| Date |
Text |
| 2008-02-11 10:45:09 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE:PLEASE SEE THE PLANS NEED TO CONTAIN THE |
| | FOLLOWING RELEVANT CODES STATED FOR DESIGN. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ** CODES NEED TO BE ON BOTH ARCHITECTURAL AND |
| | ELECTRICAL SHEETS. |
| | |
| | ** PLEASE SEE THERE PLACES ON COVER SHEET WHICH STATES |
| | A 2006 FBC INSTEAD OF 2004. |
| | PLEASE KNOW EVEN WHEN THE CODE CHANGES ON THE FOLLOWING |
| | CODE CHANGE CYCLE IT WILL BE THE 2007. THIS IS NOTED |
| | FOR INFORMATION ONLY. |
| | PLEASE ADJUST NOTES. |
| | |
| | 2) NOTE: PLEASE CLARIFY THE GFI PROTECTIONFOR |
| | EXISTING OR NEW PER517.17B IN THE SELECTIVE |
| | COORDINATION DOCUMENTS SUBMITTED PER 240.12 AND ON |
| | RISER ON SHEET E0.2. |
| | |
| | 3) NOTE: PLEASE SEE THE LIGHTING PLANS CONTAIN OS |
| | DEVICES HOWEVER THESE ARE LISTED ON SYMBOL LEGEND AND |
| | DO NOT CONTAIN ANY MAXIMUM TIMES. |
| | PLEASE SUBMIT DETAIL FOR DEVICE. ARE THESE LOW VOLTAGE? |
| | LINE VOLTAGE? CONTAIN POWER PACKS ETC? |
| | 13-415.1.ABC.1.1, .1.2 (WITH EXCEPTIONS OF SOME |
| | AREAS). |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION NEEDED ON |
| | PLANS. |
| | |
| | 4) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR FA |
| | DEVICES PER FBC 11-4.28.1,.2 AND .3 (4). |
| | |
| | 5) NOTE: PLEASE SEE 450.3 WHICH PERMITS A MAXIMUM OVER |
| | CURRENT PROTECTION OF THE TRANSFORMER AT 125%. THERE IS |
| | EXCEPTIONS (SEE TABLE NOTES) AND IF MEETING EXCEPTIONS |
| | PLEASE SUBMIT ALL INFORMATION ON TYPE OF TRANSFORMER. |
| | IF THIS IS A STANDARD TRANSFORMER NOT MEETING |
| | EXCEPTIONS, PLEASE ADJUST FOR 125% MAX. |
| | TXRL3. |
| | |
| | ** PLEASE SEE TCGLD AND TGLD ARE OK. |
| | |
| | ** PLEASE SEE EXISTING TCGLC AND TGLC ARE TOO HIGH |
| | DEPENDING ON TRANSFORMER. THIS COULD BE A SAFETY/FIRE |
| | HAZARD ISSUE. |
| | PLEASE CONFIRM TYPE OF TRANSFORMER ETC AT THIS TIME. |
| | TCGLC SHOULD BE MAX 50AMPS AND TGLC SHOULD BE 70AMPS |
| | MAX. |
| | |
| | 6) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE/REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |