| 2008-02-29 15:08:03 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | *** THE FALLOWING NOTES PERTAIN TO MECHANICAL PLAN PAGE |
| | M1.01 NEW CONSTRUCTION. |
| | |
| | 1) SEE 16X12 RETURN AIR DUCT FROM ROOM ED118 TO WEST |
| | CORRIDOR IS PENETRATING A 1HR. RATED PARTITION (SEE |
| | YELLOW HIGH LIGHT ON PLAN), PLEASE COMPLY WITH 2004 |
| | FBC/M 607.5.3. |
| | |
| | 2) SEE 16X10 SUPPLY AIR DUCT SAME AS ABOVE IS |
| | PENETRATING A 1HR. RATED PARTITION (SEE YELLOW HIGH |
| | LIGHT ON PLAN), PLEASE COMPLY WITH 2004 FBC/M 607.5.3. |
| | |
| | 3) SEE 12X8 SUPPLY AIR DUCT IN WEST CORRIDOR IS |
| | PENETRATING A 1HRS. RATED PARTITION (SEE YELLOW HIGH |
| | LIGHT ON PLAN), PLEASE COMPLY WITH 2004 FBC/M 607.5.4 |
| | OR STATE THE EXCEPTION BEING MET. |
| | |
| | 4) SEE 2HRS RATED PARTITION SEPARATING THE NORTH PART |
| | OF THE WING FROM THE SOUTH 6 DUCTS HAVE FIRE DAMPERS |
| | BUT NEED TO BE SMOKE DAMPERS (SEE YELLOW HIGH LIGHT ON |
| | PLAN), PLEASE CORRECT PER 2004 FBC/M 607.5.4 OR STATE |
| | THE EXCEPTION BEING MET. |
| | |
| | 5) SEE 18X16 AND 26X18 DUCTS PENETRATING THE EAST END |
| | OF THE 2HRS RATED PARTITION (SEE YELLOW HIGH LIGHT ON |
| | PLAN), PLEASE COMPLY WITH 2004 FBC/M 607.5.4 OR STATE |
| | THE EXCEPTION BEING MET. |
| | |
| | 6) SEE 54X16 RETURN AIR DUCT AT THE SOUTHEAST CORNER OF |
| | PLAN IS PENETRATING A 1HR. RATED PARTITION (SEE YELLOW |
| | HIGH LIGHT ON PLAN), PLEASE COMPLY WITH 2004 FBC/M |
| | 607.5.3. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |