| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | COMMENTS FOR SHEETE2. |
| | |
| | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | |
| | 2} LOCATE ALL SERVICE EQUIPMENT ON THE RISER DIAGRAM. |
| | IF PANEL "B" IS THE GUEST HOUSE PANEL IT MUST HAVE A |
| | MAIN BREAKER OR A DISCONNECT PER 225.31, LOCATED PER |
| | 225.32 AND GROUNDED PER 250.32. |
| | |
| | 3} THE WASHER /LAUNDRY CIRCUIT IS NOT LISTED ON THE |
| | PANEL SCHEDULE. 210.11(C)(2). |
| | |
| | 4} THERE ARE TWO GUEST HOUSE WATER HEATERS LISTED IN |
| | PANEL "B", BUT ONLY ONE SHOWN ON THE FLOOR PLAN, |
| | CORRELATE SAME.VERIFY THE MAIN HOUSE WATER HEATER IS |
| | FED FROM PANEL "B", IF IN FACT PANEL "B" IS LOCATED IN |
| | THE GUEST HOUSE. |
| | |
| | 5} A SERVICE RECEPTACLE PER 210.63 IS REQUIRED FOR THE |
| | ACU FOR THE GUEST HOUSE. |
| | |
| | 6} THE LOAD CALCULATION LISTS ALL HEAT STRIPS AT 10000W |
| | WHICH DOES NOT CORRELATE WITH THE PANEL SCHEDULE OR |
| | MANUFACTURERS SPEC'S ON M1. |
| | |
| | 7} A SEPARATE PERMIT IS REQUIRED FOR THE GENERATOR |
| | SHOWN ON THE RISER DIAGRAM UNLESS ALL DOCUMENTS |
| | REQUIRED FOR A RESIDENTIAL GENERATOR ARE SUBMITTED WITH |
| | THIS APPLICATION. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/805-6676 |
| | |