| 2008-02-07 10:02:58 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) THE MAIN HOUSE AND THE GUEST HOUSE CAN NOT BE ON THE |
| | SAME ENERGY CALCULATION. PLEASE SUBMIT SEPARATE ENERGY |
| | CALCULATIONS FOR EACH BUILDING, SEE 2004 FBC |
| | 13-101.2.5.1. |
| | |
| | 2) PLEASE HAVE THE REVISED ENERGY CALCULATIONS SIGNED |
| | BY OWNER/AGENT ALSO, SEE 2004 FBC 13-600.3.ABC.2. |
| | |
| | 3) ENERGY CALCULATIONS LINE 8B DOES NOT SHOW THE RAISED |
| | WOOD FLOOR OR INSULATION, SEE 2004 FBC 13-605.2.A.1.1 |
| | AND 13-605.1.C.2. PLEASE CORRECT ALSO THE PLANS IF |
| | NEEDED. |
| | |
| | 4) SHOW AN A/C EQUIPMENT SCHEDULE WITH ALL THE |
| | PERTINENT INFORMATION ON THE MECHANICAL PLAN, SEE 2004 |
| | WPB AMEND. 106.3.5.4 (10). |
| | |
| | 5) SHOW ALL THE BATHROOM EXHAUST FANS ON THE MECHANICAL |
| | PLAN AS THEY ARE ON THE ELECTRICAL PLAN, SEE 2004 FBC/R |
| | R303.3 EXCEPT. |
| | |
| | 6) SHOW THE LOCATION OF THE GUEST HOUSE A/C CONDENSER |
| | UNIT ON THE MECHANICAL AND ELECTRICAL PLANS, SEE 2004 |
| | FBC/R M1307. |
| | |
| | 7) A/C SYSTEM 2 COOLING LOAD CALCULATIONS ARE CALLING |
| | FOR 23,601 TOTAL COOLING BTU'S. A 3 TON A/C SYSTEM AT |
| | 34,200 TOTAL COOLING BTU'S WOULD BE TO LARGE AS YOU CAN |
| | ONLY GO 15% OVER THE COOLING LOAD CALCULATION, SEE 2004 |
| | FBC 13-607.1.ABC.1.1. PLEASE CORRECT. |
| | |
| | 8) A/C SYSTEM 3 COOLING LOAD CALCULATIONS ARE CALLING |
| | FOR 23,046 TOTAL COOLING BTU'S. A 3 TON A/C SYSTEM AT |
| | 34,200 TOTAL COOLING BTU'S WOULD BE TO LARGE AS YOU CAN |
| | ONLY GO 15% OVER THE COOLING LOAD CALCULATION, SEE 2004 |
| | FBC 13-607.1.ABC.1.1. PLEASE CORRECT. |
| | |
| | 9) ELECTRICAL PLAN E-2 IS SHOWING A GAS INSTA-HOT WATER |
| | HEATER IN THE GARAGE OF THE GUEST HOUSE, THIS MAY BE A |
| | CONFINED SPACE. PLEASE SUBMIT COMBUSTION AIR |
| | CALCULATIONS, SEE 2004 FBC/R G2407.5. |
| | |
| | 10) PLEASE SUBMIT DETAILED MANUFACTURER'S |
| | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE |
| | GAS INSTA-HOT WATER HEATER AND ALL OTHER GAS APPLIANCES |
| | BEING INSTALLED. |
| | |