| 2008-04-01 09:24:16 | BUILDING PLAN REVIEW |
| | PERMIT: 08020128 (PLAN REVIEW) |
| | ADD: 1760 PALM BEACH LAKES |
| | CONT: RYAN COMPANIES |
| | TEL: (621)677-7235 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP |
| | STEVEN J. FAUTSCH |
| | AR# 93674 |
| | |
| | ENGINEERING FIRM TRC WORLD WIDE ENGINEERING |
| | MARCUS O. UNTERWEGER |
| | PE#63860 |
| | |
| | BUILDING TYPE: I-B/ FULLY SPRINKLERED |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTS WEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS & |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| | IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION |
| | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. PLEASE CORRECT |
| | SHEET G001 BUILDING CODE INFORMATION. PLEASE NOTE THAT |
| | IF A PERMIT APPLICATION WILL NEED TO BE APPLIED FOR |
| | BEFORE OCT 1, 2008 TO LOCK THIS PROJECT IN UNDER THE |
| | 2004 FBC. OCT 1, 2008 THE 2007 FBC |
| | WILL GO INTO AFFECT. |
| | |
| | 2) FBC* 109.3.7 RESIDENT INSPECTOR. SUBMIT INSPECTOR |
| | RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA, |
| | DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM. A RESIDENT |
| | INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO |
| | ONE OR MORE OF THE FOLLOWING: |
| | XXX -BUILDINGS/ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | - ANY MAJOR STRUCTURAL ALTERATIONS |
| | - STRUCTURES IN WHICH THE CONCRETE |
| | DESIGN IS BASED ON COMPRESSIVE STRENGTH (F'C) IN EXCESS |
| | OF 3000 PSI |
| | - PILE DRIVING |
| | XXX - BUILDINGS OVER 20,000 SQ FT IN AREA |
| | - BUILDINGS OVER 2 STORIES IN HEIGHT |
| | - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS OF |
| | CONSTRUCTION |
| | |
| | 3) FBC* 109.3.7 SINCE A RESIDENT INSPECTOR WILL |
| | REQUIRED, THREE OF ALL DOCUMENTS (PLANS, REPORTS, |
| | SUBMITTALS AND PRODUCT APPROVALS) WILL BE REQUIRED FOR |
| | ISSUANCE OF THE PERMIT. |
| | |
| | 4) SOILS REPORTS 2 REPORTS WERE SUBMITTED, PLEASE |
| | SUBMIT THREE REPORTS WITH ORIGINAL SIGNATURES, NOT |
| | COPIES OR STAMPED SIGNATURES. 1802.2.1 QUESTIONABLE |
| | SOIL. WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| | DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT |
| | SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| | BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 5) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| | AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 6) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO |
| | THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 8) SHEET G001 THE BUILDING CODE INFORMATION : |
| | 8A) THE PLANS INDICATE THIS TO HAVE A S2 AND M |
| | OCCUPANCY PLEASE SEE CODE SECTIONS THAT WOULD CLASSIFY |
| | THIS AS A MIXED USE BUILDING, NOT THE NON-SEPARATED USE |
| | AS INDICATED IN YOUR CODE ANALYSIS. |
| | |
| | 406.2.7MIXED OCCUPANCIES. PARKING GARAGES SHALL BE |
| | SEPARATED FROM OTHER OCCUPANCIES IN ACCORDANCE WITH |
| | SECTION 302.3.2 . |
| | |
| | 406.3.4 PLEASE SEE ALLOWABLE MIXED USES ALLOWED IN THE |
| | SAME BUILDING AS A OPEN PARKING GARAGE.302.3 MIXED USE |
| | AND 508.7 A, B, M & R OCCUPANCIES. |
| | |
| | 302.3.2 SEPARATED USES. |
| | EACH PORTION OF THE BUILDING SHALL BE INDIVIDUALLY |
| | CLASSIFIED AS TO USE AND SHALL BE COMPLETELY SEPARATED |
| | FROM ADJACENT AREAS BY FIRE BARRIER WALLS OR HORIZONTAL |
| | ASSEMBLIES OR BOTH HAVING A FIRE-RESISTANCE RATING |
| | DETERMINED IN ACCORDANCE WITH TABLE 302.3.2 FOR USES |
| | BEING SEPARATED. EACH FIRE AREA SHALL COMPLY WITH THIS |
| | CODE BASED ON THE USE OF THAT SPACE. EACH FIRE AREA |
| | SHALL COMPLY WITH THE HEIGHT LIMITATIONS BASED ON THE |
| | USE OF THAT SPACE AND THE TYPE OF CONSTRUCTION |
| | CLASSIFICATION. IN EACH STORY, THE BUILDING AREA SHALL |
| | BE SUCH THAT THE SUM OF THE RATIOS OF THE FLOOR AREA OF |
| | EACH USE DIVIDED BY THE ALLOWABLE AREA FOR EACH USE |
| | SHALL NOT EXCEED ONE. |
| | |
| | TABLE 302.3.2 WILL REQUIRE A 2HR RATING BETWEEN THE S2 |
| | AND MERCANTILE OCCUPANCIES. |
| | ALSO SEE SECTION 508.7.1 FIRE SEPARATION. |
| | |
| | 508.7.1 FIRE SEPARATION |
| | FIRE SEPARATION ASSEMBLIES BETWEEN THE PARKING |
| | OCCUPANCY AND THE UPPER OCCUPANCY SHALL CORRESPOND TO |
| | THE REQUIRED FIRE-RESISTANCE RATING PRESCRIBED IN TABLE |
| | 302.3.2 FOR THE USES INVOLVED. THE TYPE OF CONSTRUCTION |
| | SHALL APPLY TO EACH OCCUPANCY INDIVIDUALLY, EXCEPT THAT |
| | STRUCTURAL MEMBERS, INCLUDING MAIN BRACING WITHIN THE |
| | OPEN PARKING STRUCTURE, WHICH IS NECESSARY TO SUPPORT |
| | THE UPPER OCCUPANCY, SHALL BE PROTECTED WITH THE MORE |
| | RESTRICTIVE FIRE-RESISTANCE-RATED ASSEMBLIES OF THE |
| | GROUPS INVOLVED AS SHOWN IN TABLE 601 . MEANS OF EGRESS |
| | FOR THE UPPER OCCUPANCY SHALL CONFORM TO CHAPTER 10 AND |
| | SHALL BE SEPARATED FROM THE PARKING OCCUPANCY BY FIRE |
| | BARRIERS HAVING AT LEAST A 2-HOUR FIRE-RESISTANCE |
| | RATING AS REQUIRED BY SECTION 706 , WITH SELF-CLOSING |
| | DOORS COMPLYING WITH SECTION 715 . MEANS OF EGRESS FROM |
| | THE OPEN PARKING GARAGE SHALL COMPLY WITH SECTION 406.3 |
| | (OPEN PARKING GARAGES) . |
| | |
| | NOTE PLEASE SEE 2004 FBC CODE COMMENTARY FOR SECTION |
| | 508.7.1. THIS SECTION CONTAINS ADDITIONAL CONDITIONS |
| | FOR THE USE OF 508.7 AS AN ALTERNATIVE TO THE GENERAL |
| | MIXED-USE PROVISIONS IN SECTION 302.3. IT CONTAINS AN |
| | ADDITIONAL FIVE CRITERIA. |
| | |
| | 8B) SHEET G001 BUILDING CODE INFO ALSO INDICATES THIS |
| | TO BE A OPEN PARKING GARAGE PLEASE PROVIDE OPENING |
| | CALCULATIONS MEETING THE REQUIREMENTS OF 406.3.3.1. |
| | ALSO SEE EXCEPTION. |
| | IN ADDITION TO THIS REQUIREMENT PLEASE SEE ALLOWABLE |
| | OPENINGS IN TABLE 704.8. PLANS INDICATE WALLS WITH LESS |
| | THAN 10?-0? FROM THE PROPERTY LINE, PLEASE PROVIDE |
| | OPENING CALCULATIONS FOR EXTERIOR WALLS. |
| | |
| | 8C) PLANS INDICATE WALLS WITHIN 10?-0? OF THE PROPERTY |
| | LINE THE CODE ANALYSIS DOES |
| | NOT PROVIDE THE ALLOWABLE OPENINGS MENTIONED ABOVE( |
| | TABLE 704.8) NOR THE RATING OF THE BUILDING ELEMENTS |
| | THAT ARE LISTED IN TABLE 601, PLEASE PROVIDE THE HOURLY |
| | RATING REQUIRED, THE BUILDING ELEMENTS FIRE RATING CAN |
| | BE TAKEN FROM TABLE 720.1 AND FOR COLUMNS AND BEAMS |
| | TABLE 721.3.4 & TABLE 721.3.5. |
| | |
| | 9) SHEET G001 INDICATES IN A NOTE SEE SHEET A001 FOR |
| | THE FLORIDA PRODUCT APPROVALS. |
| | THE INSPECTORS CAN NOT COMPLETE THEIR INSPECTIONS |
| | WITHOUT THE ACTUAL PRODUCT APPROVALS. WE AS PLAN |
| | REVIEWERS ALSO CAN NOT EVEN START OUR PORTION OF THE |
| | REVIEW UNTIL THE FLORIDA COVERSHEETS AND THE ASSOCIATED |
| | REPORT AND TECHNICAL SHEETS ARE PROVIDED. |
| | GLAZED OPENINGS: IN MANY CASES THE FLORIDA COVERSHEET |
| | MAY LIST MULTIPLE SERIES OF WINDOWS UNDER A SINGLE |
| | REPORT AND OR IN A SINGLE REPORT THEIR MAY HAVE |
| | MULTIPLE OPTIONS |
| | TO GLAZING IN THICKNESS AND TYPE OF LAMINATIONS TO |
| | CREATE LAMINATED GLAZING UNITS WITH LARGE MISSILE |
| | IMPACT TESTING. UNTIL THE CONTRACTOR OR DESIGNER |
| | INDICATES WHICH OF THESE |
| | OPTIONS ARE TO BE INSTALLED WE CAN NOT DETERMINE CODE |
| | COMPLIANCE FOR THE PRODUCT. |
| | PLEASE SUPPLY THREE SETS OF PRODUCT APPROVALS WITH IN |
| | BINDERS INDENTIFYING EACH OF THE |
| | PRODUCTS. 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 10A) SHEET G001 NOTES FOR PRODUCT APPROVALS NOTE THERE |
| | MAY NO FLORIDA AND MIAMI-DADE APPROVALS FOR ROOF |
| | HATCHES BUT THERE IS A LOCAL PRODUCT APPROVAL UNDER |
| | AHJ, AUTHORITY HAVING JURISDICTION, THE CITY OF WEST |
| | PALM BEACH DOES HAVE A LOCAL APPROVAL FOR THE NYSTORM |
| | RHG3630T ROOF SCUTTLE, A COPY WILL BE ATTACHED. |
| | |
| | 10B) PLEASE SEE SHEET A020 EXIT WIDTH ANALYSIS, PLEASE |
| | CORRECT THE CODE TO THE 2004 FBC W/ 2007 SUPPLEMENTS. |
| | |
| | |
| | 11) NOTE, IT APPEARS THAT THE EXIT WIDTH ANALYSIS AND |
| | THE EXIT WIDTH DOOR & STAIR KEY FOUND ON A021 INDICATE |
| | A OVERAGE OF 96 OCCUPANTS OUR CALCULATIONS INDICATE A |
| | SHORTAGE OF -34 OCCUPANTS, IN EITHER CASE THE PLANS |
| | WILL NEED TO MEET THE MINIMUM CODE REQUIREMENTS FOR |
| | WIDTH REQUIREMENTS. |
| | I WILL EXPLAIN THE AREAS WHERE I BELIEVE WE MAY HAVE A |
| | DIFFERENCE IN OUR FIGURES, AND THERE MAY BE LESS SEVERE |
| | ISSUES THAT WILL NEED TO BE ADDRESSED. |
| | |
| | 11A) A-305 STAIR- A THE STAIR WIDTH IS INDICATED AS |
| | 4?-6? BUT THE INTERMEDIATE OR MID- LANDING IS ONLY |
| | 4?-0? IN DEPTH. PLEASE SEE 1009.4THE MINIMUM DIMENSION |
| | MEASURED IN THE DIRECTION OF TRAVEL IS TO BE EQUAL TO |
| | THE WIDTH OF THE STAIRWAY. THIS IS AN ISSUE THAT WE SEE |
| | ON ALL OF THE STAIRS. |
| | |
| | 11B) STAIRWAY A & ESCALATORS DO NOT MEET THE SHAFT |
| | ENCLOSURES AND THE EXCEPTIONS FOUND IN 707.2 EXCEPTION |
| | 2, THE STAIR A WOULD NOT BE PART OF THE EGRESS |
| | CALCULATION & PROTECTED ACCORDING TO ITEMS 2.1 AND 2.2. |
| | PLEASE PROVIDE ADDITIONAL INFORMATION FOR CODE |
| | COMPLIANCE. |
| | |
| | 11C) IF THE 2ND FLOOR IS TO BE LEFT OPEN TO THE STAIR-A |
| | PLEASE REVIEW 404 ATRIUM REQUIREMENTS |
| | AND 404.5 ENCLOSURE OF ATRIUMS AS WELL AS POSSIBLE |
| | 404.4 SMOKE CONTROL. |
| | |
| | 11D) THIS IS A COMMENT THAT MAY OR MAY NOT APPLY TO |
| | THIS STAIRWELL DEPENDING ON THE REVISIONS TO THE PLAN, |
| | THIS COMMENT DOES PERTAIN TO OTHER STAIRWELLS SO IN |
| | CONSIDERATION TO THE CONCEPT CHANGES I WOULD BRING THIS |
| | ISSUE TO VIEW. PLEASE SEE 1019.1.4 WHERE NON-RATED |
| | WALLS OR UNPROTECTED OPENINGS ENCLOSE THE EXTERIOR OF |
| | THE STAIRWAY AND THE WALLS OR OPENINGS ARE EXPOSED BY |
| | OTHER PARTS OF THE BUILDING AT AN ANGLE LESS THAN 180 |
| | DEGREES, THE BUILDING EXTERIOR WALLS WITHIN 10 FT |
| | HORIZONTALLY OF A NONRATED WALL OR OPENING SHALL BE |
| | CONSTRUCTED AS REQUIRED FOR A MINIMUM 1-HOUR FIRE |
| | RESISTANCE WITH ? HOUR OPENING PROTECTIVES. SEE CODE |
| | COMMENTARY. |
| | |
| | 11E) STAIRWELL B THERE ARE UNKNOWNS BUT ASSUMPTIONS AS |
| | TO DOORS IN THE DOOR SCHEDULE, |
| | SEE SHEET A611 DOOR NUMBERS 071.1- 074.2 THESE DOOR |
| | WIDTHS ARE NOT GIVEN. THE 4 DOORS AT THE TOP OF THE |
| | STAIRS DO NOT PROVIDE DOOR INFORMATION, AND THE DOORS |
| | AT THE BOTTOM OF THE |
| | STAIRS ARE GIVEN AS ROUGH OPENINGS NOT CLEAR OPENING. |
| | PLEASE PROVIDE ADDITIONAL INFORMATION SO A REVIEW OF |
| | THIS EXIT CAN BE ACCOMPLISHED. 106.1.2*. |
| | |
| | 11F) THERE MAY BE A BIT OF CONVERGENCE FROM THE 4 DOORS |
| | AT THE TOP STAIRS AND STAIRS, THIS IS A UNKNOWN UNTIL |
| | THE DOOR WIDTHS CAN BE DETERMINED |
| | |
| | 11G) THE MID-LANDING, PLEASE SEE 1009.4THE MINIMUM |
| | DIMENSION MEASURED IN THE DIRECTION OF TRAVEL IS TO BE |
| | EQUAL TO THE WIDTH OF THE STAIRWAY. THIS IS AN ISSUE |
| | THAT WE SEE ON ALL OF THE STAIRS. |
| | |
| | 11H) FOR STAIRS B,C & D ALL OF THESE STAIRS WE AGREE |
| | WITH THE DESIGNER AT 600 OCCUPANT LOAD FOR EACH |
| | STAIRWELL. ISSUES WITH THESE STAIRS WILL BE THE |
| | MID-LANDING 1009.4 AND 1019.1.4 WHERE NON-RATED WALLS |
| | OR UNPROTECTED OPENINGS ENCLOSE THE EXTERIOR OF THE |
| | STAIRWAY AND THE WALLS OR OPENINGS ARE EXPOSED BY OTHER |
| | PARTS OF THE BUILDING AT AN ANGLE LESS THAN 180 |
| | DEGREES, THE BUILDING EXTERIOR WALLS WITHIN 10 FT |
| | HORIZONTALLY OF A NONRATED WALL OR OPENING SHALL BE |
| | CONSTRUCTED AS REQUIRED FOR A MINIMUM 1-HOUR FIRE |
| | RESISTANCE WITH ? HOUR OPENING PROTECTION. SEE CODE |
| | COMMENTARY. |
| | |
| | 11I) STAIR E MID-LANDING, , PLEASE SEE 1009.4THE |
| | MINIMUM DIMENSION MEASURED IN THE DIRECTION OF TRAVEL |
| | IS TO BE EQUAL TO THE WIDTH OF THE STAIRWAY. THIS IS AN |
| | ISSUE THAT WE SEE ON ALL OF THE STAIRS. |
| | |
| | 11J) STAIR E SEE THE BOTTOM SET OF DOORS THE WIDTH OF |
| | THE DOOR IS NOT ON THE DOOR SCHEDULE FOR DOOR NUMBER |
| | 074.1 & 07.42. ADDITIONAL INFORMATION |
| | REQUIRED.106.1.2*. |
| | |
| | 11K) STAIR F, THE ISSUE WITH THIS STAIR IS THE WIDTH OF |
| | THE STAIR VERSES HAND RAILS. SEE 1009.11.2 HANDRAILS |
| | SHALL BE PROVIDED WITHIN 30 INCHES OF ALL PORTIONS OF |
| | THE STAIR WIDTH REQUIRED FOR EGRESS CAPACITY IN |
| | ACCORDANCE WITH TABLE 1005.1 . |
| | SHEET A021 INDICATES THE USE OF ONLY (1) HANDRAIL WHICH |
| | IN ACTUALITY ONLY A 10?-0? WIDE STAIR AND OCCUPANT LOAD |
| | OF 400 NOT THE 540 AS INDICATED IN THE PLAN MULTIPLE |
| | HANDRAILS WOULD BE NEEDED TO ACCOMMODATE AND ACHIEVE |
| | THE 540 OCCUPANT LOAD FOR THIS STAIR. THIS IS THE |
| | STAIRWAY THAT CURRENTLY LOOSES 140 OF THE OCCUPANTS AS |
| | DESIGNED BY NOT HAVING MORE INTERMEDIATE HANDRAILS. |
| | |
| | 12A) A021 REFERS TO DETAIL#2 SHEET A331 THIS SECTION OR |
| | DETAIL REFERENCES DETAIL 20 ON SHEET A231. IT APPEARS |
| | TO BE AN EXPANSION JOINT IN THE FLOOR BUT THERE IS NO |
| | INFORMATION THAT I CAN FIND ON THE FIREPROOFING |
| | REQUIREMENTS TABLE 601 FOR FLOOR SYSTEMS AND OCCUPANCY |
| | TYPE SEPARATION TABLE 302.3.2.PLEASE PROVIDE FLOOR |
| | CEILING TYPE PENETRATIONS FOR PIPES AND CONDUITS AS |
| | WELL AS FOR ANY HORIZONTAL PENETRATION OF RATED FLOOR/ |
| | CEILING ASSEMBLY. |
| | SEE 711.3.& 712.3.1. |
| | |
| | 12B) SHEET A331 INDICATES DETAIL 2 THE RIGHT UPPER |
| | PORTION INDICATES A CIRCULATION AREA THAT LEADS IN TO |
| | STAIRWELL D, THE WALL TYPE IS P5 THIS WALL TYPE |
| | INDICATES A FINISH ON ONE SIDE. SHEET A601 PARTITION |
| | TYPES INDICATES THE USE OF PLYWOOD ON OR WITHIN MANY |
| | PARTITIONS. PLEASE SEE 603.1(1.1) FIRE RETARDANT |
| | TREATED WOOD SHALL BE PERMITTED IN: |
| | 1.1 NONBEARING PARTITIONS WHERE THE REQUIRED FIRE |
| | RESISTANCE RATING IS LESS THAN TWO HOURS OR LESS. |
| | |
| | 603.21 MATERIALS ALLOWED IN CONCEALED SPACES OF |
| | BUILDINGS OF TYPE I AND II CONSTRUCTION IN ACCORDANCE |
| | WITH SECTION 717.5. PLEASE UPDATE TO FIRE RETARDANT |
| | TREATED PLYWOOD. |
| | |
| | 13) SHEET A110 INDICATES THE DISABLED PARKING SPACES |
| | AND ACCESS AISLES BUT NOT THE ELEVATION CHANGES OF THE |
| | PARKING LOT VERSES DISABLED SPACES AND ACCESS AISLES. |
| | THE OTHER ISSUE IS NO INFORMATION FOR DETECTABLE |
| | WARNING AT HAZARDOUS VEHICULAR AREAS 11-4.29.5. |
| | |
| | 14) SHEET A110 PLEASE PROVIDE INFORMATION ON VAN |
| | ACCESSIBILITY, 11-4.6.5 VERTICAL CLEARANCE. |
| | A) 114? TO VEHICLE ACCESS ROUTE FROM SITE ENTRANCE TO |
| | EXIT & PASSENGER LOADING ZONES |
| | ALSO SEE 11-4.6.6. |
| | B) 98? MINIMUM AT PARKING ZONE. |
| | C) SIGNAGE 11-4.6.4 |
| | |
| | 15) PLEASE PROVIDE COMPLIANCE WITH 11-4.1.3(8)(A) AND |
| | SECTION 11-4.1.3(8)(B) AND SHALL BE SATISFIED |
| | INDEPENDENTLY.. |
| | |
| | 16) SHEET A301 DETAIL 1 INDICATES THE USE OF A FOOD |
| | SERVICE AREA THE PLANS INDICATE A AREA FOR 50 FOR |
| | SEATING, PLEASE COMPLY WITH 11-5.1 INDICATING THE AREA |
| | OF 5 % DISABLED PERSONS. |
| | |
| | 17) PLEASE PROVIDE SECTIONS FOR COUNTERS AND BARS TO |
| | INDICATE COMPLIANCE WITH 11-5.2, |
| | 11-5.5 & 11-5.6 A303 DETAIL 2 INDICATES A 3?-0? COUNTER |
| | HEIGHT.. |
| | |
| | 18) A311 ROOM TRAINING/ LOUNGE IS 2448 SQ FT APPROX / |
| | 15 = 163 OCCUPANT LOAD, THIS IS AN ASSEMBLY AREA |
| | REQUIRING 1 HR RATED WALLS AND OPENING PROTECTIVES. SEE |
| | TABLE 1004.1.2,THIS WILL BE CLASSIFIED AS A A2 |
| | OCCUPANCY OCCUPANT LOAD > THAN 50. SEE TABLE 1016.1 |
| | ASSEMBLY LOADS> THAN 30 WITH FIRE SPRINKLERS WILL STILL |
| | REQUIRE 1 HR RATING. PLEASE CORRECT WALL TYPES AND |
| | OPENING PROTECTIVES. TABLE 715.3. SEE CORRIDOR 118 DOES |
| | NOT INDICATE A FIRE RESISTANCE RATING. |
| | |
| | 19) SHEET A311 FAMILY RESTROOM 107, REST ROOMS 108, 109 |
| | AND 131 DO NOT INDICATE AN UNOBSTRUCTED TURNING SPACE |
| | AS REQUIRED IN 11-4.22.3. THE ACCESSIBLE STALLS IN |
| | RESTROOM |
| | 108 & 109 DO NOT PROVIDE THE WIDTH DIMENSION SEE FIGURE |
| | 30(A) STANDARD STALL A MINIMUM OF 60? CLEAR. |
| | |
| | 20) SHEET A351 & A352 BOTH INDICATE AN ELECTRICAL |
| | DISTRIBUTION CENTER THAT DOES NOT HAVE A CODE COMPLIANT |
| | STAIR. THE CODE DOES ALLOW FOR FIXED LADDERS AS PART OF |
| | A MEANS OF EGRESS IN THE FOLLOWING LOCATIONS: FOR |
| | BOILERS (1014.3), REFRIGERATION ROOM (1014.4), STAGE |
| | EXITS 410.5.4, 1014.6.6.1 GALLERY, GRIDIRONS AND |
| | CATWALKS THAT ARE ASSOCIATED WITH STAGES |
| | AND HELISTOPS (1018.1.2.). PLEASE PROVIDE A CODE |
| | COMPLIANT STAIRWAY. SEE 1014.1 & TABLE 1014.1. |
| | |
| | 21) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE |
| | ELECTRICAL DISTRIBUTION CENTER, PRE-MANUFACTURED? TYPE |
| | OF MATERIAL, FIRE RATINGS ETC? NFPA 13.8.14.10. |
| | |
| | 22)THE WALLS OR SHAFT WHERE THE CURRENT SHIPS LADDER IS |
| | LOCATED HAS A 2 HR FIRE RATING BUT THERE ARE NO WALL |
| | RATINGS FOR THE WALLS SURROUNDING THE EDC. 106.1.2. |
| | ADDITIONAL INFORMATION REQUIRED. THIS WOULD APPEAR TO |
| | BE PART OF THE SHAFT WALL CONSTRUCTION BUT THERE ARE NO |
| | WALL IDENTIFICATION TAGS. |
| | |
| | 23) THE SAME SHEETS IDENTIFY ANOTHER SHIPS LADDER WHICH |
| | RISES TO THE ROOF LEVEL WITH A |
| | ROOF HATCH. NOTE THIS WILL BE A PRODUCT THAT WILL |
| | REQUIRE A FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA.. |
| | NOTE CURRENTLY NEITHER THE STATE NOR MIAMI-DADE |
| | CURRENTLY HAVE A LISTING. THE CITY OF WPB DOES HAVE A |
| | LOCAL APPROVAL FOR A NYSTROM RHG3630T ROOF HATCH. A |
| | COPY WILL BE ATTACHED. |
| | |
| | 24) SHEET A361 MAIN ELECTRIC CENTER PLEASE PROVIDE |
| | ADDITIONAL INFORMATION ON THE ELECTRICAL DISTRIBUTION |
| | CENTER, PRE-MANUFACTURED? TYPE OF MATERIAL, FIRE |
| | RATINGS ETC? NFPA 13.8.14.10. |
| | |
| | 25) SHEET A361 ALSO INDICATES THERE TO BE A GENERATOR, |
| | PLEASE PROVIDE THE SIZE OF GENERATOR AND PROVIDE |
| | ANCHORAGE DETAILS 1609. 1.3 ANCHORAGE AGAINST MOMENT OF |
| | OVERTURNING, SLIDING AND UPLIFT. |
| | |
| | 26) PLEASE PROVIDE THE AMOUNT OF PROPANE AND TYPE OF |
| | TANKS TO BE USED. PLANS INDICATE SEE MECHANICAL PLANS |
| | FOR ATTACHMENT, M-111 INDICATES THE GENERATOR AND TANKS |
| | IN A DIFFERENT LOCATION. 106.1.2*. ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 27) S001 DESIGN CODES, PLEASE UPDATE THE 2004 FBC AND |
| | SUPPLEMENTS TO THE 2007 SUPPLEMENTS. NOTE IF THIS MAJOR |
| | WORKING DRAWING REVIEW IS NOT SUBMITTED AS A PERMIT |
| | BEFORE OCT.1, 2008 IT WILL NEED TO BE RE-REVIEWED UNDER |
| | THE 2007 FBC. |
| | |
| | 28)) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR |
| | OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | |
| | 28A) WINDOWS: CURTAIN-WALL |
| | ****************************************************** |
| | * **************** |
| | NOTE: THE FOLLOWING SYSTEMS LISTED BELOW, HAVE NOT |
| | PROVIDED THE FLORIDA COVERSHEET THAT |
| | PROVIDES ADDITIONAL INFORMATION NOT LISTED IN THE TEST |
| | REPORT. |
| | |
| | THE SECOND ISSUE WITH THE NOA?S ARE THEY WERE TESTED |
| | BEFORE THE 2004 FBC WENT INTO EFFECT. BEFORE THIS DATE |
| | STEEL INCREASES OF 1 1/3 WERE COMMON PLACE AND TAKEN |
| | WITH FASTENERS, A P.E. SHOULD REVIEW THE TEST REPORT |
| | INFORMATION TO SEE IF THE INCREASES WERE TAKEN. THE |
| | NEWER MIAMI-DADE NOA?S THAT WERE RENEWED AFTER THE 2004 |
| | FBC WENT INTO EFFECT WILL STATE UNDER THE HEADING (3) |
| | CALCULATIONS, ANCHOR VERIFICATION VERIFIED TO THE 2004 |
| | FBC- NO STEEL INCREASES TAKEN. |
| | 1605.3.1.1 LOAD REDUCTION. |
| | 1. IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT OF |
| | TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE EFFECT |
| | OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN SHALL |
| | NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD LOAD AND |
| | ANY OF THE VARIABLE LOADS. |
| | 2. INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE |
| | MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED |
| | STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD |
| | COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD |
| | INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER |
| | 23 . |
| | EXCEPTION: INCREASES IN ALLOWABLE STRESS SHALL BE |
| | PERMITTED IN ACCORDANCE WITH ACI 530/ASCE 5/TMS 402 |
| | PROVIDED THE LOAD REDUCTION OF SECTION 1605.3.1.1 ITEM |
| | 1 SHALL NOT BE APPLIED. |
| | 3. SIMULTANEOUS USE OF BOTH ONE-THIRD INCREASE IN |
| | ALLOWABLE STRESS AND THE 25-PERCENT REDUCTION IN |
| | COMBINED LOADS SHALL NOT BE PERMITTED. |
| | |
| | 28B) WINDOWS: STOREFRONT |
| | 28C) AUTOMATIC BYPASS DOOR PEDESTRIANS AND CARTS 28D) |
| | EXTERIOR GLAZED SWING DOORS |
| | 28E) EXTERIOR HOLLOW METAL DOORS SINGLE AND PAIRS 28F) |
| | EXTERIOR COIL DOORS/ SECTIONAL DOORS |
| | 28G) FASCIA SYSTEMS |
| | 28H) EFIS WALL SYSTEMS |
| | 28I) ROOFING SYSTEMS W/ INSULATION- ONLY A DRIP EDGE |
| | REPORT SUBMITTED, NO REPORT FOR FLAT |
| | DECK |
| | 28J) ROOF HATCH- SEE ATTACHMENT |
| | |
| | |
| | *******THE CITY REQUEST THE FLORIDA COVER SHEETS ***** |
| | |
| | 29) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 30) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 31) THE CODE ANALYSIS INDICATES THIS TO BE A TYPE I-B |
| | BUILDING REQUIRING FIRE RATINGS OF THE |
| | STRUCTURAL STEEL AND BAR JOIST, PLEASE PROVIDE THE |
| | MANUFACTURERS SPEC AND THE THICKNESS REQUIRED TO |
| | ACHIEVE THE REQUIRED FIRE RATING. |
| | |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |