Plan Review Notes
Plan Review Notes For Permit 08020108
Permit Number 08020108
Review Stop M
Sequence Number 1
Notes
Date Text
2008-02-29 15:08:03PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 *** THE FALLOWING NOTES PERTAIN TO MECHANICAL PLAN PAGE
 M1.01 NEW CONSTRUCTION.
  
 1) SEE 16X12 RETURN AIR DUCT FROM ROOM ED118 TO WEST
 CORRIDOR IS PENETRATING A 1HR. RATED PARTITION (SEE
 YELLOW HIGH LIGHT ON PLAN), PLEASE COMPLY WITH 2004
 FBC/M 607.5.3.
  
 2) SEE 16X10 SUPPLY AIR DUCT SAME AS ABOVE IS
 PENETRATING A 1HR. RATED PARTITION (SEE YELLOW HIGH
 LIGHT ON PLAN), PLEASE COMPLY WITH 2004 FBC/M 607.5.3.
  
 3) SEE 12X8 SUPPLY AIR DUCT IN WEST CORRIDOR IS
 PENETRATING A 1HRS. RATED PARTITION (SEE YELLOW HIGH
 LIGHT ON PLAN), PLEASE COMPLY WITH 2004 FBC/M 607.5.4
 OR STATE THE EXCEPTION BEING MET.
  
 4) SEE 2HRS RATED PARTITION SEPARATING THE NORTH PART
 OF THE WING FROM THE SOUTH 6 DUCTS HAVE FIRE DAMPERS
 BUT NEED TO BE SMOKE DAMPERS (SEE YELLOW HIGH LIGHT ON
 PLAN), PLEASE CORRECT PER 2004 FBC/M 607.5.4 OR STATE
 THE EXCEPTION BEING MET.
  
 5) SEE 18X16 AND 26X18 DUCTS PENETRATING THE EAST END
 OF THE 2HRS RATED PARTITION (SEE YELLOW HIGH LIGHT ON
 PLAN), PLEASE COMPLY WITH 2004 FBC/M 607.5.4 OR STATE
 THE EXCEPTION BEING MET.
  
 6) SEE 54X16 RETURN AIR DUCT AT THE SOUTHEAST CORNER OF
 PLAN IS PENETRATING A 1HR. RATED PARTITION (SEE YELLOW
 HIGH LIGHT ON PLAN), PLEASE COMPLY WITH 2004 FBC/M
 607.5.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]