| 2008-02-14 15:26:07 | ***FAILED*** |
| | |
| | |
| | 1)INDICATE SETBACK DIMENSIONS FROM ALL NEW |
| | CONSTRUCTION TO ALL PROPERTY LINES.ALL NEW |
| | CONSTRUCTION SHALL COMPLY WITH CURRENT REGULATIONS. |
| | PURSUANT TO SECTION 94-74 OF THE CITY'S ZONING AND LAND |
| | DEVELOPMENT REGULATIONS (ZLDRS): |
| | |
| | MINIMUM SETBACKS FOR PRINCIPAL BUILDING. |
| | A.FRONT: 25 FEET; |
| | B.CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60 |
| | FEET WIDE; |
| | C.REAR: 15 FEET OR TEN PERCENT OF DEPTH, WHICHEVER |
| | IS LESS; |
| | D.SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL. |
| | |
| | THE SECOND FLOOR ADDITION AT THE REAR OF THE STRUCTURE |
| | DOES NOT MEET THE MINIMUM REQUIRED SETBACK OF 5' TO THE |
| | PROPERTY LINE.PLEASE REVISE. |
| | |
| | 2)INDICATE SETBACK DIMENSIONS FROM ANY PROPOSED OR |
| | RELOCATED A/C EQUIPMENT (IF ANY) TO ALL PROPERTY LINES. |
| | AS PER SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL |
| | EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A |
| | REQUIRED SETBACK. |
| | |
| | 3)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND |
| | LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF |
| | THE PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE, |
| | LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE |
| | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.PLEASE |
| | SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION |
| | 94-442 AND 94-445 OF THE ZLDRS. |
| | |
| | 4)INDICATE SEPARATION DISTANCE FROM EXISTING |
| | PRINCIPAL STRUCTURE TO THE PROPOSED GARAGE ADDITION. |
| | NOTE: MUST MAINTAIN A MINIMUM OF 6' SEPARATION. |
| | |
| | 5)INDICATE HEIGHT DIMENSIONS FROM GRADE TO THE |
| | MIDPOINT OF THE UPPERMOST ROOF'S PITCH.PURSUANT TO |
| | SECTION 94-74 OF THE ZLDRS:MAXIMUM HEIGHT FOR |
| | PRINCIPAL BUILDING = 30'.ALSO INDICATE HEIGHT |
| | DIMENSION OF THE CHIMNEY FROM GRADE TO THE UPPERMOST |
| | POINT OF THE CHIMNEY.CLARIFY IF CHIMNEY IS PROPOSED |
| | OR EXISTING, IF PROPOSED, THE CHIMNEY SHALL NOT EXCEED |
| | 33' IN HEIGHT MEASURED FROM GRADE. |
| | |
| | 6)INDICATE ALL OVERHANG DIMENSIONS, AND BALCONY |
| | DIMENSIONS FROM THE WALL TO THE OUTERMOST POINT. |
| | PURSUANT TO SECTION 94-305 OF THE ZLDRS:STRUCTURAL |
| | OVERHANGS, INCLUDING BUT NOT LIMITED TO BALCONIES, |
| | CORNICES, GUTTERS, EAVES, AND ROOF OVERHANG PROJECTIONS |
| | SHALL NOT EXTEND FARTHER THAN THREE FEET INTO ANY |
| | SETBACK. |
| | |
| | |
| | NOTE:ACCESSORY STRUCTURE SHALL NOT EXCEED 75 PERCENT |
| | OF THE GROSS FLOOR AREA OF THE PRIMARY STRUCTURE WITH A |
| | MAXIMUM FLOOR AREA OF 1,000 SQUARE FEET. |
| | |
| | NOTE:AS THERE ARE DIMENSIONALLY NONCONFORMING |
| | STRUCTURES ON THE LOT WITH RESPECT TO THE SETBACK |
| | REQUIREMENTS, NO NEW NONCONFORMITY SHALL BE CREATED AND |
| | NO EXISTING NONCONFORMITY SHALL BE INCREASED. |
| | |
| | |
| | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, |
| | ZONING TECHNICIAN (561)805-6720 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, |
| | ZONING TECHNICIAN (561)805-6720 |