| Date |
Text |
| 2008-08-15 07:26:47 | 2004 FBC W/2007 REVISIONS |
| | ADDITION AND REMODEL |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE NOTICE OF COMMENCEMENT HAS EXPIRED AND WILL NEED |
| | TO BE RE-RECORDED. THE ACTUAL WORK IS REQUIRED TO START |
| | WITHIN 90 DAYS OF THE RECORDING. FS 713 |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SHEET C1 WHICH CONTAINED THE DESIGN CRITERIA WAS NOT |
| | RE-SUBMITTED. PLEASE SPECIFY DESIGN CRITERIA ON THE |
| | PLANS. ( APPLICABLE CODE, WINDSPEED, EXPOSURE CATEGORY, |
| | ETC.) FBC R301.2 |
| | |
| | 4) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS SEPARATED |
| | BY LESS THAN 6 FEET (1828 MM) SHALL HAVE NOT LESS THAN |
| | A ONE-HOUR FIRE-RESISTIVE RATING WITH EXPOSURE FROM |
| | BOTH SIDES. PROJECTIONS SHALL NOT EXTEND TO A POINT |
| | CLOSER THAN 4 FEET (1220 MM) FROM AN ADJACENT |
| | PROJECTION OR WALL. THE PLANS SHOW LESS THAN 6 FEET TO |
| | THE PROPERTY LINES AT GARAGE AND SECOND FLOOR ADDITION. |
| | THEREFORE, THE DISTANCE TO THE STRUCTURES ON THE |
| | ADJACENT LOT ARE REQUIRED TO BE NOTED ON THE SITE PLAN |
| | AND IF LESS THAN 6 FEET THEN THE WALLS MUST HAVE ONE |
| | HOUR FIRE RATING AND HAVE NO OPENINGS(R302.2). |
| | |
| | 5) PLEASE DO NOT TAPE THE RAS 117 CALCULATIONS TO THE |
| | SIGNED AND SEALED PLANS (SEE SHEET A4.0) . SOME OF THE |
| | TEXT IS MISSING FROM THE BOTTOM RIGHT SIDE OF THE RAS |
| | CALCULATIONS. THE PRODUCT APPROVAL THAT WAS SUBMITTED |
| | DOES NOT CORRESPOND WITH THE CALCULATIONS. THE PRODUCT |
| | APPROVAL IS FOR A GAF BUILT-UP ROOF SYSTEM NOA NO. |
| | 03-0501.05 AND THE CALCULATIONS ARE FOR A FIRESTONE |
| | SYSTEM NOA NO. 05-0830.10. |
| | PLEASE COORDINATE. |
| | |
| | 6) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE |
| | ENTRY DOOR IS NON-IMPACT FOR THE GLAZING. SUBMIT |
| | PRODUCT APPROVALS FOR THE STORM PANELS FOR THIS DOOR. |
| | SUBMIT AN INSTALLATION SCHEDULE, SPECIFY THE FASTENER |
| | TYPE, FASTENER SPACING, MOUNT TYPE, EDGE DISTANCE, |
| | ETC. |
| | |
| | 7) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE |
| | SIGNED BY THE OWNER/AGENT. FBC CHAPTER 13-6. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |