| 2008-02-27 17:30:24 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.REVISE GOVERNING CODE (FBC2004 WITH 2007 |
| | SUPPLEMENTS/REVISIONS).X1.1. |
| | |
| | 2.CLARIFY BUILDING TYPE 1B WITH FIRE RESISTANCE OF |
| | 3-2-2.PLEASE DECLARE REQUIRED FIRE RESISTANCE BY |
| | COMPONENT (WALL, FLOOR, ROOF, ETC.). FBC TABLE 602. |
| | |
| | 3.DECLARE OCCUPANCY FBC3. |
| | |
| | 4.AL2.1, OCCUPANT LOAD IS DECLARED BASED ON |
| | 240SF/OCCUPANT.SEE FBC TABLE 1004.1.2, CLARIFY USE OF |
| | THIS AREA.IS THIS AN EMERGENCY ROOM OR AN INPATIENT |
| | TREATMENT AREA?THE AREA IS LABELED PEDIATRIC ED AND |
| | HAS AN AMBULANCE PORTE COCHERE OUTSIDE.PLEASE REVISE |
| | OCCUPANT LOAD AND RELATED REQUIREMENTS. |
| | |
| | 5.SHEET A5.1, ROOM 121 XRAY APPEARS TO HAVE AN |
| | INCORRECT ROOM DESIGNATION AND DETAIL MARKER 21 A5.1 |
| | APPEARS TO BE MISSING FROM THE FLOOR PLAN A2.2, OR THE |
| | ROOM 120 ON THE FLOOR PLAN IS MISLABELED AS EXISTING |
| | TREATMENT. |
| | |
| | 6.DETAIL MARKER 7 A5.3 (TOILET) ON SHEET A2.2 DOES |
| | NOT CORRELATE WITH THE DETAIL (CORRIDOR). |
| | |
| | 7.SHOW MANEUVERING CLEARANCE PULL SIDE FBC11-25 FOR |
| | THE DOOR AT RECEPTION ED131. |
| | |
| | |