Plan Review Notes
Plan Review Notes For Permit 08020119
Permit Number 08020119
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-02-07 15:57:111. THE EXISTING FIRE DEPARTMENT CONNECTIONS LOCATED ON
 THE EXISTING RISER MUST PROPERLY SWIVEL AND BE EQUIPPED
 WITH PROTECTIVE CAPS.
  
 2. THE NEW FIRE SPRINKLER HEAD INSTALLATION TO COMPLY
 WITH NFPA 13.
  
 3. THE ENTIRE EXISTING FIRE SPRINKLER SYSTEM IS TO MEET
 MINIMUM CODE REQUIREMENTS AS A RECENT INSPECTION REPORT
 FOR THE SYSTEM DECLARED DEFICIENICES.
  
 4. A SPARE HEAD BOX WITH APPROPRIATE STYLE FIRE
 SPRINKLERS ALONG WITH A WRENCH SHALL BE PROVIDED.
  
 5. ANY FIRE SPRINKLER SYSTEM DEFICIENCIES DISCOVERED
 DURING THE NEW INSTALLATION OF FIRE SPRINKLER HEADS
 MUST BE REPAIRED.
  
 6. WHEN THE NEW REPAIRS ARE COMPLETE, THE FIRE
 SPRINKLER SYSTEM SHALL PROVIDE THE PROTECTION FOR WHICH
 IT WAS INTENDED.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX