Plan Review Notes
Plan Review Notes For Permit 08020108
Permit Number 08020108
Review Stop E
Sequence Number 2
Notes
Date Text
2008-03-27 08:37:04** DENIED2ND REVIEW**
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH SPECIFICALLY
 REQUESTED LIGHTING PERFORMANCE CALCULATIONS PER FBC
 13-415.2.
 PLEASE SEE THE PREVIOUS REVIEW NOTES ALSO NOTED THIS
 PROJECT IS UNDER THE 2004 FBC W/2007 REVISIONS.
 PLEASE SEE THERE IS NOW A NEW FORM 400D-01 SUBMITTED IN
 RESPONSE TO PREVIOUS COMMENT HOWEVER THIS 400D -01 IS
 FROM THE 2001 FBC WHICH IS NO LONGER IN ADOPTION.
 THE RESPONSE LETTER EVEN STATES THE FORM 400D FROM FBC
 CHAPTER 13 WILL BE SUBMITTED. PLEASE VERIFY CODE.
 PLEASE SEE THE ADOPTION OF THE 2004 FBC WAS OCTOBER
 1ST, 2005.HOW IS IT POSSIBLE THAT FORM D WHICH IS
 FROM THE 2001 FBC IS BEING FILLED OUT, SIGNED DATED AND
 SEALED BY THE ENGINEER OF RECORD WHEN THE CODE CHANGED
 ALMOST THREE YEARS AGO?
 ONE COPY OF THE SUBMITTED CALCULATIONS ARE BEING
 RETAINED BY THIS OFFICE.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.1 ETC.
 ** THIS 2004 FBC WAS REVISED THREE TIMES WITH
 SUPPLEMENTS SINCE ITS ADOPTION IN OCT 05.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH SPECIFICALLY
 REQUESTED TO STATE MINIMUM RELEVANT CODES ON PLANS.
 THE RESPONSE WAS THIS WAS DONE IN DIVISION SPECS,
 HOWEVER DIVISION SPECS ARE NOT PART OF THE RECORD PLANS
 OR DOCUMENTS SIGNED, DATED OR SEAL BY THE DESIGN
 PROFESSIONAL.
 AS STATED ON PREVIOUS REVIEW PLEASE BE SURE ELECTRICAL
 PLANS CONTAIN THE RELEVANT CODES.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NPFA-101
 2002 NFPA-72
 2002 NFPA-99
  
 ** PLEASE SEE THAT NOT ALL CODES REFLECTED ON THE
 DIVISION SPEC SHEET ARE CURRENT ADOPTED STANDARDS.
 PLEASE LIST THE ABOVE ON PLANS.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WHICH GAVE
 SOME EXAMPLES OF OVER CURRENT PROTECTION WHICH IS SHOWN
 TOO HIGH FOR THE TRANSFORMERS AS SHOWN ON RISER. PLEASE
 SEE FOR EXAMPLE THE OCP FOR TRANSFORMERS FROM GHC TO
 TXRL3 WHICH IS A 25KVA UNIT WITH 100AMP OCP AND TGLC
 WHICH IS 30KVA UNIT WITH 80A OCP.
 PLEASE SEE THESE DO NOT CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE GHC.
 PLEASE SEE 450.3, 240.4, AND 310.16 ETC AND COORDINATE
 ALL ON RISER WITH PANELS AND MINIMUM CODE REQUIREMENTS.
 THE ABOVE ARE GIVEN AS EXAMPLES AS DONE ON PREVIOUS
 REVIEW AND THIS OFFICE IS NOT LISTING ALL POSSIBLE.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH
 RESPECT TO MINIMUM ADA LEVELS FOR DEVICES TO BE STATED
 ON PLANS. RESPONSE MENTIONS THIS IS DONE IN DIVISION
 SPECS. THIS IS NOT ACCEPTABLE AS THE RECORD SET OF
 PLANS ARE REQUIRED TO CONTAIN THE *MINIMUM* LEVELS
 ALONG WITH * MINIMUM* DESIGN. 11-4.28.1,.2,.3(4).
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]