| 2008-03-08 14:40:07 | 2008-03-08 14:40:07 |
| | |
| | ** DENIED REVIEW** |
| | |
| | ** PLAN REVIEW |
| | SUPER TARGET |
| | 1760 PALM BEACH LAKES BLVD. |
| | |
| | ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET |
| | SUBMITTED FOR REVIEW AND SOME ITEMS NOT YET ON PLANS A |
| | REVIEW OF ONLY THE DOCUMENTS SUBMITTED CAN BE DONE AT |
| | THIS TIME. THERE MAY BE NEW COMMENTS ON THE FOLLOWING |
| | REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR * PLAN |
| | REVIEW ONLY * AND HAVE NOT BEEN SUBMITTED UNDER PERMIT |
| | APPLICATION. PLEASE KNOW THAT ONCE ALL ITEMS FOR CODE |
| | REVIEWS ARE DONE PLANS WILL STILL REMAIN IN FAILED |
| | STATS UNTIL PERMIT APPLICATION HAS BEEN MADE. |
| | VERIFICATION OF SEVERAL ITEMS SUCH AS VALID LICENSING |
| | ETC IS DONE AT TIME OF APPLICATION BEFORE ISSUANCE OF |
| | PERMIT(S). |
| | IF THERE ARE ANY QUESTIONS ON THIS PLEASE CONTACT THIS |
| | OFFICE/REVIEWER. |
| | |
| | 2) NOTE: PLEASE KNOW THAT ALL LOW VOLTAGE WIRING SHALL |
| | BE UNDER SEPARATE PERMITS FROM THE MAIN ELECTRICAL |
| | PERMIT. THE LV FOR PHONE, CATV AND OTHER SYSTEMS NOT |
| | INCLUDING LV FOR SECURITY MAY BE ALL UNDER ONE LV |
| | PERMIT. THE SECURITY SYSTEM IS A SEPARATE LV PERMIT |
| | FROM OTHERS LISTED ABOVE. IN EITHER CASE AS ALL LOW |
| | VOLTAGE SYSTEMS ARE SHOWN ON BASE BUILDING PLANS, THE |
| | APPLICANT MAY REFERENCE THESE PLANS FOR A *TURN-AROUND* |
| | PERMIT. |
| | ** THIS IS GIVEN FOR INFORMATIONAL PURPOSE AND IF THERE |
| | ARE ANY QUESTIONS ON THIS ITEM PLEASE CONTACT THIS |
| | REVIEWER. |
| | |
| | 3) NOTE: PLEASE SEE NOTICE AT THE END OF THIS REVIEW |
| | WHICH IS NOTED AS ** IMPORTANT** ON CORRECT PROCEDURE |
| | ON RE-SUBMITTING PLANS AND THE REMOVING OF OLD/VOIDED |
| | SHEETS. IF THERE QUESTIONS PLEASE CONTACT THIS |
| | REVIEWER. |
| | |
| | 4) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS AS WELL AS |
| | COVER SHEET ON ARCHITECTURAL COVER SHEETS CONTAIN THE |
| | FOLLOWING CODES. SOME OF THESE MAY ALREADY BE LISTED |
| | HOWEVER NOT ALL AT BOTH PLACES. THESE MAY BE ON THE |
| | FIRST E-SHEET AND NOT ON ALL SHEETS. |
| | |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA_70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | 2002 NFPA-110 |
| | 2003 NFPA-20 (NOT YET DETERMINED) |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH ALSO |
| | MAY REQUIRE SPECIFIC CODES TO BE LISTED ON PLANS. |
| | |
| | 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE GENERATOR, ALL ATS EQUIPMENT, AND FUEL |
| | TANK. |
| | PLEASE KNOW THAT A REVIEW OF THE FUEL TANK WILL BE DONE |
| | BY THE MECHANICAL, FIRE MARSHAL ETC. |
| | PLEASE SEE COMMENTS BELOW WITH RESPECT TO THE ATS |
| | UNITS. |
| | ** PLEASE SUBMIT ANY FIRE PUMP AND FIRE PUMP |
| | CONTROLLERS SPECS/CUT SHEETS AS WELL IF THIS BUILDING |
| | WILL CONTAIN ANY SUCH UNITS. PLANS DID NOT SEEM TO |
| | CONTAIN ANY FIRE PUMP ETC AND A REVIEW OF MANY ITEMS |
| | COULD NOT BE DONE IF THIS BUILDING IS GOING TO CONTAIN |
| | A FIRE PUMP. |
| | IF APPLICABLE PLEASE SEE NFPA-20, CHAPTERS 9 AND 10. |
| | |
| | 6) NOTE: PLEASE SEE THE EMERGENCY LIFE SAFETY EQUIPMENT |
| | IS NOT PERMITTED IN THE SAME ROOM(S) AS THE NORMAL |
| | ELECTRICAL EQUIPMENT. PLEASE SEE NFPA-110 7.2, 7.1.3 |
| | PLEASE SEE 7.2.2.1 BELOW ALSO. |
| | 7.2.1THE EPS SHALL BE INSTALLED IN A SEPARATE ROOM FOR |
| | LEVEL 1 INSTALLATIONS. EPSS EQUIPMENT SHALL BE |
| | PERMITTED TO BE INSTALLED IN THIS ROOM. |
| | 7.2.1.1THE ROOM SHALL HAVE A MINIMUM 2-HOUR FIRE RATING |
| | OR BE LOCATED IN AN ADEQUATE ENCLOSURE LOCATED OUTSIDE |
| | THE BUILDING CAPABLE OF RESISTING THE ENTRANCE OF SNOW |
| | OR RAIN AT A MAXIMUM WIND VELOCITY REQUIRED BY LOCAL |
| | BUILDING CODES. |
| | 7.2.1.2NO OTHER EQUIPMENT, INCLUDING ARCHITECTURAL |
| | APPURTENANCES, EXCEPT THOSE THAT SERVE THIS SPACE, |
| | SHALL BE PERMITTED IN THIS ROOM. |
| | 7.2.2EPSS EQUIPMENT SHALL NOT BE INSTALLED IN THE SAME |
| | ROOM WHERE THE NORMAL ELECTRICAL SERVICE EQUIPMENT IS |
| | INSTALLED. |
| | 7.2.2.1TRANSFER SWITCHES SHALL BE PERMITTED TO BE |
| | INSTALLED IN THE NORMAL ELECTRICAL SERVICE ROOM WHERE |
| | TWICE THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF |
| | NFPA 70, NATIONAL ELECTRICAL CODE, EXISTS BETWEEN |
| | EQUIPMENT ENCLOSURES. |
| | |
| | 7) NOTE: PLEASE SEE 230.95, 240.13 AS THESE SECTIONS OF |
| | THE CODE AMONG OTHERS REQUIRED GROUND FAULT PROTECTION |
| | (GFP) ON THE SERVICE. THE PLANS CLEARLY SHOW THE GFP |
| | PROTECTION REQUIRED HOWEVER PLEASE SEE 700.6D, 700.26 |
| | AND NFPA-110 6.2.15. AS THE CODE REQUIRES GFP ON NORMAL |
| | SIDE AND REQUIRES GF SENSING ON THE EMERGENCY SIDE THE |
| | ISOLATION OF THE SYSTEMS AND NEUTRALS IS IMPERATIVE. |
| | PROVISIONS SHALL BE INCLUDED FOR ENSURING CONTINUITY, |
| | TRANSFER, AND ISOLATION OF THE PRIMARY AND THE EPS |
| | NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY |
| | GROUNDED TO ACHIEVE GROUND-FAULT SENSING. |
| | PLEASE SEE THE FOLLOWING INFORMATION GIVEN IS SECTIONS |
| | REMOVED FROM WHITE PAPERS AS WELL FROM TWO MANUFACTURES |
| | OF TRANSFER SWITCHES AND GENERATORS. THIS MAY HELP IN |
| | PROVIDING THE NEEDED EQUIPMENT AND ADJUSTMENT SO THE |
| | PLANS AND RISER. |
| | |
| | ** ** ASCO WHITE PAPER EXCERPT*** |
| | **WHERE GROUND FAULTPROTECTION IS TRIGGERED BY THE |
| | CODE AND AN ALTERNATE POWER SUPPLY IS INCLUDED, |
| | SWITCHING OF THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT |
| | SHOWN ABOVE ILLUSTRATESSUCH A CIRCUMSTANCE. THE |
| | SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, GROUND |
| | FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE |
| | DISCONNECT AT A MINIMUM. IF ITIS INSTALLED THERE AND |
| | THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID |
| | CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT |
| | WHEN THE GENERATOR ISFEEDING THE LOAD WILL CAUSE THE |
| | MAIN SERVICE DISCONNECT TO OPEN. THIS WILL NOT |
| | DISCONNECT THE ARCING FAULT FROM THE GENERATOR. |
| | COORDINATION IS THUSLOST." |
| | |
| | *****CATERPILLAR WHITE PAPER EXCERPT*** |
| | SHOULD THE DESIGNER WANT TO GROUND THE GENERATOR AND |
| | STILL ADHERE TO CODE AND AVOID THE PROBLEMS |
| | OF SPLIT RETURN PATHS AND IMPROPER GFP SENSING |
| | THE USE OF A FOUR POLE TRANSFER SWITCH IS CALLED FOR. |
| | FOUR POLE TRANSFER SWITCHES |
| | FOUR POLE SWITCHES ARE EMPLOYED TO INSURE |
| | THAT THE GENERATOR CAN BE GROUNDED WITHOUT COMPROMISING |
| | THE NEC. THAT IS, THE GEN SET |
| | CAN BE WIRED AS A SEPARATELY DERIVED SYSTEM BY |
| | GROUNDING THE NEUTRAL AT THE GEN SET AS LONG AS THE |
| | NEUTRAL IS NO LONGER SOLID THROUGH THE TRANSFER SWITCH. |
| | THIS OF COURSE INFERS THAT NEUTRAL BE SWITCHED AT THE |
| | SAME TIME AS THE PHASES. |
| | THIS SCHEME WILL ALSO INSURE GFP OPERATION AS INTENDED. |
| | FIG. 12 SHOWS A FOUR POLE TRANSFER SWITCH WIRED WITH A |
| | GEN SET HAVING ITS NEUTRAL GROUNDED AT THE HOUSING. IN |
| | THIS WIRING THE NEUTRAL RETURN PATH IS DELIBERATELY |
| | OPEN FOR GROUND RETURN CURRENTS BY THE TRANSFER SWITCH |
| | CONTACTS. THIS WILL ALSO AVOID NUISANCE TRIPPING IN THE |
| | CASE OF AN UNBALANCED LOAD. IN EFFECT, THE GEN SET IS |
| | NOW COMPLETELY ISOLATED FROM THE UTILITY SERVICE AND |
| | PRESENTS AN EFFECTIVE AND SAFE ALTERNATIVE TO SOLID |
| | NEUTRAL LINES. A DESIGNER HAS THE TOOLS TO NOW |
| | CONFIGURE A STANDBY SYSTEM AS EITHER SEPARATELY DERIVED |
| | OR NOT. IF THE SYSTEM NEEDS ARE FOR NOT GROUNDING THE |
| | GEN SET AT ITS SITE THEN A THREE POLE TRANSFER SWITCH |
| | WITH A SOLID NEUTRAL SHOULD BE EMPLOYED. IF THE GEN SET |
| | NEEDS TO BE GROUNDED AT ITS SITE, THEN A FOUR POLE |
| | TRANSFER SWITCH MUST BE DESIGNED INTO THE SYSTEM. THIS |
| | WILL INSURE THAT THE NEUTRAL IS SWITCHED ISOLATING THE |
| | NORMAL OR UTILITY SUPPLY. LASTLY, SHOULD THE DESIGNER |
| | DECIDE TO SWITCH THE NEUTRAL, CONSIDERATION TO CONTACT |
| | RATINGS AND PERFORMANCE SHOULD BE TAKEN INTO ACCOUNT. |
| | FOURTH POLE AND UL REQUIREMENTS |
| | AS OF APRIL 1989, UL 1008 REQUIRED THAT THE FOURTH POLE |
| | OF A TRANSFER SWITCH BE TESTED AND PROVEN TO HAVE |
| | RATINGS EQUAL TO ITS PHASE CONTACTS IF NOT OF THE SAME |
| | CONSTRUCTION. AND THAT BUS SPACING IS CLOSER TO LINE |
| | THAN ITS LINE TO LINE SPACING OR IT HAS A DIFFERENT |
| | MEANS OF SUPPORT FOR ITS NEUTRAL BUS. THAT MEANS THAT |
| | THE NEUTRAL CONTACT MUST BE CAPABLE OF WITHSTAND AND |
| | CLOSE INTO FAULT RATINGS AT LEAST EQUAL TO THE PHASE |
| | CONTACTS. THE FACT IS, NOT ALL TRANSFER SWITCHES |
| | EMPLOYING A FOURTH POLE ARE CONSTRUCTED IN LIKE |
| | FASHION. |
| | |
| | AS NOTED ABOVE THE USE OF 4-POLE TRANSFER SWITCHES IS |
| | NEEDED. PLEASE SHOW ON PLANS THE SEPARATELY DERIVED |
| | GROUNDING ELECTRODE SYSTEM AT THE GENERATOR. |
| | |
| | 8) NOTE: PLEASE SEE PANEL LP4 ON THE SECONDARY SIDE OF |
| | THE TRANSFORMER REQUIRES A MAIN CIRCUIT BREAKER PER |
| | 240.21, 408.36. |
| | |
| | 9) NOTE: PLEASE COMPLETE ALL INFORMATION ON PLANS AND |
| | SUPPORTING DOCUMENTS FOR COMPLIANCE WITH THE FBC AND |
| | CHAPTER 13. |
| | PLEASE KNOW THE MINIMUM REQUIRES FEDERALLY ADOPTED INTO |
| | LAW IN JULY 04 WAS THAT ALL STATES ARE REQUIRED TO MEET |
| | THE MINIMUM OF 1999 ASHRAE 90.1 OR BETTER BY THE NEXT |
| | CODE CYCLE. PLEASE SEE THE FBC AND CHAPTER 13 FOR ALL |
| | ITEMS. |
| | THIS NOTE WILL BE DONE INS SUB-SECTIONS AND THE INPUT |
| | DATA REPORT WILL BE NOTED AS IDR. |
| | |
| | A) PLEASE BE SURE TO SEE 13-415.1.ABC.1.1, .1.2, .1.3 |
| | AND .1.4 FOR ALL LIGHTING CONTROLS REQUIRED. PLEASE SEE |
| | THERE ARE SEVERAL LOCATIONS WHICH ARE MISSING REQUIRED |
| | CONTROLS. |
| | FOR EXAMPLE: |
| | MISSING SEPARATE SPACES OVER RIDES AND LIGHTING |
| | CONTROLS.ALL OVER RIDES ARE REQUIRED FOR SYSTEM |
| | CONTROLS. |
| | SOME EXAMPLES OFROOMS MISSING REQUIRED CONTROLS: |
| | 143,008,105,105A,108,109,122,168,139 ETC THIS IS NOT |
| | ALL LOCATIONS AND ONLY GIVING A FEW AS EXAMPLES. |
| | MISSING LIGHTING ZONES AS REQUIRED. |
| | MISSING BACK UP TIME FOR OUTSIDE LIGHTING PROGRAMMING |
| | WHICH CODE SECTION ABOVE REQUIRES A 10HR MINIMUM. |
| | PLEASE SEE MISSING CONTROLS AND DETAILS FOR OUTSIDE |
| | LIGHTING. |
| | |
| | B) PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND PLEASE |
| | PLACE REQUIRED NOTES ON PLANS ACCORDINGLY. |
| | |
| | C) PLEASE SEE 13-413.1.ABC.1.1 AND .1.2 AND SUBMIT |
| | VOLTAGE DROP CALCULATIONS FOR ALL WORST CASE. PLEASE |
| | SEE THERE ARE BRANCH CIRCUITS AND FEEDERS WHICH ARE IN |
| | QUESTION DUE TO THE LONGER LENGTHS AS SHOWN ON PLANS. |
| | |
| | D) PLEASE BE SURE ALL LIGHTING ON PLANS COORDINATES |
| | WITH THE LIGHTING ON THE IDR SUBMITTED WITH THE ENERGY |
| | CALCULATIONS. PLEASE KNOW AT THIS TIME THERE ARE |
| | SEVERAL HUNDRED FIXTURES/LUMINAIRES MISSING FORM THE |
| | IDR. |
| | PLEASE SEE FOR EXAMPLE: THE IDR FOR EXTERIOR LIGHTING |
| | SHOWS NOT ONE FIXTURE. HOW IS THIS POSSIBLE WHEN THERE |
| | ARE HUNDRED(S) OF LUMINAIRES ONPLANS??? |
| | PLEASE SEE FOR EXAMPLE: THE LIGHTING SHOWN ON THE |
| | FIXTURE LEGEND DOES NOT CORRELATE WITH THE IDR FOR |
| | DOZENS OF FIXTURES FOR THE CORRECT WATTAGES. PLEASE SEE |
| | 13-415.2.ABC.1, .1.1, .1.2 AND .1.3 FOR VA RATINGS TO |
| | BE USED IN CALCULATIONS. |
| | THIS SHALL INCLUDE ALL ACCENT LIGHTING SUCH AS TRACK |
| | LIGHTING WHICH IS NOTED SPECIFICALLY IN THE CODES ABOVE |
| | ALONG WITH THE VA TO BE FIGURED FOR COLD CATHODE |
| | LIGHTING NOTED ON SPECIALTY LIGHTING PLANS. |
| | |
| | E) PLEASE BE SURE TO SHOW AND INDICATE ALL LIGHTING |
| | FIXTURE DESIGNATIONS ON PLANS. PLEASE SEE SOME |
| | LOCATIONS DO CONTAIN A NOTE FOR TYPES OF FIXTURES |
| | HOWEVER MANY AREAS DO NOT CONTAIN DESIGNATIONS WHICH |
| | COORDINATE WITH THE FIXTURE LEGEND. |
| | EXAMPLE: ARE 102 |
| | |
| | F) PLEASE COORDINATE ELECTRICAL WATER HEATERS ON |
| | PLANS/EQUIPMENT SCHEDULE WITH THAT OF THE UNITS SHOWN |
| | ON THE IDR. THE IDR APPEARS TO SHOW MORE THAN THE UNITS |
| | ON EQUIPMENT SCHEDULE. |
| | |
| | ** PLEASE SEE THAT THE NOTES ABOVE WITH RESPECT TO FBC |
| | CHAPTER 13 ARE SOME OF THE ITEMS GIVEN AS EXAMPLES AND |
| | ARE IN NO WAY ALL ITEMS. PLEASE SEE COMMENTS FROM OTHER |
| | TRADES FOR THE SAME CHAPTER. |
| | |
| | 10) NOTE: PLEASE SUBMIT SITE LIGHTING PLANS. UNABLE TO |
| | REVIEW AT THIS TIME. |
| | NEC 2005, FBC CHAPTER 13 |
| | FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 FOR ADDITIONAL |
| | INFORMATION. |
| | |
| | 11) NOTE: PLEASE SUBMIT EMERGENCY EGRESS PHOTO-METRICS |
| | FOR ALL EGRESS PATHS INCLUDING ALL STAIR AREAS. PLEASE |
| | SEE 7.8.1.3, 7.9.2.2 AS THE LIGHTING LEVELS FOR STAIRS |
| | UNDER NORMAL CONDITIONS ARE REQUIRED AT 10FT CANDLES |
| | MINIMUM. |
| | PLEASE SEE THAT ALL REQUIRED EGRESS PATHS, MAIN |
| | ELECTRICAL ROOMS, ELEVATOR EQUIPMENT/MACHINE ROOMS ETC |
| | SHALL CONTAIN BATTERY BACK UP TYPE FIXTURES TO PROVIDE |
| | THE 1FT CANDLE MINIMUM FOR THE *EGRESS PATHS*. PLEASE |
| | SEE 7.8.1.2.2 AND 7.8.2. |
| | COULD NOT LOCATE FIXTURES ON FIXTURE LEGEND WITH THE |
| | REQUIRED BATTERY BACK UP. |
| | PHOTO-METRICS ARE REQUIRED AND AS NONE HAVE BEEN |
| | SUBMITTED AT THIS TIME NO REVIEW CAN BE DONE. FLORIDA |
| | ADMINISTRATIVE CODE 61G15-33.004 |
| | FBC 106.1.2 |
| | |
| | 12) NOTE: PLEASE PROVIDE GROUND RISE ON ONE-LINE SHEET |
| | OR OTHER SHEET PER 250.58. ALSO AS NOTED ABOVE WITH |
| | RESPECT TO THE GENERATOR AND SEPARATELY DERIVED SYSTEMS |
| | PER 250.20, 250.30. THE NOTE ON RISER SHEET FOR |
| | TRANSFORMER GROUND IS OK. |
| | |
| | 13) NOTE: PLEASE INDICATE COLOR CODING FOR THE 277/480V |
| | SYSTEM AS FOLLOWS. |
| | BROWN, PURPLE AND YELLOW. |
| | THIS LOCAL JURISDICTION EXISTINGWIRING SYSTEMS ARE AS |
| | NOTED ABOVE INCLUDING OTHER LOCAL JURISDICTIONS AS THE |
| | NEC DOES NOT PROVIDE COLOR CODING NEEDED FOR THESE |
| | VOLTAGES. THE ORANGE MARKING AS NOTED IN THE NEC IS FOR |
| | THE HIGH-LEG OF AN OPEN DELTA SYSTEM. |
| | 90.4 |
| | |
| | 14) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS ON THE PROPOSED UPS SYSTEM. PLEASE BE SURE |
| | DOCUMENTS CONTAIN A LISTING FROM A NRTL. (NATIONALLY |
| | RECOGNIZED TESTING LABORATORY). |
| | 110.3, 90.7. |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 15) NOTE: PLEASE SEE NOTE ONE E001 MENTIONS TO SEE E361 |
| | FOR DETAILS ON THE GENERATOR HOWEVER NO DETAILED |
| | SPECIFIC INFORMATION COULD BE LOCATED. |
| | PLEASE SEE OCTAGONAL NOTE #15 FOR EXAMPLE. |
| | PLEASE SEE OTHER SHEETS ON PLANS SUBMITTED CONTAIN |
| | OTHER NOTES IN BOXES AND OCTAGONAL NOTES HOWEVER THE |
| | NOTES DO NOT MATCH OR THE NOTE IS NOT ON ANY LEGEND OR |
| | DETAIL ON SHEET TO LOCATE INFORMATION. |
| | PLEASE SEE ONE EXAMPLE BESIDES ONE NOTED ABOVE: SHEET |
| | E210 NOTES 4 AND 6 WHICH ARE IN LISTED NOTED. ONLY ONE |
| | NOTE/ SQUARE BOX #6 WAS LOCATED ON SHEET, WHERE IS NOTE |
| | #4? |
| | OCTAGONAL NOTES ON E355, E14, E17, ??? |
| | ** PLEASE GO THROUGH ALL SHEETS AND UPDATE NOTES, ETC |
| | THIS NOTES ONLY SOME ITEMS. SOME OTHERS NOTED ABOVE WAS |
| | THE MISSING FIXTURE DESIGNATIONS OR NOTES/BOXES ETC FOR |
| | THE FIXTURES. |
| | |
| | 16) NOTE: PLEASE SEE THE ALARM DEVICE LOCATIONS AS |
| | NOTED ON PLANS SHEET E-210 MAKE NOTE TO SEE |
| | ARCHITECTURAL SHEETS FOR LOCATIONS AND DEVICE HEIGHTS. |
| | THIS REVIEWER COULD NOT READILY LOCATE THESE ON |
| | ARCHITECTURAL SHEETS. PLEASE PROVIDE DETAILED |
| | INFORMATION ON THE ELECTRICAL PLANS OR ADD DEVICES TO |
| | E-SHEETS. |
| | PLEASE PROVIDE A RESPONSE WHERE THESE ITEMS ARE |
| | LOCATED. |
| | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. |
| | SEE THE NEXT NOTE: |
| | |
| | 17) NOTE: PLEASE INCLUDE ALL MINIMUM LEVELS FOR FLORIDA |
| | ADA COMPLIANCE. |
| | PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) MORE |
| | SPECIFICALLY. THE LEVELS FOR ALL DEVICES TO MEET |
| | MINIMUM ADA LEVELS NEED TO BE NOTED ON PLANS AS WELL AS |
| | ADJUSTING THE DEVICES NOTED ON PLANS. |
| | FOR EXAMPLE: STROBES SHOWN AT LEVELS WAY BELOW THE |
| | MINIMUM LEVELS REQUIRED FOR ADA. (15CD ETC, WHEN |
| | REQUIRES TO BE 75CD MINIMUM). |
| | |
| | 18) NOTE: PLEASE SEE FBC 3006.2, .4 ETC AND POSSIBLE |
| | COMMENTS FROM OTHER TRADES. PLEASE KNOW THE ELEVATOR |
| | MACHINE ROOMS ARE REQUIRED MEETING INDIVIDUAL AIR |
| | CONDITIONING AS WELL AS VENTILATION REQUIREMENTS. |
| | PLEASE SEE NEC 620.21-620.25. AT THIS TIME THERE ARE |
| | ITEMS IN THESE ROOMS AND OTHER EQUIPMENT WHICH IS |
| | REQUIRED TO BE ON DEDICATED CIRCUITS YET THEY FEED |
| | OTHER AREAS. SEE THE FOLLOWING COMMENT WHICH DIRECTLY |
| | AFFECT THIS NOTE. |
| | PLEASE SEE FOR EXAMPLE: THE LIGHTING IN THE MACHINE |
| | ROOM IS REQUIRED TO BE ON A DEDICATE CIRCUIT YET PLANS |
| | SHOWS THIS SAME CIRCUIT FEEDING OTHER AREAS/ROOMS WHICH |
| | IS NOT PERMITTED. |
| | |
| | 19) NOTE: PLEASE SEE THE PLANS SHOWS CIRCUITS FOR MUCH |
| | OF THE EQUIPMENT FOR ESCALATOR AND ELEVATOR TO A Y1 |
| | PANEL YET NO Y PANEL COULD BE LOCATED IN PANEL |
| | SCHEDULES OR LOCATED ON RISER. WHAT IS THIS PANEL? NEC |
| | 240.4,310.16, 408, 620 ETC |
| | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 20) NOTE: PLEASE SEE 620.213 AND ASME A17.1-2004, |
| | SAFETY CODE FOR ELEVATORS AND ESCALATORS, REQUIRES A |
| | MINIMUM OF 5 FT-CANDLES (54 LUX) AT THE PIT FLOOR AND |
| | REQUIRES LUMINAIRES TO BE EXTERNALLY GUARDED TO PREVENT |
| | ACCIDENTAL BREAKAGE. |
| | PLEASE INCLUDE IN THE PHOTO-METRIC CALCULATIONS AS |
| | NEEDED ABOVE FOR EGRESS PATHS. MAY SUBMIT ONE AS |
| | TYPICAL FOR BOTH. |
| | |
| | 21) NOTE: PLEASE SUBMIT MORE DETAIL FOR THE RTCU |
| | CONTROL PANELS WHICH THE GFI RECEPTACLES FOR ROOFTOP |
| | EQUIPMENT IS BEING SHOWN. THESE ARE 277/480V UNITS, AND |
| | NOT CLEAR WHAT THESE PANELS ARE AT THIS TIME. PLEASE |
| | CLARIFY. |
| | |
| | 22) NOTE: PLEASE SEE ROOM LOCATED ON SHEET E131 WHICH |
| | IS TO THE LEFT AND DOWN FROM AREA/ROOM 122. THIS ROOM |
| | DOES NOT APPEAR TO SHOW ANY DOORS. |
| | FBC 106.1.2 |
| | |
| | 23) NOTE: PLEASE KNOW THE RATINGS OF THE MAIN |
| | ELECTRICAL ROOM 145 AND ELECTRICAL DISTRIBUTION ROOM |
| | 116 NEEDS TO BE VERIFIED. PLEASE KNOW AS FULL FIRE |
| | SPRINKLER PLANS WERE NOT SUBMITTED THE ROOM RATING |
| | NEEDS TO BE VERIFIED. |
| | THIS INFORMATION WILL BE GONE OVER WITH THE BUILDING |
| | REVIEWER WHEN BUILDING REVIEW IS DONE. COULD NOT |
| | READLIY LOCATE ON THE ARCHITECTURAL SHEETS THE RATING |
| | OF THESE ROOMS. |
| | MAY BE 3HRS OR AT THE LEAST 1HR. 450.42 |
| | WILL ALSO NEED MORE INFORMATION ON THE VENTILATION |
| | TAKING PLACE IN THESE ROOMS ONCE THE MECHANICAL REVIEW |
| | TAKES PLACE. |
| | PLEASE PROVIDE TEMPERATURE RISE AND EQUIPMENT HEATING |
| | WILL NEED TO BE GONE OVER. |
| | |
| | 24) NOTE: PLEASE SEE THE PANEL SCHEDULES NOTE A *HANDLE |
| | LOCK-OFF DEVICE* ON SOME ITEMS. PLEASE BE SURE TO |
| | VERIFY THE DEVICES BEING NOTED AS MANY OF THESE ITEMS |
| | ARE ONLY LISTED FOR TEMPORARY USE AND IF A DEVICE IS TO |
| | BE PERMANENTLY INSTALLED IN LIEU OF A REQUIRED |
| | DISCONNECT THE LOCK OFF DEVICE SHALL BE AN INTEGRAL |
| | PART OF THE BREAKER ASSEMBLY. |
| | PLEASE PROVIDE NOTE ACCORDINGLY AND PLEASE KNOW THIS |
| | WILL BE VERIFIED IN FIELD BY THE ELECTRICAL INSPECTOR |
| | AND FINAL DETERMINATION BY THE AHJ. |
| | 110.3, 90.4, 90.7. |
| | |
| | 25) NOTE: PLEASE SEE 210.8B2 INTHE 2005 NEC AS GFI |
| | PROTECTION IS REQUIRED FOR ALL 120V 15/20 AMP CIRCUITS |
| | IN KITCHENS. |
| | PLANS DO NOT SHOW PROTECTION, EQUIPMENT SCHEDULE DOES |
| | NOT SHOW PROTECTION AND COULD NOT LOCATE THE BREAKERS |
| | IN PANELS FOR REQUIRED PROTECTION. |
| | PLEASE PROVIDE AND ADJUST PLANS. |
| | |
| | 26) NOTE: PLEASE CLARIFY ACCESS TO THE EDR 116, WHICH |
| | APPEARS TO BE SHOWN THROUGH A ROOM 115. WHAT IS THIS |
| | ROOM 115? |
| | PLEASE SEE A351 WHICH INDICATES THE ROOM SHOWN AS 116 |
| | ON ELECTRICAL PLANS AS 129 ON A-SHEETS. PLEASE |
| | COORDINATE. |
| | **MAY NOT ACCESS THROUGH A STORAGE, OFFICE ROOM AS THIS |
| | CLEARLY WOULD INTERFERE WITH THE MEANS OF EGRESS |
| | PATHS. |
| | THIS MAY ALSO BE NOTED BY THE FIRE MARSHAL AND BUILDING |
| | REVIEWER(S). |
| | PLEASE CLARIFY. |
| | LS 101, NEC ACCESS TO ELECTRICAL ROOM 110.26, 240.24 |
| | |
| | 27) NOTE: PLEASE SEE KNOW THE CODE WILL REQUIRE A |
| | NEUTRAL CONDUCTOR TO THE FIRST MEANS OF DISCONNECT FOR |
| | EACH OF THE ATS DEVICES. RISER SHOWS (7) WITH 3W, WHICH |
| | LENDS TO NO NEUTRAL CONDUCTORS. PLEASE KNOW THAT |
| | WHETHER OR NOT THE UNIT IS SEPARATELY DERIVED THIS IS |
| | REQUIRED. |
| | 250.6, 250.24, 250.20 ETC |
| | |
| | 28) NOTE: PLEASE INDICATE THE SIZES OF BRANCH CIRCUIT |
| | CONDUCTORS ON THE PANEL SCHEDULES. AS THE VD |
| | CALCULATIONS HAVE NOT BEEN SUBMITTED AND THESE ARE NOT |
| | SHOWN AT THIS TIME ON PANEL SCHEDULES, UNABLE TO VERIFY |
| | ALL. |
| | 240.4, 310.16. |
| | FBC 106.1.2, 106.3.5.1.2FOR ADDITIONAL INFORMATION. |
| | |
| | 29) NOTE: PLEASE PROVIDE NOTES ON PLANS FOR REQUIRED |
| | SIGNAGE FOR ARC FLASH PROTECTION. 110.16 |
| | |
| | 30) NOTE: PLEASE INCLUDE DISCONNECTING MEANS FOR ALL |
| | FEEDERS FROM GENERATOR TO BUILDING. PLEASE SEE, |
| | 225.31-225.39, 700.12B6, 701.11B6, AND 702.11B6. PLEASE |
| | KNOW BASED ON NOT HAVING THE INFORMATION ON THE |
| | BREAKERS FOR THE GENERATOR, THE CODE REQUIRES THE MEANS |
| | OF DISCONNECT TO BE *WITHIN SIGHT* AND *READILY |
| | ACCESSIBLE*. PLEASE SEE NEC ART 100 FOR DEFINITIONS. |
| | PLEASE ALSO KNOW AS THERE MAY BE ZONING AND OTHER |
| | REQUIREMENTS WHICH MAY REQUIRED FENCING/WALLS/AND |
| | LANDSCAPING THE BREAKERS MAY NOT BE READILY ACCESSIBLE. |
| | PLEASE ALSO KNOW THAT BASED ON THE GENERATOR AND THE |
| | LOCATION OF THIS UNIT THESE MAY BE INSIDE A LOCKED |
| | ENCLOSURE. THIS BEING SAID SEPARATE DISCONNECTSWHICH |
| | ARE NOT REQUIRED TO CONTAIN OVER CURRENT PROTECTION |
| | WILL BE REQUIRED AT THE BUILDING OR IN CLOSE PROXIMITY |
| | TO BE DETERMINED BY THIS OFFICEAND THE FIRE MARSHAL. |
| | |
| | 31)NOTE: PLEASE KNOW ALTHOUGH NOT REQUIRED, A |
| | RESPONSE LETTER WILL BE HELPFUL IN THE FOLLOWING |
| | REVIEW. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2008-03-07 19:04:11 | 2008-03-07 19:04:11 |
| | |
| | REVIEW CONTINUED 3/7, IN PROGRESS TO CONTINUE 3/8, |
| | NOTES TO FOLLOW ONCE COMPLETED. |
| 2008-02-16 19:56:14 | 2008-02-16 19:56:14 |
| | |
| | REVIEW STOPPED,ELECTRICAL REVIEW WILL CONTINUE AFTER |
| | 2/29. PLANS WILL GO INTO *F* STATUS AT THAT TIME AND |
| | NOTES WILL BE POSTED ONCE REVIEW IS COMPLETED. |
| 2008-02-16 19:04:46 | 2008-02-16 19:04:46 |
| | |
| | ONE ROLL IN ELECTRICAL FOR REVIEW. |