| Plan Review Notes For Permit 08020108 |
| Permit Number |
08020108 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-03-13 13:53:16 | ***DENIED*** | | | | | | 1) PLEASE SEE MECHANICAL COMMENTS REGARDING DUCT | | | LOCATIONS RELATIVE TO FIRE RATED PARTITIONS. | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 3) SITE TO BE CLEANED OF EXCESSIVE CONSTRUCTION DEBRIS | | | DAILY. | | | | | | 4) PLEASE ADD NOTE TO DOOR SCHEDULE INDICATING FIRE | | | RATED DOORS TO BE PROVIDED WITH UL LISTED CLOSERS. | | | | | | 5) PLEASE IDENTIFY DOORS PROVIDED WITH PANIC HARDWARE | | | IN DOOR SCHEDULE. | | | | | | 6) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR | | | WALLS AND CEILING. | | | | | | 7) BUILDING FIRE PROTECTION EQUIPMENT TO BE MAINTAINED. | | | IN ADDITION TO THE FIRE SPRINKLER SYSTEM, SEPARATE SHOP | | | DRAWINGS AND PERMIT REQUIRED FOR FIRE ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|