| Date |
Text |
| 2008-04-10 15:14:44 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.THE VALUE FOR THE SITEWORK APPEARS LOW.PLEASE |
| | GIVE A BREAKDOWN OF VALUE, BY SQUARE FOOT, SUMMARIZING |
| | ALL WORK TO BE PERFORMED UNDER THIS SITEWORK PERMIT. |
| | |
| | 2.THE PLANS DO NOT APPEAR ACCURATE AS TO SCOPE OF |
| | WORK.FOR INSTANCE, A HATCHED AREA IS SHOWN IN THE |
| | CENTER OF THE LARGE BUILDING AS AN ADDITION, BUT MY |
| | UNDERSTANDING IS THAT HALF OF THE BUILDING WAS TORN |
| | DOWN AND IS IN THE PROCESS OF BEING RECONSTRUCTED, WEST |
| | SIDE.CODE REQUIREMENTS FOR ACCESSIBILITY MAY BE |
| | AFFECTED BY SCOPE OF WORK, SEE OTHER COMMENTS. |
| | |
| | 3.SEE FBC11-4.6.2, ACCESSIBLE PARKING SPACES SHALL BE |
| | DISPERSED AND LOCATED CLOSEST TO THE ACCESSIBLE |
| | ENTRANCES. |
| | |
| | 4.AN EXISTING RAMP IS SHOWN ON THE WEST SIDE OF THE |
| | BUILDING.IS THIS RAMP COMPLIANT FOR ACCESSIBILITY |
| | FBC11-4.8 OR IS THIS FOR LOADING? |
| | |
| | 5.SHOW THE ACCESSIBLE ROUTE AT THE REAR OF THE |
| | BUILDING, NORTH SIDE.THE EXIT DOOR APPEARS TO HAVE A |
| | LANDING, SEE FBC11-4.1.3(9), SAME NUMBER OF ACCESSIBLE |
| | MEANS OF EGRESS SHALL BE PROVIDED AS REQUIRED FOR |
| | EXITS.THE GRAPHIC SHOWS LANDSCAPING IN THIS AREA.IS |
| | THIS A REQUIRED ACCESSIBLE EXIT?THE ACCESSIBLE ROUTE |
| | TO GET AWAY FROM THE BUILDING IS NOT CLEARLY IDENTIFIED |
| | ON THE NORTH, EAST, AND WEST SIDES.IT IS MY |
| | UNDERSTANDING THAT A PORTION OF THE BUILDING IS NEW |
| | CONSTRUCTION; WAS TORN DOWN AND REBUILT. |
| | |
| | 6. SHOW ALL REQUIRED DETECTABLE WARNINGS, |
| | FBC11-4.29.5. |
| | |
| | 7. DECLARE TOTAL NUMBER OF PARKING SPACES AND NUMBER OF |
| | ACCESSIBLE SPACES, FBC11-4.1.2(5)(A). |
| | |
| | 8.PLEASE SEE FBC11-4.1.6, OWNER HAS AN OBLIGATION TO |
| | PROVIDE ACCESSIBLE FEATURES EVEN WHEN THOSE FEATURES |
| | ARE NOT BEING ALTERED.THIS CODE SECTION AFFECTS OTHER |
| | COMMENTS.PLEASE CONTACT ME IF YOU NEED ASSISTANCE IN |
| | DETERMINING SCOPE OF REQUIRED CODE COMPLIANCE. |
| | |
| | 9. SEE ADA 4.29.2* DETECTABLE WARNINGS ON WALKING |
| | SURFACES. DETECTABLE WARNINGS SHALL CONSIST OF RAISED |
| | TRUNCATED DOMES WITH A DIAMETER OF NOMINAL 0.9 IN (23 |
| | MM), A HEIGHT OF NOMINAL 0.2 IN (5 MM) AND A |
| | CENTER-TO-CENTER SPACING OF NOMINAL 2.35 IN (60 MM) AND |
| | SHALL CONTRAST VISUALLY WITH ADJOINING SURFACES, EITHER |
| | LIGHT-ON-DARK, OR DARK-ON-LIGHT. |
| | |
| | A. REVISE CONCRETE SIDEWALK CURB RAMP DETAIL, SHEET C3. |
| | HTTP://WWW.ACCESS-BOARD.GOV/ADAAG/DWS/UPDATE.HTM. |
| | TACTILE SURFACE SHOWN, PLEASE REVISE DETAIL TO SHOW |
| | TRUNCATED DOMES. |
| | |
| | B. REVISE CONCRETE SIDEWALK CURB RAMP DETAIL, SHEET C3, |
| | TO SHOW THE VISUAL CONTRAST REQUIRED.IF THE DESIGN |
| | INTENT AND COMPLIANCE ARE NOT CLEAR, CALCULATIONS PER |
| | ADA4.29.2 MAY BE REQUIRED. |
| | |
| | 10. SHOW ALL REQUIRED DETECTABLE WARNING LOCATIONS ON |
| | THE PLAN, HAZARDOUS VEHICULAR AREAS, FBC11-4.29.5. |
| | |
| | 11. C2, THE GRAPHIC FOR THE ACCESSIBLE ROUTE AND SOME |
| | OF THE PARKING LOT STRIPING IS THE SAME AS BUILDING |
| | ADDITION AREA.PLEASE REVISE SO THAT THE TWO ARE |
| | CLEARLY DEFINED.IDENTIFICATION OF THE STRIPING WOULD |
| | BE HELPFUL. |
| | |
| | 12. SHEET C4, SECTION AA AND BB, PLEASE ADVISE AS TO |
| | WHERE THESE SECTIONS ARE SHOWN ON THE PLAN.REVISE TO |
| | CLEARLY SHOW COMPLIANCE WITH DETECTABLE WARNING |
| | REQUIREMENTS. |
| | |
| | 13. C1, C2 SHOW EXISTING HANDICAP RAMPS AT VEHICULAR |
| | APPROACH (STREET TO PARKING LOT) AREAS.PLEASE PROVIDE |
| | A DETAIL TO SHOW COMPLIANCE WITH FBC11-4.29.5; NOTE |
| | THAT EXITING IS TO THE PUBLIC WAY FBC11, DEFINITIONS. |
| | |
| | 14. SEE ATTACHED ACCESSIBLE PARKING DETAIL.PLEASE |
| | REVISE C4 TO BE CONSISTENT WITH THIS DETAIL WHICH IS |
| | REQUIRED BY MUNICIPAL CODE.NOTE THAT THE WHEEL STOP |
| | DIMENSION, ACCESSIBILITY SYMBOL COLOR AND SIZE DO NOT |
| | CONFORM TO THE STANDARD ADOPTED. |
| | |
| | 15. PROVIDE A TYPICAL ACCESSIBLE PARKING SIGN, |
| | FBC11.4.6.4. |