCK WILL BE REQUIRED ON THE FIRE LINE BACKFLOW |
| | DEVICE. |
| | |
| | 24.NFPA 13 - 2002 EDITION - SHALL BE REFERENCED FOR |
| | THE INSTALLATION OF THE BUILDING'S SPRINKLER SYSTEM. IT |
| | IS INDICATED ON SHEET F300 REFERENCING THE 2004 |
| | EDITION. |
| | |
| | 25.PROVIDE A LAYOUT OF THE BUILDING'S FIRE SPRINKLER |
| | SYSTEM TO BE INSTALLED.PLEASE BE ADVISED THAT |
| | SPECIFICATIONS AND OTHER RELATED MATERIALS ARE NOT |
| | NEEDED AT THIS TIME. |
| | |
| | 26.FIRE SPRINKLER SYSTEM SHALL BE MONITORED. |
| | |
| | 27.ALTHOUGH IN PLAN SET, NO SHEETS F111, F300 ARE NOT |
| | SHOWN IN THE SHEET INDEX (SHEET G001) . |
| | |
| | 28.SHEETS R111, R141, R401, R411, R421, R501, R601, |
| | R621, AND R901 ARE NOT SHOWN IN THE SHEET INDEX (SHEET |
| | G001) . |
| | |
| | 29.COULD NOT LOCATE THE FLOWS AND TAMPERS ON THE |
| | SPRINKLER AND/OR FIRE ALARM DRAWINGS. |
| | |
| | 30.PLEASE EXPLAIN THE CORRELATION BETWEEN THE |
| | SPRINKLER SUPERVISORY INITIATING DEVICE PLAN ( E901 FOR |
| | EXAMPLE) AND A FIRE ALARM PLAN. |
| | |
| | 31.INDICATE THE FLOOR LEVAL ON THE FIRE ALARM |
| | SHEETS. |
| | |
| | 32.IT IS SHOWN ON SHEET E912,THE ELECTRICAL |
| | DISTRIBUTION CENTER/ROOM 116.HOW DOES ONE ACCESS THIS |
| | SPACE?IS THIS AREA FIRE PROTECTED (SPRINKLERED, FIRE |
| | RESISTIVE SEPARATED, ETC.) |
| | |
| | 33.HOW IS THE EMERGENCY LIGHTING IN THE STAIRWELLS |
| | ATTAINED? |
| | |
| | 34.PLEASE EXPLAIN WHAT IS AN INTRUSION SYSTEM. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET |
| | EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |