| Notes |
| Date |
Text |
| 2008-12-07 14:44:34 | REVIEW #: 3RD | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | NOTE: MECHANICAL PLANS HAVE NOW BEEN SUBMITTED FOR | | | REVIEW FOR THE FIRST TIME. ALL PREVIOUS REVIEW COMMENTS | | | HAVE BEEN ADDRESSED. PLEASE ADDRESS THE FOLLOWING | | | RELATED TO NEW MECHANICAL PLANS: | | | | | | 1. THE GUEST AREA AND 2ND FLOOR, ALL DUCTS ARE MISSING | | | SIZES. PLEASE SHOW THE SIZE OF ALL AIR DISTRIBUTION | | | COMPONENTS TO BE INSTALLED IN ORDER TO DEMONSTRATE | | | COMPLIANCE WITH FBCR M1601.1 AND M1601.3 AS WELL AS | | | M1602.4 FOR BALANCED RETURN AIR. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|