2008-02-11 10:45:09** DENIED REVIEW **
  
 1) NOTE:PLEASE SEE THE PLANS NEED TO CONTAIN THE
 FOLLOWING RELEVANT CODES STATED FOR DESIGN.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** CODES NEED TO BE ON BOTH ARCHITECTURAL AND
 ELECTRICAL SHEETS.
  
 ** PLEASE SEE THERE PLACES ON COVER SHEET WHICH STATES
 A 2006 FBC INSTEAD OF 2004.
 PLEASE KNOW EVEN WHEN THE CODE CHANGES ON THE FOLLOWING
 CODE CHANGE CYCLE IT WILL BE THE 2007. THIS IS NOTED
 FOR INFORMATION ONLY.
 PLEASE ADJUST NOTES.
  
 2) NOTE: PLEASE CLARIFY THE GFI PROTECTIONFOR
 EXISTING OR NEW PER517.17B IN THE SELECTIVE
 COORDINATION DOCUMENTS SUBMITTED PER 240.12 AND ON
 RISER ON SHEET E0.2.
  
 3) NOTE: PLEASE SEE THE LIGHTING PLANS CONTAIN OS
 DEVICES HOWEVER THESE ARE LISTED ON SYMBOL LEGEND AND
 DO NOT CONTAIN ANY MAXIMUM TIMES.
 PLEASE SUBMIT DETAIL FOR DEVICE. ARE THESE LOW VOLTAGE?
 LINE VOLTAGE? CONTAIN POWER PACKS ETC?
 13-415.1.ABC.1.1, .1.2 (WITH EXCEPTIONS OF SOME
 AREAS).
 FBC 106.1.2 FOR ADDITIONAL INFORMATION NEEDED ON
 PLANS.
  
 4) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR FA
 DEVICES PER FBC 11-4.28.1,.2 AND .3 (4).
  
 5) NOTE: PLEASE SEE 450.3 WHICH PERMITS A MAXIMUM OVER
 CURRENT PROTECTION OF THE TRANSFORMER AT 125%. THERE IS
 EXCEPTIONS (SEE TABLE NOTES) AND IF MEETING EXCEPTIONS
 PLEASE SUBMIT ALL INFORMATION ON TYPE OF TRANSFORMER.
 IF THIS IS A STANDARD TRANSFORMER NOT MEETING
 EXCEPTIONS, PLEASE ADJUST FOR 125% MAX.
 TXRL3.
  
 ** PLEASE SEE TCGLD AND TGLD ARE OK.
  
 ** PLEASE SEE EXISTING TCGLC AND TGLC ARE TOO HIGH
 DEPENDING ON TRANSFORMER. THIS COULD BE A SAFETY/FIRE
 HAZARD ISSUE.
 PLEASE CONFIRM TYPE OF TRANSFORMER ETC AT THIS TIME.
 TCGLC SHOULD BE MAX 50AMPS AND TGLC SHOULD BE 70AMPS
 MAX.
  
 6) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE/REVIEWER.
  