| 2008-04-24 13:25:53 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1-5. ADDRESSED. |
| | |
| | 4.FIRST REVIEW; AL2.1, OCCUPANT LOAD IS DECLARED |
| | BASED ON 240SF/OCCUPANT.SEE FBC TABLE 1004.1.2, |
| | CLARIFY USE OF THIS AREA.IS THIS AN EMERGENCY ROOM OR |
| | AN INPATIENT TREATMENT AREA?THE AREA IS LABELED |
| | PEDIATRIC ED AND HAS AN AMBULANCE PORTE COCHERE |
| | OUTSIDE.PLEASE REVISE OCCUPANT LOAD AND RELATED |
| | REQUIREMENTS. |
| | |
| | SECOND REVIEW; MY APOLOGIES IF MY COMMENT WAS NOT |
| | CLEAR.SEE FBC TABLE 1004.1.2, OUTPATIENT AREAS |
| | REQUIRE 100SF/PERSON.ISN'T AN EMERGENCY DEPARTMENT |
| | PRIMARILY OUTPATIENT?OTHER AREAS WERE REVISED AS |
| | "SLEEPING" WITH AN OCCUPANT LOAD OF 120.INPATIENT |
| | TREATMENT AREAS CAN BE 240, BUT OUTPATIENT IS 100SF PER |
| | OCCUPANT.PLEASE CLARIFY USE OF THE SPACE OR REVISE |
| | THE OCCUPANT LOAD ACCORDINGLY (100SF PER PERSON). |
| | |
| | 5.PREVIOUS COMMENT NOT ADDRESSED.PLEASE SEE SHEET |
| | A5.1, DETAILS 20 AND 21, XRAY ROOM IS MARKED AS ED120, |
| | BUT SHEET A2.2 XRAY IS MARKED AS ED121.EITHER THE |
| | FLOOR PLAN OR THE DETAILS ARE INCORRECT AS THEY DO NOT |
| | MATCH.DETAILS FOR XRAY ROOM IS REQUIRED BY FBC435; |
| | PLEASE CLARIFY LOCATION/CORRELATE DETAILS WITH THE |
| | FLOOR PLAN. |
| | |
| | 6-7. ADDRESSED. |
| | |
| | NEW COMMENT: |
| | |
| | 8.ALL SHEETS ARE TO INCLUDE THE DATE, FS481, |
| | FAC61G1-15.23.002.THE ATTORNEY FOR THE FLORIDA BOARD |
| | OF ARCHITECTS HAS ADVISED THAT THE REVISION DATE DOES |
| | NOT MEET THIS REQUIREMENT; THE SIGNATURE/SEAL MUST BE |
| | DATED. |
| | |
| | 9.THE ARCHITECT IS TO CERTIFY THE ENERGY CALCS. |
| | ENERGY CALCS TO BE IN A CODE COMPLIANT FORMAT; PLEASE |
| | SEE ELECTRIC COMMENTS (INCORRECT YEAR USED, FBC2001 |
| | RATHER THAN FBC2004). |
| | |
| | 10. SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC, |
| | FBC13-103.1. |
| | |