Plan Review Notes
Plan Review Notes For Permit 08020104
Permit Number 08020104
Review Stop ENG
Sequence Number 2
Notes
Date Text
2008-03-28 13:38:36FAILED FOR FOLLOWING REASONS:
  
 1.PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 DWG C-5 OF C-7 SAYS SEE DWG A1.3,THIS DWG WAS NOT IN
 THE PACKAGE YOU SUBMITTED. PLEASE SUBMIT DWG A1.3
 SHOWING LOCATION & DETAILS OF DUMPSTER PER CITY
 STANDARD.
  
 3. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 4. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 5. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT&STORM WATER QUALITY CALCULATIONS. STORM
 WATER CALS MUST BE APPROVED FROM 100045TH STREET
 ENGINEERING SERVICES BEFORE WE APPROVED.
  
 YOUR SFWMD COPY WAS ISSUED IN 1992. WE DO NOT ALLOW
 MORE THAN 5 YEAR OLD PERMIT. MAY BE YOU TAKE IT BACK TO
 SFWMD FOR REAPPROVAL.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723