Plan Review Notes
Plan Review Notes For Permit 08020108
Permit Number 08020108
Review Stop M
Sequence Number 2
Notes
Date Text
2008-03-28 08:43:14*** PROVISO ***
 1) UNWANTED FIRE DAMPERS AT THE SMOKE PARTITIONS WILL
 NEED TO BE REMOVED AND NOT LOCKED OPEN, PER 2004 FBC/M
 607.2.
  
 2) AFTER REMOVING UNWANTED FIRE DAMPERS AND REPLACING
 THE DUCT SECTION SEAL AROUND PENETRATIONS TO PREVENT
 FREE PASSAGE OF SMOKE, PER 2004 FBC 710.6.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]